Mammography

Room Code MAMMO-I
Net Room Area Briefed 16
Hours of Operation Available 24 Hours
Occupancy 1 patient; Up to 2 staff assisting
Description / Special Requirements X-ray room for mammography imaging procedures, with change area within the room. Acoustics: Acoustic privacy required Body Protected electrical area Additional Design Considerations: - Radiation shielding as advised by Radiation Consultant - Cable ducts between X-ray table and control area may be required - 'X-ray in Use' lights required oustide each entry door
Amendment 24.10.2010 First Draft 21.04.2011 Services modified 03.09.2023 RDS reviewed

Fabric and outline specifications

ID Fabric Material Finish Specification Selection Remarks
5062 Ceiling Acoustic Prefinished Drop-in tiles, 600x600 mm
8040 Door protection Composite Prefinished PVC To door frame
3022 Wall finish Resinate, 6mm Prefinished Splashback to basin, other smooth impervious finish also acceptable
4159 Cornice Aluminium Powdercoat Angle flush against wall, in line with ceiling grid
3000 Wall finish Paint Acrylic, washable
8010 Door protection Composite Prefinished PVC Protection plate to 900mm AFFL
9130 Doors Solid Core Paint 1 1/2 leaf, with lead shielding 1400mm clear opening
1000 Floor finish Vinyl Standard slip resistant Seamless, coved
2000 Skirting Vinyl Prefinished Floor vinyl coved, 150mmH

Fittings and Furniture (FF)

ID Description Category Group Qty Selection / Remarks
2150 Chair: patient Furniture/ Fitting 3 1 to change area
8299 Chair: mammography MEQ - Imaging 3 1 part of mammography system
2100 Chair: ergonomic, office Furniture/ Fitting 3 1 to desk
3400 Coathook Metalwork 1 2 to change area, 1 @1200H
4350 Cupboard: tall Furniture/ Fitting 1 1 adjustable shelves
4700 Curtain track: privacy screen Metalwork 1 1 to change area
5250 Curtain: privacy screen Furniture/ Fitting 3 1 to change area
5900 Desk Furniture/ Fitting 3 1
6152 Dispenser: disposable glove Furniture/ Fitting 2 1
6154 Dispenser: paper/ hand towel Furniture/ Fitting 2 1 to basin
6158 Dispenser: soap antiseptic Furniture/ Fitting 2 1 to basin
13700 Mirror Metalwork 1 1 to change area
20000 Shelving unit: adjustable Furniture/ Fitting 1 1 above desk, optional
8404 Bracket: sharps disposal MEQ - General 2 1
8321 Suction bottle MEQ - General 3 1
8318 Suction adapter MEQ - General 3 1
8297 Bracket: suction bottle MEQ - General 2 1
8309 Oxygen flowmeter MEQ - General 3 1
8313 Rack: lead apron MEQ - Imaging 1 1
9117 Sharps disposal: wall mounted, 7L MEQ - General 2 1
10061 Waste bin: General, 20 Litres Furniture/ Fitting 3 1

Fixtures, Equipment and associated Services (FE)

ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
2800 Basin: handwash, Type B 1 1 ___ ___ yes ___ yes yes yes ___
40404 Tapware: sensor 1 1 yes ___ yes yes yes ___ ___ ___ straight spout
54510 Telephone: handset, standard 3 1 ___ yes ___ ___ ___ ___ ___ ___ to desk
9097 X-ray unit: mammography, 3D 2 1 yes yes ___ ___ ___ ___ ___ ___ with control panel
9092 Control console 1 1 yes yes ___ ___ ___ ___ ___ ___ part of mammography system

Services

ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 3 1- desk; 1- patient services panel; 1- mammography control console
5000 Airconditioning HVAC
2242 General LED: colour corrected Lighting
6005 Dimmable Lighting
8010 Staff/ Nurse assist call Nurse Call 1
8080 Emergency call Nurse Call 1
2577 PO: Double Power 3 2- desk; 1- wall
2579 PO: Emergency power, single Power 2 to patient services panel
2576 PO: Cleaner Power 1
9040 Body protected Power
12011 Radiation shielding Shielding to walls, floor, ceiling, doors & glazing as specified by Radiation Consultant
2724 Direct connection: Emergency power Power 1 sensor operated tapware
6076 Special: 'X-ray In Use' lights Lighting 1
7000 Oxygen (O2) Medical Gases 1
7040 Suction Medical Gases 1
6838 Trunking: 100mm x 70mm Electrical Installations 1 between generator cabinet, mammography unit, and control console
11505 Floor duct for power & data Services Ducts 1 between generator cabinet, mammography unit, and control console
6827 Cabinet: generator Power 1 for mammography unit; supplied by imaging vendor
2791 PO: Special: 3 phase Power 1 to mammography generator cabinet
2578 PO: Emergency power, double Power 2 to mammography control console