X-ray room for mammography imaging procedures, with change area within the room.
Acoustics: Acoustic privacy required
Body Protected electrical area
Additional Design Considerations:
- Radiation shielding as advised by Radiation Consultant
- Cable ducts between X-ray table and control area may be required
- 'X-ray in Use' lights required oustide each entry door
Amendment
24.10.2010 First Draft
21.04.2011 Services modified
03.09.2023 RDS reviewed
Fabric and outline specifications
ID
Fabric
Material
Finish
Specification
Selection
Remarks
5062
Ceiling
Acoustic
Prefinished
Drop-in tiles, 600x600 mm
8040
Door protection
Composite
Prefinished PVC
To door frame
3022
Wall finish
Resinate, 6mm
Prefinished
Splashback
to basin, other smooth impervious finish also acceptable
4159
Cornice
Aluminium
Powdercoat
Angle flush against wall, in line with ceiling grid
3000
Wall finish
Paint
Acrylic, washable
8010
Door protection
Composite
Prefinished PVC
Protection plate to 900mm AFFL
9130
Doors
Solid Core
Paint
1 1/2 leaf, with lead shielding
1400mm clear opening
1000
Floor finish
Vinyl
Standard slip resistant
Seamless, coved
2000
Skirting
Vinyl
Prefinished
Floor vinyl coved, 150mmH
Fittings and Furniture (FF)
ID
Description
Category
Group
Qty
Selection / Remarks
2150
Chair: patient
Furniture/ Fitting
3
1
to change area
8299
Chair: mammography
MEQ - Imaging
3
1
part of mammography system
2100
Chair: ergonomic, office
Furniture/ Fitting
3
1
to desk
3400
Coathook
Metalwork
1
2
to change area, 1 @1200H
4350
Cupboard: tall
Furniture/ Fitting
1
1
adjustable shelves
4700
Curtain track: privacy screen
Metalwork
1
1
to change area
5250
Curtain: privacy screen
Furniture/ Fitting
3
1
to change area
5900
Desk
Furniture/ Fitting
3
1
6152
Dispenser: disposable glove
Furniture/ Fitting
2
1
6154
Dispenser: paper/ hand towel
Furniture/ Fitting
2
1
to basin
6158
Dispenser: soap antiseptic
Furniture/ Fitting
2
1
to basin
13700
Mirror
Metalwork
1
1
to change area
20000
Shelving unit: adjustable
Furniture/ Fitting
1
1
above desk, optional
8404
Bracket: sharps disposal
MEQ - General
2
1
8321
Suction bottle
MEQ - General
3
1
8318
Suction adapter
MEQ - General
3
1
8297
Bracket: suction bottle
MEQ - General
2
1
8309
Oxygen flowmeter
MEQ - General
3
1
8313
Rack: lead apron
MEQ - Imaging
1
1
9117
Sharps disposal: wall mounted, 7L
MEQ - General
2
1
10061
Waste bin: General, 20 Litres
Furniture/ Fitting
3
1
Fixtures, Equipment and associated Services (FE)
ID
Description
Grp
Qty
Ele
Data
CdW
HtW
WmW
Tap
Dns
Gas
Selection / Remarks
2800
Basin: handwash, Type B
1
1
___
___
yes
___
yes
yes
yes
___
40404
Tapware: sensor
1
1
yes
___
yes
yes
yes
___
___
___
straight spout
54510
Telephone: handset, standard
3
1
___
yes
___
___
___
___
___
___
to desk
9097
X-ray unit: mammography, 3D
2
1
yes
yes
___
___
___
___
___
___
with control panel
9092
Control console
1
1
yes
yes
___
___
___
___
___
___
part of mammography system
Services
ID
Description
Service Category
Qty
Selection / Remarks
1006
Voice / Data outlet: double
Communications
3
1- desk; 1- patient services panel; 1- mammography control console
5000
Airconditioning
HVAC
2242
General LED: colour corrected
Lighting
6005
Dimmable
Lighting
8010
Staff/ Nurse assist call
Nurse Call
1
8080
Emergency call
Nurse Call
1
2577
PO: Double
Power
3
2- desk; 1- wall
2579
PO: Emergency power, single
Power
2
to patient services panel
2576
PO: Cleaner
Power
1
9040
Body protected
Power
12011
Radiation shielding
Shielding
to walls, floor, ceiling, doors & glazing as specified by Radiation Consultant
2724
Direct connection: Emergency power
Power
1
sensor operated tapware
6076
Special: 'X-ray In Use' lights
Lighting
1
7000
Oxygen (O2)
Medical Gases
1
7040
Suction
Medical Gases
1
6838
Trunking: 100mm x 70mm
Electrical Installations
1
between generator cabinet, mammography unit, and control console
11505
Floor duct for power & data
Services Ducts
1
between generator cabinet, mammography unit, and control console