A single bay for neonates requiring Intensive Care nursing and medical treatment. The Bay will include provisions for charting and storage. A staff handwash basin (Type A) should be provided within close access of each Bay. An external outlook is required.
Acoustics: Sound attenuation level - high; Acoustic privacy is required to perimeter walls
Cardiac Protected electrical area/ IPS - Isolated Power Supply
Special requirements:
- Lighting should be controllable with blackout facilities
- Sound levels should be controllable and less than 40db, including
air-conditioning, telephones, alarms, paging systems & basin taps
- power should be supplied from 2 separate isolated power supplies
Amendment
24.10.2010 First Draft
21.04.2011 Room Fabric and FF modified
06.01.2017 Room area, Fabric, FF, FE & Services updated
Fabric and outline specifications
ID
Fabric
Material
Finish
Specification
Selection
Remarks
2000
Skirting
Vinyl
Prefinished
Floor vinyl coved, 150mmH
3000
Wall finish
Paint
Acrylic, washable
5010
Ceiling
Plasterboard
Paint, washable
Flush set, suspended
7030
Observation
Alum/ Glass
Powdercoat
Internal window, door height
with integral venetians, optional
4020
Wall protection
Composite
Prefinished PVC
Crash rail at 900 AFFL
3022
Wall finish
Resinate, 6mm
Prefinished
Splashback
to basin, tiles or other smooth impervious finish also acceptable
4031
Wall protection
Composite
Prefinished PVC
Corner guards to 1500AFFL
to handwash bay
1000
Floor finish
Vinyl
Standard slip resistant
Seamless, coved
7001
Windows
External outlook to the area required
949813
Cornice
Plasterboard
Paint
Square set
Fittings and Furniture (FF)
ID
Description
Category
Group
Qty
Selection / Remarks
150
Air flowmeter
Furniture/ Fitting
3
3
1252
Blind: Venetian integral
Furniture/ Fitting
1
2
to external window and observation window if provided, blackout required
1465
Bracket: suction bottle
Furniture/ Fitting
2
3
2655
Chair: visitor
Furniture/ Fitting
3
2
1 may be reclining chair for parent
4600
Curtain track: bed screen
Metalwork
1
1
to full bay
5000
Curtain: bed screen
Furniture/ Fitting
3
1
to basin
5598
Shelving unit: adjustable, full height
Furniture/ Fittings
1
1
storage
6152
Dispenser: disposable glove
Furniture/ Fitting
2
1
near basin
6154
Dispenser: paper/ hand towel
Furniture/ Fitting
2
1
to basin
6156
Dispenser: soap
Furniture/ Fitting
2
1
to basin
6158
Dispenser: soap antiseptic
Furniture/ Fitting
2
1
to basin
16250
Oxygen flowmeter
Furniture/ Fitting
3
3
21680
Stool: adjustable, mobile
Furniture/ Fitting
3
1
staff use
22000
Suction bottle
Furniture/ Fitting
3
3
23950
Trolley
Furniture/ Fitting
3
1
storage & preparation
24100
Waste bin: paper, 20 Litre
Furniture/ Fitting
3
1
to basin
Fixtures, Equipment and associated Services (FE)
ID
Description
Grp
Qty
Ele
Data
CdW
HtW
WmW
Tap
Dns
Gas
Selection / Remarks
3100
Basin: scrub, Type A
1
1
___
___
yes
___
yes
yes
yes
___
basin in close proximity; taps: sensor outlet; elbow action lever taps also acceptable
31700
Light: examination, ceiling
1
1
yes
___
___
___
___
___
___
___
26000
Humidicrib
3
1
yes
___
___
___
___
___
___
___
46700
Services pendant: adj height
1
1
yes
yes
___
___
___
___
___
___
or wall mounted services
Services
ID
Description
Service Category
Qty
Selection / Remarks
1006
Voice / Data outlet: double
Communications
2
1 outlet for telephone
5000
Airconditioning
HVAC
temperature controllable from 21degrees C to 30 degrees C
6001
General: colour corrected
Lighting
6005
Dimmable
Lighting
variable lighting level
7000
Oxygen (O2)
Medical Gases
3
to patient supply unit or wall mounted
7020
Medical Air (MA)
Medical Gases
3
to patient supply unit or wall mounted
7040
Suction
Medical Gases
3
to patient supply unit or wall mounted
8010
Staff/ Nurse assist call
Nurse Call
1
to patient supply unit or wall mounted
8080
Emergency call
Nurse Call
1
to patient supply unit or wall mounted
2579
PO: Emergency power, single
Power
16
to patient supply unit or wall mounted; provide an additional 8 power outlets if HBN/ HTM compliance is required