A single room for neonates requiring Intensive Care nursing and medical treatment. Sliding glazed doors on the entry side. The Room will include provisions for charting and storage. A staff handwash basin (Type A) should be provided within each Room. An external outlook is required.
Acoustics: Sound attenuation level - high; Acoustic privacy is required to perimeter walls
Cardiac Protected electrical area/ IPS - Isolated Power Supply
Special requirements:
- Lighting should be controllable with blackout facilities
- Sound levels should be controllable and less than 40db, including
air-conditioning, telephones, alarms, paging systems & basin taps
- power should be supplied from 2 separate isolated power supplies
Amendment
14.01.2019 First Draft
03.09.2023 RDS reviewed
Fabric and outline specifications
ID
Fabric
Material
Finish
Specification
Selection
Remarks
3000
Wall finish
Paint
Acrylic, washable
3022
Wall finish
Resinate, 6mm
Prefinished
Splashback
to basin, other smooth impervious finish also acceptable
1000
Floor finish
Vinyl
Standard slip resistant
Seamless, coved
7001
Windows
essential
5010
Ceiling
Plasterboard
Paint, washable
Flush set, suspended
1253
Observation
Alum/ Toughened glass
Powdercoat
Internal window, double glazed
from write-up station; with integral venetian blinds
6170
Doors
Alum/ Toughened glass
Powdercoat/ Paint
Triple leaf, fully glazed, sliding
1253
Observation
Alum/ Toughened glass
Powdercoat
Internal window, double glazed
between two bays; with integral venetians; optional
2000
Skirting
Vinyl
Prefinished
Floor vinyl coved, 150mmH
4020
Wall protection
Composite
Prefinished PVC
Crash rail at 900mm AFFL
2767
Cornice
Plasterboard
Paint
Square set
4030
Wall protection
Composite
Prefinished PVC
Corner guards to 900mm AFFL
as required; other heights also acceptable as per project standardisation
Fittings and Furniture (FF)
ID
Description
Category
Group
Qty
Selection / Remarks
1050
Bench: laminate
Furniture/ Fitting
1
1
can be free-standing
1252
Blind: Venetian integral
Furniture/ Fitting
1
2
to internal & external windows if provided, blackout required
2655
Chair: visitor
Furniture/ Fitting
3
1
2926
Dispenser: hand sanitiser
Furniture/ Fitting
2
1
4410
Cupboard: under bench
Furniture/ Fitting
1
1
4430
Cupboard: drawer unit
Furniture/ Fitting
1
1
4460
Cupboard: wall mounted
Furniture/ Fitting
1
1
4600
Curtain track: bed screen
Metalwork
1
2
around recliner and also along sliding doors
5000
Curtain: bed screen
Furniture/ Fitting
3
2
6152
Dispenser: disposable glove
Furniture/ Fitting
2
1
near basin
6154
Dispenser: paper/ hand towel
Furniture/ Fitting
2
1
to basin
6158
Dispenser: soap antiseptic
Furniture/ Fitting
2
1
to basin
8291
Air flowmeter
MEQ - General
3
3
8297
Bracket: suction bottle
MEQ - General
2
3
8311
Oxygen flowmeter: low flow
MEQ - General
3
3
8319
Suction adapter: low flow
MEQ - General
3
3
8321
Suction bottle
MEQ - General
3
3
8404
Bracket: sharps disposal
MEQ - General
2
1
8593
Bracket: patient monitor
MEQ - General
2
1
8405
Sharps disposal: wall mounted, 11L
MEQ - General
2
1
8594
Linen carrier: dirty, single
MEQ - Furniture
3
1
8607
Waste bin: clinical, 50 litres
MEQ - Furniture
3
1
8616
Trolley: procedure
MEQ - Furniture
3
1
8912
Blender: air & oxygen, low flow
MEQ - General
3
1
air-oxygen blender
21680
Stool: adjustable, mobile
Furniture/ Fitting
3
1
staff use
22660
Table: round
Furniture/ Fitting
3
1
besides recliner; optional
24102
Waste bin: general
Furniture/ Fitting
3
1
to basin
Fixtures, Equipment and associated Services (FE)
ID
Description
Grp
Qty
Ele
Data
CdW
HtW
WmW
Tap
Dns
Gas
Selection / Remarks
3100
Basin: scrub, Type A
1
1
___
___
yes
___
yes
yes
yes
___
8764
Chair: recliner, electric
3
1
yes
___
___
___
___
___
___
___
8472
Infusion pump: syringe
3
2
yes
opt
___
___
___
___
___
___
Qty TBC by project
8542
Light: examination, single, ceiling mounted
2
1
yes
___
___
___
___
___
___
___
optional
8778
Monitor: physiologic, critical care, neonatal
3
1
yes
yes
___
___
___
___
___
___
8955
Incubator: infant
3
1
yes
yes
___
___
___
___
___
___
with optional examination light attached to the incubator
8957
Lamp: phototherapy, neonatal
3
1
yes
___
___
___
___
___
___
___
could be shared between a group of bays
8786
Supply unit: ceiling, double arm
2
1
yes
yes
___
___
___
___
___
___
with optional examination light mounted on the pendant; or wall mounted services panel
8988
Infusion pump: enteral feeding
3
1
yes
opt
___
___
___
___
___
___
Qty TBC by project
8989
Infusion pump: single channel
3
2
yes
opt
___
___
___
___
___
___
Qty TBC by project
9006
Ventilator: neonatal/ paediatric
3
1
yes
yes
___
___
___
___
___
___
40404
Tapware: sensor
1
1
yes
___
yes
yes
yes
___
___
___
straight spout
54510
Telephone: handset, standard
3
1
___
yes
___
___
___
___
___
___
Services
ID
Description
Service Category
Qty
Selection / Remarks
1006
Voice / Data outlet: double
Communications
5
4- services pendant; 1- bench
5000
Airconditioning
HVAC
Refer to Part E of these Guidelines; with adjustable temperature control