1 Bed Room - Standard, 18m2, Outboard Ensuite

Room Code NB-IS-P-I
Net Room Area Briefed 18
Hours of Operation 24 Hours
Occupancy 1 baby; up to 5 staff; 1-2 parents
Description / Special Requirements A single room for neonates requiring positive pressure isolation to protect them from acquiring an infection while undergoing nursing and medical treatment. The Room will include provisions for charting and storage. A staff handwash basin (Type A) should be provided within each Room. An external outlook is required. Acoustics: Sound attenuation level - high; Acoustic privacy is required to perimeter walls Cardiac Protected electrical area/ IPS - Isolated Power Supply Special requirements: - Lighting should be controllable with blackout facilities - Sound levels should be controllable and less than 40db, including air-conditioning, telephones, alarms, paging systems & basin taps - power should be supplied from 2 separate isolated power supplies
Amendment 14.01.2019 First Draft 03.09.2023 RDS reviewed 16.05.2024 Fabrics updated

Fabric and outline specifications

ID Fabric Material Finish Specification Selection Remarks
2000 Skirting Vinyl Prefinished Floor vinyl coved, 150mmH
4020 Wall protection Composite Prefinished PVC Crash rail at 900mm AFFL
3000 Wall finish Paint Acrylic, washable
1000 Floor finish Vinyl Standard slip resistant Seamless, coved
7001 Windows essential
5010 Ceiling Plasterboard Paint, washable Flush set, suspended
2767 Cornice Plasterboard Paint Square set
1253 Observation Alum/ Toughened glass Powdercoat Internal window, double glazed from write-up station; with integral venetian blinds
3022 Wall finish Resinate, 6mm Prefinished Splashback to basin, other smooth impervious finish also acceptable
1253 Observation Alum/ Toughened glass Powdercoat Internal window, double glazed between two bays; with integral venetians; optional
4030 Wall protection Composite Prefinished PVC Corner guards to 900mm AFFL as required; other heights also acceptable as per project standardisation
9127 Doors Solid Core/ Safety glass Paint 1 1/2 leaf, observation panel Min. 1350mm clear opening; 1400mm clear opening ideal; with integral venetian blinds

Fittings and Furniture (FF)

ID Description Category Group Qty Selection / Remarks
1050 Bench: laminate Furniture/ Fitting 1 1 can be free-standing
1252 Blind: Venetian integral Furniture/ Fitting 1 2 to internal & external windows if provided, blackout required
2655 Chair: visitor Furniture/ Fitting 3 1
2926 Dispenser: hand sanitiser Furniture/ Fitting 2 1
4410 Cupboard: under bench Furniture/ Fitting 1 1
4430 Cupboard: drawer unit Furniture/ Fitting 1 1
4460 Cupboard: wall mounted Furniture/ Fitting 1 1
4600 Curtain track: bed screen Metalwork 1 2 around recliner and also along sliding doors
5000 Curtain: bed screen Furniture/ Fitting 3 2
6152 Dispenser: disposable glove Furniture/ Fitting 2 1 near basin
6154 Dispenser: paper/ hand towel Furniture/ Fitting 2 1 to basin
6158 Dispenser: soap antiseptic Furniture/ Fitting 2 1 to basin
8291 Air flowmeter MEQ - General 3 3
8297 Bracket: suction bottle MEQ - General 2 3
8311 Oxygen flowmeter: low flow MEQ - General 3 3
8319 Suction adapter: low flow MEQ - General 3 3
8321 Suction bottle MEQ - General 3 3
8404 Bracket: sharps disposal MEQ - General 2 1
8593 Bracket: patient monitor MEQ - General 2 1
8405 Sharps disposal: wall mounted, 11L MEQ - General 2 1
8594 Linen carrier: dirty, single MEQ - Furniture 3 1
8607 Waste bin: clinical, 50 litres MEQ - Furniture 3 1
8616 Trolley: procedure MEQ - Furniture 3 1
8912 Blender: air & oxygen, low flow MEQ - General 3 1
21680 Stool: adjustable, mobile Furniture/ Fitting 3 1 staff use
22660 Table: round Furniture/ Fitting 3 1 besides recliner; optional
24102 Waste bin: general Furniture/ Fitting 3 1 to basin

Fixtures, Equipment and associated Services (FE)

ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
3100 Basin: scrub, Type A 1 1 ___ ___ yes ___ yes yes yes ___
8764 Chair: recliner, electric 3 1 yes ___ ___ ___ ___ ___ ___ ___
8472 Infusion pump: syringe 3 2 yes opt ___ ___ ___ ___ ___ ___ Qty TBC by project
8542 Light: examination, single, ceiling mounted 2 1 yes ___ ___ ___ ___ ___ ___ ___ optional
8778 Monitor: physiologic, critical care, neonatal 3 1 yes yes ___ ___ ___ ___ ___ ___
8955 Incubator: infant 3 1 yes yes ___ ___ ___ ___ ___ ___ with optional examination light attached to the incubator
8957 Lamp: phototherapy, neonatal 3 1 yes ___ ___ ___ ___ ___ ___ ___
8786 Supply unit: ceiling, double arm 2 1 yes yes ___ ___ ___ ___ ___ ___ with optional examination light mounted on the pendant; or wall mounted services panel
8988 Infusion pump: enteral feeding 3 1 yes opt ___ ___ ___ ___ ___ ___ Qty TBC by project
8989 Infusion pump: single channel 3 2 yes opt ___ ___ ___ ___ ___ ___ Qty TBC by project
9006 Ventilator: neonatal/ paediatric 3 1 yes yes ___ ___ ___ ___ ___ ___
40404 Tapware: sensor 1 1 yes ___ yes yes yes ___ ___ ___ straight spout
54510 Telephone: handset, standard 3 1 ___ yes ___ ___ ___ ___ ___ ___

Services

ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 5 4- services pendant; 1- bench
5000 Airconditioning HVAC Refer to Part E of these Guidelines; with adjustable temperature control
2242 General LED: colour corrected Lighting variable lighting level
7000 Oxygen (O2) Medical Gases 3 to services pendant
7020 Medical Air (MA) Medical Gases 3 to services pendant
7040 Suction Medical Gases 3 to services pendant
8010 Staff/ Nurse assist call Nurse Call 1 to services pendant
8080 Emergency call Nurse Call 1 to services pendant
2576 PO: Cleaner Power 1
9030 Cardiac protected/ IPS Power
2724 Direct connection: Emergency power Power 3 1- for sensor operated tapware; 1- services pendant; 1- examination ceiling light (optional)
2723 PO: Cardiac Protected/IPS, single Power 20 to services pendant
2577 PO: Double Power 1 bench
6055 Special: task light, built in Lighting under O/H cupboards
2761 Direct connection: Tool Air Medical Gases 1 to services pendant (for brakes)
2582 PO: Single Power 1 for electric recliner
5040 Pressure: positive HVAC