Print Download PDF Version
Neonatal Bay - Resuscitation
Room Code
NB-R-I
Net Room Area Briefed
4
Hours of Operation
24 Hours
Occupancy
1 baby; up to 4 staff
Description / Special Requirements
The Neontal Resuscitation Bay is a bay for assessment, resuscitation, treatment and transfer preparation of Neonates with critical conditions. A scrub basin must be located in close proximity. Resuscitation diagnostic equipment such as infant resuscitation trolley, and ventilator must be provided. Isolated power (IPS) must be provided.
Cardiac Protected electrical area
Amendment
Fabric and outline specifications
ID
Fabric
Material
Finish
Specification
Selection
Remarks
5010
Ceiling
Plasterboard
Paint, washable
Flush set, suspended
4031
Wall protection
Composite
Prefinished PVC
Corner guards to 1500mm AFFL
as required, other heights also acceptable as per project standardisation
1000
Floor finish
Vinyl
Standard slip resistant
Seamless, coved
3092
Wall protection
MDF
Laminate
Bed protection wall panel
2000
Skirting
Vinyl
Prefinished
Floor vinyl coved, 150mmH
3000
Wall finish
Paint
Acrylic, washable
6025
Cornice
Aluminium
Powdercoat
shadow line
Fittings and Furniture (FF)
ID
Description
Category
Group
Qty
Selection / Remarks
4600
Curtain track: bed screen
Metalwork
1
1
5000
Curtain: bed screen
Furniture/ Fitting
3
1
6152
Dispenser: disposable glove
Furniture/ Fitting
2
1
6154
Dispenser: paper/ hand towel
Furniture/ Fitting
2
1
to basin
6158
Dispenser: soap antiseptic
Furniture/ Fitting
2
1
to basin
8291
Air flowmeter
MEQ - General
3
1
8321
Suction bottle
MEQ - General
3
1
8297
Bracket: suction bottle
MEQ - General
2
1
8311
Oxygen flowmeter: low flow
MEQ - General
3
1
8319
Suction adapter: low flow
MEQ - General
3
1
to baby
8404
Bracket: sharps disposal
MEQ - General
2
1
mounted to trolley
8406
Sharps disposal: on trolley, 11L
MEQ - General
3
1
10061
Waste bin: General, 20 Litres
Furniture/ Fitting
3
1
to basin
8399
Trolley: resuscitation, neonatal
MEQ - Furniture
3
1
or in a nearby resuscitation bay
8593
Bracket: patient monitor
MEQ - General
2
1
optional
8594
Linen carrier: dirty, single
MEQ - Furniture
3
1
8922
Laryngoscope set: fiber optic, neonatal
MEQ - General
3
1
Fixtures, Equipment and associated Services (FE)
ID
Description
Grp
Qty
Ele
Data
CdW
HtW
WmW
Tap
Dns
Gas
Selection / Remarks
3100
Basin: scrub, Type A
1
1
___
___
yes
___
yes
yes
yes
___
in close proximity
8954
Warmer unit: neonatal, with resuscitation
3
1
yes
opt
___
___
___
___
___
___
40404
Tapware: sensor
1
1
yes
___
yes
yes
yes
___
___
___
straight spout
8778
Monitor: physiologic, critical care, neonatal
3
1
yes
yes
___
___
___
___
___
___
optional
8973
Pump: suction/ aspirator, portable
3
1
yes
___
___
___
___
___
___
___
or in a nearby resuscitation bay
Services
ID
Description
Service Category
Qty
Selection / Remarks
1006
Voice / Data outlet: double
Communications
1
per cot space
5000
Airconditioning
HVAC
2242
General LED: colour corrected
Lighting
7000
Oxygen (O2)
Medical Gases
1
per cot space
7020
Medical Air (MA)
Medical Gases
1
per cot space
7040
Suction
Medical Gases
1
per cot space
8010
Staff/ Nurse assist call
Nurse Call
1
+ indicator button & light
8080
Emergency call
Nurse Call
1
+ indicator button & light
9040
Body protected
Power
2724
Direct connection: Emergency power
Power
1
sensor operated tapware
6829
PO: Isolated Power Suppy (IPS), single
Power
6
per cot space
11000
Wall panel
Services Panels
1
patient services
1005
Voice / Data outlet: single
Communications
1
to patient monitor (optional)
2579
PO: Emergency power, single
Power
1
to patient monitor (optional)