A single bay for neonates requiring Special Care nursing and medical treatment. This includes neonates requiring continuing care, close observation by nursing staff or higher levels of nursing care such as low birth weight . The Bay will include provisions for charting and storage. A staff handwash basin (Type A) should be provided within proximity for each Bay. Provisions of handwash basins must comply to Part D of these Guidelines. An external outlook is required.
Acoustics: Sound attenuation level - high; Acoustic privacy is required to perimeter walls
Body Protected electrical area
Special requirements:
- Lighting should be controllable with blackout facilities
- Sound levels should be controllable and less than 40db, including
air-conditioning, telephones, alarms, paging systems & basin taps
- power should be supplied from 2 separate isolated power supplies
Amendment
24.10.2010 First Draft
27.01.2017 Room area, Fabric, FF, FE & Services updated
19.05.2022 Room Area, FF&FE items and services updated
03.09.2023 RDS reviewed
Fabric and outline specifications
ID
Fabric
Material
Finish
Specification
Selection
Remarks
7001
Windows
desirable
5010
Ceiling
Plasterboard
Paint, washable
Flush set, suspended
2000
Skirting
Vinyl
Prefinished
Floor vinyl coved, 150mmH
3000
Wall finish
Paint
Acrylic, washable
1000
Floor finish
Vinyl
Standard slip resistant
Seamless, coved
2767
Cornice
Plasterboard
Paint
Square set
4020
Wall protection
Composite
Prefinished PVC
Crash rail at 900mm AFFL
as required
4031
Wall protection
Composite
Prefinished PVC
Corner guards to 1500mm AFFL
as required; other heights also acceptable as per project standardisation
Fittings and Furniture (FF)
ID
Description
Category
Group
Qty
Selection / Remarks
1050
Bench: laminate
Furniture/ Fitting
1
1
can be free-standing
1252
Blind: Venetian integral
Furniture/ Fitting
1
1
to external window if provided, blackout required
2655
Chair: visitor
Furniture/ Fitting
3
1
2926
Dispenser: hand sanitiser
Furniture/ Fitting
2
1
4410
Cupboard: under bench
Furniture/ Fitting
1
1
to each bay
4430
Cupboard: drawer unit
Furniture/ Fitting
1
1
to each bay; under bench
4600
Curtain track: bed screen
Metalwork
1
1
5000
Curtain: bed screen
Furniture/ Fitting
3
1
8291
Air flowmeter
MEQ - General
3
2
8297
Bracket: suction bottle
MEQ - General
2
2
8306
IV pole: mobile
MEQ - General
3
1
8311
Oxygen flowmeter: low flow
MEQ - General
3
2
8319
Suction adapter: low flow
MEQ - General
3
2
8321
Suction bottle
MEQ - General
3
2
8404
Bracket: sharps disposal
MEQ - General
2
1
8593
Bracket: patient monitor
MEQ - General
2
1
20000
Shelving unit: adjustable
Furniture/ Fitting
1
1
over bench
21680
Stool: adjustable, mobile
Furniture/ Fitting
3
1
8594
Linen carrier: dirty, single
MEQ - Furniture
3
1
8607
Waste bin: clinical, 50 litres
MEQ - Furniture
3
1
8912
Blender: air & oxygen, low flow
MEQ - General
3
1
oxygen-air blender
9117
Sharps disposal: wall mounted, 7L
MEQ - General
2
1
Fixtures, Equipment and associated Services (FE)
ID
Description
Grp
Qty
Ele
Data
CdW
HtW
WmW
Tap
Dns
Gas
Selection / Remarks
8472
Infusion pump: syringe
3
1
yes
opt
___
___
___
___
___
___
Qty TBC by project
8778
Monitor: physiologic, critical care, neonatal
3
1
yes
yes
___
___
___
___
___
___
wall mounted
8957
Lamp: phototherapy, neonatal
3
1
yes
___
___
___
___
___
___
___
could be shared between a group of bays
8955
Incubator: infant
3
1
yes
yes
___
___
___
___
___
___
with optional examination light attached to the incubator; or incubator/ warmer combo unit
8988
Infusion pump: enteral feeding
3
1
yes
opt
___
___
___
___
___
___
Qty TBC by project
8989
Infusion pump: single channel
3
1
yes
opt
___
___
___
___
___
___
Qty TBC by project
Services
ID
Description
Service Category
Qty
Selection / Remarks
1006
Voice / Data outlet: double
Communications
3
1- bench; 2- services panel
5000
Airconditioning
HVAC
Refer to Part E of these Guidelines with adjustable temperature control