1 Bed Room - Standard, 18m2, Outboard Ensuite

Room Code OR-HY-VS-I
Net Room Area Briefed 76
Hours of Operation 24 Hours
Occupancy 1 patient; 5 - 12 staff
Description / Special Requirements The Operating Room - Vascular/ Cardiac provides an aseptic environment in which to carry out surgical procedures under local, regional or general anaesthetic. The Vascular/ Cardiac OR will include Angiography imaging equipment. Cardiac Protected electrical area Special Air Conditioning - HEPA filtration Additional Design Considerations: - Minimum critical dimension 6000mm on at least 1 side. - 'Laser In Use' warning lights may be required outside all exit doors to room if laser equipment is to be used - Lead shielding will be required; to be assessed by Radiation Consultant - External windows are desirable - double glazed with integral Venetian blinds - Provide isolated power supply individually to each large Operating Room, together with its associated line isolation and overload monitors
Amendment 10.03.2023 RDS updated 16.05.2024 Fabrics & Services updated

Fabric and outline specifications

ID Fabric Material Finish Specification Selection Remarks
8010 Door protection Composite Prefinished PVC Protection plate to 900mm AFFL
2269 Doors Solid Core/ Lead glass Paint Double leaf, observation panel, lead shielding 1600 min clear opening to patient entry/exit and scrub; obs panel with sliding cover or internal venetians
9001 Doors Solid Core Paint Single leaf 920mm clear opening, to Control Room
8040 Door protection Composite Prefinished PVC To door frame
1000 Floor finish Vinyl Standard slip resistant Seamless, coved
7025 Observation Lead glass Clear Internal window
5020 Ceiling Plasterboard Paint, scrub resistant Flush set, suspended
6015 Cornice Plasterboard Paint Flush coved between wall & ceiling
2313 Skirting Vinyl Prefinished Floor vinyl coved, 300mmH
3010 Wall finish Paint Scrub resistant epoxy paint or full height wall vinyl also acceptable
9006 Doors Solid Core/ Safety glass Paint Single leaf, observation panel 920mm clear opening to sterile stock room/ setup room, obs panel with sliding cover or integral venetians

Fittings and Furniture (FF)

ID Description Category Group Qty Selection / Remarks
1030 Bench: resinate Furniture/ Fitting 1 1 documentation station: computers, write-up
6152 Dispenser: disposable glove Furniture/ Fitting 2 1
8291 Air flowmeter MEQ - General 3 4 to services pendants; for medical air
8296 Bowl stand: single MEQ - General 3 2
8297 Bracket: suction bottle MEQ - General 2 4
8306 IV pole: mobile MEQ - General 3 2
8309 Oxygen flowmeter MEQ - General 3 4 to services pendants; for Oxygen
8313 Rack: lead apron MEQ - Imaging 2 1
8318 Suction adapter MEQ - General 3 4 to services pendants
8321 Suction bottle MEQ - General 3 4
8343 Cabinet: storage, instrument, OR, double door, recessed MEQ - Furniture 2 2
8385 Carrier stand, suction canisters MEQ - General 3 1
8398 Trolley: resuscitation MEQ - Furniture 3 1
8408 Kick bucket MEQ - General 3 2
8411 Stool: adjustable, OR MEQ - Furniture 3 2
8412 Stool: adjustable, OR, with backrest MEQ - Furniture 3 1 for anaesthetist
8593 Bracket: patient monitor MEQ - General 2 1 for cardiac monitor, mounted on anaesthesia pendant
8594 Linen carrier: dirty, single MEQ - Furniture 3 2
8603 Headlight: surgical MEQ - General 3 1
8620 Trolley: instrument MEQ - Furniture 3 3
8622 Trolley: gowns MEQ - Furniture 3 1
8627 Trolley: anaesthetic MEQ - Furniture 3 1
8630 Table: mayo MEQ - Furniture 3 1

Fixtures, Equipment and associated Services (FE)

ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
6468 Camera: in room 2 1 yes yes ___ ___ ___ ___ ___ ___ PTZ, optional, part of integration system
8472 Infusion pump: syringe 3 2 yes opt ___ ___ ___ ___ ___ ___ Qty TBC by project
8473 Infusion pump: rapid, blood/ solution warming, on stand 3 1 yes ___ ___ ___ ___ ___ ___ ___ Qty TBC by project
8548 Light: surgical, single, ceiling, with two monitor arms & camera 2 1 yes opt ___ ___ ___ ___ ___ ___ light configurations may change depending on OR integration system requirements
8714 Anaesthesia unit: standard 3 1 yes opt ___ ___ ___ ___ ___ ___
8767 Defibrillator: with monitor 3 1 yes ___ ___ ___ ___ ___ ___ ___
8786 Supply unit: ceiling, double arm 2 3 yes yes ___ ___ ___ ___ ___ ___ 1- anaesthesia pendant; 1- surgical pendant; 1- perfusionist pendant
8822 Warming cabinet: dual compartment, freestanding, 500L 3 1 yes ___ ___ ___ ___ ___ ___ ___ optional
8924 Electrosurgical unit: monopolar/ bipolar 3 1 yes ___ ___ ___ ___ ___ ___ ___
8941 Integration system: OR, HD 2 1 yes yes ___ ___ ___ ___ ___ ___ optional, includes 2 display monitors and 1 control monitor in the surgical field, 2 display monitor on the wall, and 1 control monitor on the nurse workstation
8952 Smoke evacuation system, surgical 3 1 yes ___ ___ ___ ___ ___ ___ ___
8953 Hypo-hyperthermia unit: general 3 1 yes ___ ___ ___ ___ ___ ___ ___
8966 Monitor: video, medical grade, HD, 19-inch 3 2 yes yes ___ ___ ___ ___ ___ ___ optional, control monitors part of integration system
8967 Monitor: video, medical grade, HD, 26-inch 3 2 yes yes ___ ___ ___ ___ ___ ___ optional, display monitors part of integration system
8970 Monitor: video, medical grade, HD, 55-inch 3 2 yes yes ___ ___ ___ ___ ___ ___ optional, wall mounted part of integration system
8973 Pump: suction/ aspirator, portable 3 1 yes ___ ___ ___ ___ ___ ___ ___
8989 Infusion pump: single channel 3 2 yes opt ___ ___ ___ ___ ___ ___ Qty TBC by project
9023 Tracking system: instrument tray 3 1 yes yes ___ ___ ___ ___ ___ ___ optional, workstation part of CSSD instrument tracking system
9090 Ultrasound scanning unit: cardiac/ echo 3 1 yes yes ___ ___ ___ ___ ___ ___
9101 Angiography table 2 yes ___ ___ ___ ___ ___ ___ ___ optional; part of angiography system; to be deleted if operating table is provided
9222 Control panel: surgical, recessed 2 1 yes ___ ___ ___ ___ ___ ___ ___ includes slave analogue clock, elapsed time clock, temperature and humidity indicators and controls, IPS and UPS systems alarms, medical gas alarms, AGSS controls, theatre lamp controls, general lighting controls and power sockets as required
9454 Coagulation unit: ACT 3 1 yes opt ___ ___ ___ ___ ___ ___
9547 Medication dispensing system: automated, anaesthesia 2 1 yes yes ___ ___ ___ ___ ___ ___ optional, quantity and modules depend on service requirements; with this option anaesthetic trolley may not be required
9556 Supply dispensing system: automated, catheter, main unit 2 1 yes yes ___ ___ ___ ___ ___ ___ optional, depending on operational requirements
8559 Angiography: interventional radiology, single plane, ceiling mounted 2 1 yes yes ___ ___ ___ ___ ___ ___ single plane or bi-plane, ceiling mounted or floor mounted depending on operational requirements
8779 Monitor: physiologic, operating theatre/ cardiac 3 1 yes yes ___ ___ ___ ___ ___ ___ on anaesthesia pendant
9067 Operating table: mobile, electric, general 3 1 yes ___ ___ ___ ___ ___ ___ ___
9427 Pump: intra-aortic balloon (IABP) 3 1 yes yes ___ ___ ___ ___ ___ ___
9428 Injector: contrast media, mobile, single head, angiography 3 1 yes yes ___ ___ ___ ___ ___ ___
9557 Supply dispensing system: automated, catheter, auxiliary 2 1 yes yes ___ ___ ___ ___ ___ ___ optional, depending on operational requirements
9649 Ultrasound scanning unit: Intravascular (IVUS) 3 1 yes yes ___ ___ ___ ___ ___ ___ optional
10173 Cabinet: server, OR integration 3 1 yes ___ ___ ___ ___ ___ ___ ___ optional, part of integration system
10389 Light: surgical, single, ceiling, with monitor arm 2 1 yes opt ___ ___ ___ ___ ___ ___ light configurations may change depending on OR integration system requirements
10501 Heart/ lung bypass machine 3 1 yes yes ___ ___ ___ ___ ___ yes
10502 Thrombectomy system: catheter 3 1 yes ___ ___ ___ ___ ___ ___ ___
10504 Atherectomy System: rotational 3 1 yes ___ ___ ___ ___ ___ ___ ___
11400 Computer: PC & monitor 3 1 yes yes ___ ___ ___ ___ ___ ___ for nursing & medical staff documentation
13363 Pump: suction/ aspirator, surgical, mobile 3 1 yes ___ ___ ___ ___ ___ ___ ___
54520 Telephone: handset, handsfree 3 1 ___ yes ___ ___ ___ ___ ___ ___ on bench

Services

ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 2 to nurse documentation station
1005 Voice / Data outlet: single Communications 2 1- telephone; 1- anaesthesia medication dispensing unit (optional)
1379 Audio/ Video outlet Communications 8 for services pendants; 2- anaesthetic pendant, 2- perfusionist pendant; 4- surgical pendant
1947 Carbon Dioxide (CO2) Medical Gases 1 1- perfusionist pendant (optional)
8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light; to anaesthesia pendant
2024 Music system Communications 1 optional
5005 Air conditioning: special HVAC HEPA filtered
5040 Pressure: positive HVAC
2242 General LED: colour corrected Lighting variable lighting level
6074 Special: 'Laser In Use' lights Lighting outside room entries, if laser to be used (optional)
7000 Oxygen (O2) Medical Gases 4 1- anaesthesia pendant; 2- perfusionist pendant; 1- surgical pendant
7010 Nitrous Oxide (N2O) Medical Gases 2 2- anaesthesia pendant
7020 Medical Air (MA) Medical Gases 4 1- anaesthesia pendant; 2- perfusionist pendant; 1- surgical pendant
7040 Suction Medical Gases 4 1- anaesthesia pendant; 2- perfusionist pendant; 1- surgical pendant
7070 Scavenge Medical Gases 2 2- anaesthesia pendant
8080 Emergency call Nurse Call 1 + indicator button & light; to anaesthesia pendant
8090 Orderly/ Porter call Nurse Call 1 optional; to anaesthesia pendant
2576 PO: Cleaner Power 1
9030 Cardiac protected/ IPS Power
2723 PO: Cardiac Protected/IPS, single Power 30 for services pendants; 10- anaesthetic pendant, 10- perfusionist pendant, 10- surgical pendant
2724 Direct connection: Emergency power Power 3 for pendants
2728 PO: Single phase, high current, 32 Amp Power 1 optional; for laser on wall
1006 Voice / Data outlet: double Communications 8 for services pendants; 2- anaesthetic pendant, 2- perfusionist pendant; 4- surgical pendant
2756 Cable conduit Electrical 1 optional (part of integration system); for integration system server cabinet
2578 PO: Emergency power, double Power 2 for walls
2578 PO: Emergency power, double Power 2 1- resuscitation trolley; 1- warming cabinet (optional)
2726 PO: UPS, double Power 2 for walls
2760 Direct connection: Voice/ Data Communications 2 1- in room camera (optional, part of integration system), 1- operating light camera attachment
2760 Direct connection: Voice/ Data Communications 1 for surgical control panel (to be integrated with BMS & lighting controls)
2761 Direct connection: Tool Air Medical Gases 3 1 per pendant (for brakes)
2757 Direct connection: Uninterrupted power Power 3 1- surgical control panel, 2- operating lights (1 each)
2757 Direct connection: Uninterrupted power Power 1 optional (part of integration system); ; for in room camera
2726 PO: UPS, double Power 2 for nurse documentation station
2726 PO: UPS, double Power 2 optional (part of integration system); for integration system server cabinet
2726 PO: UPS, double Power 2 optional; 1- anaesthesia medication dispensing unit; 1- supply/ catheter dispensing unit
12011 Radiation shielding Shielding for walls, floor, ceiling, doors & glazing as specified by Radiation Consultant
1006 Voice / Data outlet: double Communications 3 optional (part of integration system); 1- 19" wall mounted control monitor, 2- 55" wall monitors (1 each)
1006 Voice / Data outlet: double Communications 3 optional (part of integration system); for 1- 19" control monitor and 2- 26" display monitors within the surgical field (1 each)
2726 PO: UPS, double Power 3 optional (part of integration system); 1- 19" wall mounted control monitor, 2- 55" wall monitors (1 each)
2726 PO: UPS, double Power 3 optional (part of integration system); for 1- 19" control monitor and 2- 26" display monitors within the surgical field (1 each)
6005 Dimmable Lighting
11505 Floor duct for power & data Services Ducts 1 between equipment room, control room and hydrid OR room (for angiography unit and IVUS)
5743 Trunking: 200mm x 100mm Electrical Installations 1 between equipment room, control room and hydrid OR room (for angiography unit and IVUS)
6076 Special: 'X-ray In Use' lights Lighting 1
1040 Intercom Communications 1 handsfree to control room
1006 Voice / Data outlet: double Communications 2 for walls
2694 PO: UPS, single Power 2 optional; to loudspeaker and on-air lamp (part of integration system - refer to manufacturer's specifications)
1379 Audio/ Video outlet Communications 3 optional (part of integration system); 1- 19" wall mounted control monitor, 2- 55" wall monitors (1 each)
1379 Audio/ Video outlet Communications 3 optional (part of integration system); for 1- 19" control monitor and 2- 26" display monitors within the surgical field (1 each)
6870 Surgical Air (SA7) Medical Gases 2 2- surgical pendant
1006 Voice / Data outlet: double Communications 1 to supply/ catheter dispensing units (optional)
6909 Wave pad access Security 4 2- patient entry door; 2- control room door