Operating Room - Minor

Room Code OR-MS-I
Net Room Area Briefed 36
Hours of Operation 24 Hours
Occupancy 1 patient; 3 - 5 staff
Description / Special Requirements Operating Room/ Procedures Room for minor surgical or endoscopic procedures under local, regional or general anaesthetic in an aseptic environment. A clinical scrub basin or sink should be located immediately outside the room. Clean-up and Set-up rooms may be located in close proximity. The Operating Room - Minor may vary in size from 30 m2 to 36 m2 depending on need. Cardiac Protected electrical area Special Air Conditioning - HEPA filtration Additional Design Considerations: - Minimum critical dimension 6000mm on at least 1 side. - 'Laser In Use' warning lights may be required outside all exit doors to room if laser equipment is to be used - Lead shielding may be required depending on use of X-ray equipment; to be assessed by Radiation Consultant - External windows desirable - double glazed with integral Venetian blinds
Amendment 24.10.2010 First Draft 04.04.2022 Room Fabric, FF&FE and Services updated. 16.05.2024 Fabrics & Services updated

Fabric and outline specifications

ID Fabric Material Finish Specification Selection Remarks
1000 Floor finish Vinyl Standard slip resistant Seamless, coved
6015 Cornice Plasterboard Paint Flush coved between wall & ceiling
8010 Door protection Composite Prefinished PVC Protection plate to 900mm AFFL
8040 Door protection Composite Prefinished PVC To door frame
9001 Doors Solid Core Paint Single leaf 1100mm clear opening, to clean-up room
9127 Doors Solid Core/ Safety glass Paint 1 1/2 leaf, observation panel 1600mm clear opening to patient entry/exit; obs panel with sliding cover or integral venetians
1253 Observation Alum/ Toughened glass Powdercoat Internal window, double glazed with integral venetian; optional
5020 Ceiling Plasterboard Paint, scrub resistant Flush set, suspended
2313 Skirting Vinyl Prefinished Floor vinyl coved, 300mmH
3010 Wall finish Paint Scrub resistant epoxy paint or full height wall vinyl also acceptable
9006 Doors Solid Core/ Safety glass Paint Single leaf, observation panel 920mm clear opening to sterile stock room/ setup room, obs panel with sliding cover or integral venetians
9006 Doors Solid Core/ Safety glass Paint Single leaf, observation panel 920mm clear opening to scrub bay, obs panel with sliding cover or integral venetians

Fittings and Furniture (FF)

ID Description Category Group Qty Selection / Remarks
1030 Bench: resinate Furniture/ Fitting 1 1 documentation station: computer, write up
1252 Blind: Venetian integral Furniture/ Fitting 1 2 to internal window & door glazing as required
4365 Cupboard: full ht, adj shelves Furniture/ Fitting 1 1 optional
4410 Cupboard: under bench Furniture/ Fitting 1 1 optional
4480 Cupboard: wall mounted, glass doors Furniture/ Fitting 1 1 over bench, optional
6152 Dispenser: disposable glove Furniture/ Fitting 2 1
8291 Air flowmeter MEQ - General 3 2 to services pendants
8296 Bowl stand: single MEQ - General 3 1
8297 Bracket: suction bottle MEQ - General 2 4
8306 IV pole: mobile MEQ - General 3 2
8309 Oxygen flowmeter MEQ - General 3 4 to services pendants
8318 Suction adapter MEQ - General 3 4 to services pendants
8321 Suction bottle MEQ - General 3 4
8343 Cabinet: storage, instrument, OR, double door, recessed MEQ - Furniture 2 1
8385 Carrier stand, suction canisters MEQ - General 3 1 mobile
8398 Trolley: resuscitation MEQ - Furniture 3 1
8408 Kick bucket MEQ - General 3 2
8411 Stool: adjustable, OR MEQ - Furniture 3 2
8402 Footstool: 2-step MEQ - Furniture 3 1
8412 Stool: adjustable, OR, with backrest MEQ - Furniture 3 1
8593 Bracket: patient monitor MEQ - General 3 1 for cardiac monitor, mounted on anaesthesia pendant
8594 Linen carrier: dirty, single MEQ - Furniture 3 2
8603 Headlight: surgical MEQ - General 3 1
8620 Trolley: instrument MEQ - Furniture 3 2
8622 Trolley: gowns MEQ - Furniture 3 1
8627 Trolley: anaesthetic MEQ - Furniture 3 1
8630 Table: mayo MEQ - Furniture 3 1
8746 Trolley: surgical case, closed, single door MEQ - Furniture 3 1

Fixtures, Equipment and associated Services (FE)

ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
8472 Infusion pump: syringe 3 2 yes opt ___ ___ ___ ___ ___ ___ Qty TBC by project
8473 Infusion pump: rapid, blood/ solution warming, on stand 3 1 yes ___ ___ ___ ___ ___ ___ ___ Qty TBC by project
8767 Defibrillator: with monitor 3 1 yes ___ ___ ___ ___ ___ ___ ___ on resuscitation trolley
8939 Endoscopy tower: laparoscopy 3 1 yes yes ___ ___ ___ ___ ___ ___ includes video processor, light source, insufflator, suction/ irrigator, high frequency generator (electrosurgical unit), smoke evacuator, monitor, endoscopes, and optional equipment cart
8817 Warming cabinet: single compartment, benchtop, 85L 3 1 yes ___ ___ ___ ___ ___ ___ ___ optional
8967 Monitor: video, medical grade, HD, 26-inch 3 1 yes yes ___ ___ ___ ___ ___ ___ mounted on surgical light monitor arm
8973 Pump: suction/ aspirator, portable 3 1 yes ___ ___ ___ ___ ___ ___ ___ on resuscitation trolley
8989 Infusion pump: single channel 3 2 yes opt ___ ___ ___ ___ ___ ___ Qty TBC by project
8714 Anaesthesia unit: standard 3 1 yes opt ___ ___ ___ ___ ___ ___
8758 Sequential compression device 3 1 yes ___ ___ ___ ___ ___ ___ ___
8779 Monitor: physiologic, operating theatre/ cardiac 3 1 yes yes ___ ___ ___ ___ ___ ___
8786 Supply unit: ceiling, double arm 2 2 yes yes ___ ___ ___ ___ ___ ___ 1- anaesthesia pendant (1 drop); 1- surgical pendant (1 drop)
8969 Monitor: video, medical grade, HD, 42-inch 3 1 yes yes ___ ___ ___ ___ ___ ___ wall mounted
8983 Light: surgical, single, ceiling, with monitor arm & camera 2 1 yes opt ___ ___ ___ ___ ___ ___ optional camera attachment to light head, 1 x display monitor
9067 Operating table: mobile, electric, general 3 1 yes ___ ___ ___ ___ ___ ___ ___
9222 Control panel: surgical, recessed 2 1 yes ___ ___ ___ ___ ___ ___ ___ includes slave analogue clock, elapsed time clock, temperature and humidity indicators and controls, IPS and UPS systems alarms, medical gas alarms, AGSS controls, theatre lamp controls, general lighting controls and power sockets as required
9924 Warming blanket unit: patient 3 1 yes ___ ___ ___ ___ ___ ___ ___
11400 Computer: PC & monitor 3 1 yes yes ___ ___ ___ ___ ___ ___
13363 Pump: suction/ aspirator, surgical, mobile 3 1 yes ___ ___ ___ ___ ___ ___ ___
54520 Telephone: handset, handsfree 3 1 ___ yes ___ ___ ___ ___ ___ ___ to bench

Services

ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 4 for services pendants; 2- anaesthesia pendant , 2- surgical pendant
1006 Voice / Data outlet: double Communications 2 to nurse documentation station (for computer)
5005 Air conditioning: special HVAC HEPA filtered
5040 Pressure: positive HVAC
2242 General LED: colour corrected Lighting variable lighting level
6074 Special: 'Laser In Use' lights Lighting outdside room entries, if laser to be used (optional)
7000 Oxygen (O2) Medical Gases 4 2- anaesthesia pendant; 2- surgical pendant
7010 Nitrous Oxide (N2O) Medical Gases 2 2- anaesthesia pendant
7020 Medical Air (MA) Medical Gases 2 1- anaesthesia pendant; 1- surgical pendant
7040 Suction Medical Gases 4 2- anaesthesia pendant; 2- surgical pendant
7070 Scavenge Medical Gases 2 2- anaesthesia pendant
8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light, to Anaesthetic pendant arm
8080 Emergency call Nurse Call 1 + indicator button & light, to Anaesthetic pendant arm
8090 Orderly/ Porter call Nurse Call 1 optional, to anaesthesia pendant
2576 PO: Cleaner Power 1
9030 Cardiac protected/ IPS Power
2723 PO: Cardiac Protected/IPS, single Power 16 for services pendants; 8- anaesthesia pendant, 8- surgical pendant
1379 Audio/ Video outlet Communications 4 for services pendants; 2- anaesthesia pendant , 2- surgical pendant
2760 Direct connection: Voice/ Data Communications 1 optional, for operating light camera attachment
1005 Voice / Data outlet: single Communications 1 to telephone
2724 Direct connection: Emergency power Power 2 for pendants
2757 Direct connection: Uninterrupted power Power 2 1- surgical control panel, 1- surgical light
2726 PO: UPS, double Power 2 for walls
2726 PO: UPS, double Power 2 for nurse documentation station (for computer)
2578 PO: Emergency power, double Power 2 for walls
2578 PO: Emergency power, double Power 2 1- resuscitation trolley; 1- warming cabinet (optional)
2728 PO: Single phase, high current, 32 Amp Power 1 optional; for laser on wall
2760 Direct connection: Voice/ Data Communications 1 for surgical control panel (to be integrated with BMS & lighting controls)
2761 Direct connection: Tool Air Medical Gases 2 1 per pendant (for brakes)
6005 Dimmable Lighting
1006 Voice / Data outlet: double Communications 2 1- 26" display monitor; 1- 42" wall mounted monitor
1947 Carbon Dioxide (CO2) Medical Gases 1 1- surgical pendant (optional)
2726 PO: UPS, double Power 2 1- 26" display monitor; 1- 42" wall mounted monitor
12011 Radiation shielding Shielding for walls, floor, ceiling, doors & glazing as specified by Radiation Consultant
1006 Voice / Data outlet: double Communications 2 for walls
1379 Audio/ Video outlet Communications 2 1- 26" display monitor; 1- 42" wall mounted monitor
6870 Surgical Air (SA7) Medical Gases 1 1- surgical pendant (optional)
6909 Wave pad access Security 4 2- patient entry door; 2- door to scrub up