| Room Code | OR-MS-I |
| Net Room Area Briefed | 36 |
| Hours of Operation | 24 Hours |
| Occupancy | 1 patient; 3 - 5 staff |
| Description / Special Requirements | Operating Room/ Procedures Room for minor surgical or endoscopic procedures under local, regional or general anaesthetic in an aseptic environment. A clinical scrub basin or sink should be located immediately outside the room. Clean-up and Set-up rooms may be located in close proximity. The Operating Room - Minor may vary in size from 30 m2 to 36 m2 depending on need. Cardiac Protected electrical area Special Air Conditioning - HEPA filtration Additional Design Considerations: - Minimum critical dimension 6000mm on at least 1 side. - 'Laser In Use' warning lights may be required outside all exit doors to room if laser equipment is to be used - Lead shielding may be required depending on use of X-ray equipment; to be assessed by Radiation Consultant - External windows desirable - double glazed with integral Venetian blinds |
| Amendment | 24.10.2010 First Draft 04.04.2022 Room Fabric, FF&FE and Services updated. 16.05.2024 Fabrics & Services updated 07.05.2025 Services updated |
| ID | Fabric | Material | Finish | Specification | Selection | Remarks |
| 1000 | Floor finish | Vinyl | Standard slip resistant | Seamless, coved | ||
| 6015 | Cornice | Plasterboard | Paint | Flush coved between wall & ceiling | ||
| 8010 | Door protection | Composite | Prefinished PVC | Protection plate to 900mm AFFL | ||
| 8040 | Door protection | Composite | Prefinished PVC | To door frame | ||
| 9001 | Doors | Solid Core | Paint | Single leaf | 1100mm clear opening, to clean-up room | |
| 9127 | Doors | Solid Core/ Safety glass | Paint | 1 1/2 leaf, observation panel | 1600mm clear opening to patient entry/exit; obs panel with sliding cover or integral venetians | |
| 1253 | Observation | Alum/ Toughened glass | Powdercoat | Internal window, double glazed | with integral venetian; optional | |
| 5020 | Ceiling | Plasterboard | Paint, scrub resistant | Flush set, suspended | ||
| 2313 | Skirting | Vinyl | Prefinished | Floor vinyl coved, 300mmH | ||
| 3010 | Wall finish | Paint | Scrub resistant | epoxy paint or full height wall vinyl also acceptable | ||
| 9006 | Doors | Solid Core/ Safety glass | Paint | Single leaf, observation panel | 920mm clear opening to sterile stock room/ setup room, obs panel with sliding cover or integral venetians | |
| 9006 | Doors | Solid Core/ Safety glass | Paint | Single leaf, observation panel | 920mm clear opening to scrub bay, obs panel with sliding cover or integral venetians |
| ID | Description | Category | Group | Qty | Selection / Remarks |
| 1030 | Bench: resinate | Furniture/ Fitting | 1 | 1 | documentation station: computer, write up |
| 1252 | Blind: Venetian integral | Furniture/ Fitting | 1 | 2 | to internal window & door glazing as required |
| 4365 | Cupboard: full ht, adj shelves | Furniture/ Fitting | 1 | 1 | optional |
| 4410 | Cupboard: under bench | Furniture/ Fitting | 1 | 1 | optional |
| 4480 | Cupboard: wall mounted, glass doors | Furniture/ Fitting | 1 | 1 | over bench, optional |
| 6152 | Dispenser: disposable glove | Furniture/ Fitting | 2 | 1 | |
| 8291 | Air flowmeter | MEQ - General | 3 | 2 | to patient supply units |
| 8296 | Bowl stand: single | MEQ - General | 3 | 1 | |
| 8297 | Bracket: suction bottle | MEQ - General | 2 | 4 | to patient supply units |
| 8306 | IV pole: mobile | MEQ - General | 3 | 2 | |
| 8309 | Oxygen flowmeter | MEQ - General | 3 | 4 | to patient supply units |
| 8318 | Suction adapter | MEQ - General | 3 | 4 | to patient supply units |
| 8321 | Suction bottle | MEQ - General | 3 | 4 | to patient supply units |
| 8343 | Cabinet: storage, instrument, OR, double door, recessed | MEQ - Furniture | 2 | 1 | |
| 8385 | Carrier stand, suction canisters | MEQ - General | 3 | 1 | mobile |
| 8398 | Trolley: resuscitation | MEQ - Furniture | 3 | 1 | |
| 8408 | Kick bucket | MEQ - General | 3 | 2 | |
| 8411 | Stool: adjustable, OR | MEQ - Furniture | 3 | 2 | |
| 8402 | Footstool: 2-step | MEQ - Furniture | 3 | 1 | |
| 8412 | Stool: adjustable, OR, with backrest | MEQ - Furniture | 3 | 1 | |
| 8593 | Bracket: patient monitor | MEQ - General | 2 | 1 | for cardiac monitor, mounted on anaesthesia supply unit |
| 8594 | Linen carrier: dirty, single | MEQ - Furniture | 3 | 2 | |
| 8603 | Headlight: surgical | MEQ - General | 3 | 1 | |
| 8620 | Trolley: instrument | MEQ - Furniture | 3 | 2 | |
| 8622 | Trolley: gowns | MEQ - Furniture | 3 | 1 | |
| 8627 | Trolley: anaesthetic | MEQ - Furniture | 3 | 1 | |
| 8630 | Table: mayo | MEQ - Furniture | 3 | 1 | |
| 8746 | Trolley: surgical case, closed, single door | MEQ - Furniture | 3 | 1 |
| ID | Description | Grp | Qty | Ele | Data | CdW | HtW | WmW | Tap | Dns | Gas | Selection / Remarks |
| 8472 | Infusion pump: syringe | 3 | 2 | yes | opt | ___ | ___ | ___ | ___ | ___ | ___ | Qty TBC by project |
| 8473 | Infusion pump: rapid, blood/ solution warming, on stand | 3 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | Qty TBC by project |
| 8767 | Defibrillator: with monitor | 3 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | on resuscitation trolley |
| 8939 | Endoscopy tower: laparoscopy | 3 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | includes video processor, light source, insufflator, suction/ irrigator, high frequency generator (electrosurgical unit), smoke evacuator, monitor, endoscopes, and optional equipment cart |
| 8817 | Warming cabinet: single compartment, benchtop, 85L | 3 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | optional |
| 8967 | Monitor: video, medical grade, 26-inch | 2 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | mounted on surgical light monitor arm |
| 8973 | Pump: suction/ aspirator, portable | 3 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | on resuscitation trolley |
| 8989 | Infusion pump: single channel | 3 | 2 | yes | opt | ___ | ___ | ___ | ___ | ___ | ___ | Qty TBC by project |
| 8714 | Anaesthesia unit: standard | 3 | 1 | yes | opt | ___ | ___ | ___ | ___ | ___ | ___ | |
| 8758 | Sequential compression device | 3 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | |
| 8779 | Monitor: physiologic, operating theatre/ cardiac | 3 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | |
| 8786 | Supply unit: ceiling, double arm | 2 | 2 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | 1- anaesthesia supply unit (1 drop); 1- surgical supply unit (1 drop) |
| 8969 | Monitor: video, medical grade, 42-inch | 2 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | wall mounted |
| 8983 | Light: surgical, single, ceiling, with monitor arm & camera | 2 | 1 | yes | opt | ___ | ___ | ___ | ___ | ___ | ___ | optional camera attachment to light head, 1 x display monitor |
| 9067 | Operating table: mobile, electric, general | 3 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | |
| 9222 | Control panel: surgical, recessed | 2 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | includes slave analogue clock, elapsed time clock, temperature and humidity indicators and controls, IPS and UPS systems alarms, medical gas alarms, AGSS controls, theatre lamp controls, general lighting controls and power sockets as required |
| 9924 | Warming blanket unit: patient | 3 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | |
| 11400 | Computer: PC & monitor | 3 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | |
| 13363 | Pump: suction/ aspirator, surgical, mobile | 3 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | |
| 54520 | Telephone: handset, handsfree | 3 | 1 | ___ | yes | ___ | ___ | ___ | ___ | ___ | ___ | to bench |
| ID | Description | Service Category | Qty | Selection / Remarks |
| 1006 | Voice / Data outlet: double | Communications | 4 | to supply units; 2- anaesthesia supply unit , 2- surgical supply unit |
| 1006 | Voice / Data outlet: double | Communications | 2 | to nurse documentation station (for computer) |
| 5005 | Air conditioning: special | HVAC | HEPA filtered | |
| 5040 | Pressure: positive | HVAC | ||
| 2242 | General LED: colour corrected | Lighting | variable lighting level | |
| 6074 | Special: 'Laser In Use' lights | Lighting | outdside room entries, if laser to be used (optional) | |
| 7000 | Oxygen (O2) | Medical Gases | 4 | 2- anaesthesia supply unit; 2- surgical supply unit |
| 7010 | Nitrous Oxide (N2O) | Medical Gases | 2 | 2- anaesthesia supply unit |
| 7020 | Medical Air (MA) | Medical Gases | 2 | 1- anaesthesia supply unit; 1- surgical supply unit |
| 7040 | Suction | Medical Gases | 4 | 2- anaesthesia supply unit; 2- surgical supply unit |
| 7070 | Scavenge | Medical Gases | 2 | 2- anaesthesia supply unit |
| 8010 | Staff/ Nurse assist call | Nurse Call | 1 | + indicator button & light, to anaesthetic supply unit arm |
| 8080 | Emergency call | Nurse Call | 1 | + indicator button & light, to anaesthetic supply unit arm |
| 8090 | Orderly/ Porter call | Nurse Call | 1 | optional, to anaesthesia supply unit |
| 2576 | PO: Cleaner | Power | 1 | |
| 9030 | Cardiac protected/ IPS | Power | ||
| 2723 | PO: Cardiac Protected/IPS, single | Power | 16 | to supply units; 8- anaesthesia supply unit, 8- surgical supply unit |
| 1379 | Audio/ Video outlet | Communications | 4 | to supply units; 2- anaesthesia supply unit , 2- surgical supply unit |
| 2760 | Direct connection: Voice/ Data | Communications | 1 | optional, for operating light camera attachment |
| 1005 | Voice / Data outlet: single | Communications | 1 | to telephone |
| 2724 | Direct connection: Emergency power | Power | 2 | to supply units |
| 2757 | Direct connection: Uninterrupted power | Power | 2 | 1- surgical control panel, 1- surgical light |
| 2726 | PO: UPS, double | Power | 2 | for walls |
| 2726 | PO: UPS, double | Power | 2 | for nurse documentation station (for computer) |
| 2578 | PO: Emergency power, double | Power | 2 | for walls |
| 2578 | PO: Emergency power, double | Power | 2 | 1- resuscitation trolley; 1- warming cabinet (optional) |
| 2728 | PO: Single phase, high current, 32 Amp | Power | 1 | optional; for laser on wall |
| 2760 | Direct connection: Voice/ Data | Communications | 1 | for surgical control panel (to be integrated with BMS & lighting controls) |
| 2761 | Direct connection: Tool Air | Medical Gases | 2 | 1 per supply unit (for brakes) |
| 6005 | Dimmable | Lighting | ||
| 1006 | Voice / Data outlet: double | Communications | 2 | 1- 26" display monitor; 1- 42" wall mounted monitor |
| 1947 | Carbon Dioxide (CO2) | Medical Gases | 1 | 1- surgical supply unit (optional) |
| 2726 | PO: UPS, double | Power | 2 | 1- 26" display monitor; 1- 42" wall mounted monitor |
| 12011 | Radiation shielding | Shielding | for walls, floor, ceiling, doors & glazing as specified by Radiation Consultant | |
| 1006 | Voice / Data outlet: double | Communications | 2 | for walls |
| 1379 | Audio/ Video outlet | Communications | 2 | 1- 26" display monitor; 1- 42" wall mounted monitor |
| 6870 | Surgical Air (SA7) | Medical Gases | 1 | 1- surgical supply unit (optional) |
| 6909 | Wave pad access | Security | 2 per door |