| Room Code | OR-NEURO-I |
| Net Room Area Briefed | 42 |
| Hours of Operation | 24 Hours |
| Occupancy | 1 patient; 5 - 8 staff |
| Description / Special Requirements | The Operating Room - Neurosurgery provides an aseptic environment in which to carry out surgical procedures under local, regional or general anaesthetic. The Operating Room will have direct access to a Scrub-up Room, exit bay and sterile stock/set-up area. Cardiac Protected electrical area Special Air Conditioning - HEPA filtration Additional Design Considerations: - Minimum critical dimension 6000mm on at least 1 side. - 'Laser In Use' warning lights may be required outside all exit doors to room if laser equipment is to be used - Lead shielding may be required depending on use of X-ray equipment - to be assessed by Radiation Consultant - External windows are desirable - double glazed with integral Venetian blinds |
| Amendment | 16.05.2024 Fabrics & Services updated 07.05.2025 Services updated |
| ID | Fabric | Material | Finish | Specification | Selection | Remarks |
| 8040 | Door protection | Composite | Prefinished PVC | To door frame | ||
| 8010 | Door protection | Composite | Prefinished PVC | Protection plate to 900mm AFFL | ||
| 9245 | Doors | Solid Core/ Safety glass | Paint | Double leaf, observation panel | 1600mm clear opening to patient entry/exit and scrub; obs panel with sliding cover or internal venetians | |
| 1000 | Floor finish | Vinyl | Standard slip resistant | Seamless, coved | ||
| 9127 | Doors | Solid Core/ Safety glass | Paint | 1 1/2 leaf, observation panel | 1600mm clear opening to anaesthetic room; obs panel with sliding cover or integral venetians | |
| 6015 | Cornice | Plasterboard | Paint | Flush coved between wall & ceiling | ||
| 9001 | Doors | Solid Core | Paint | Single leaf | Optional; 1100mm clear opening to clean-up room | |
| 5020 | Ceiling | Plasterboard | Paint, scrub resistant | Flush set, suspended | 3000mm min height AFFL | |
| 3010 | Wall finish | Paint | Scrub resistant | epoxy paint or full height wall vinyl also acceptable | ||
| 2313 | Skirting | Vinyl | Prefinished | Floor vinyl coved, 300mmH | ||
| 9006 | Doors | Solid Core/ Safety glass | Paint | Single leaf, observation panel | 920mm clear opening to sterile stock room/ setup room, obs panel with sliding cover or integral venetians |
| ID | Description | Category | Group | Qty | Selection / Remarks |
| 1030 | Bench: resinate | Furniture/ Fitting | 1 | 1 | documentation station: computers, write-up |
| 6152 | Dispenser: disposable glove | Furniture/ Fitting | 2 | 1 | |
| 8291 | Air flowmeter | MEQ - General | 3 | 2 | to patient supply units |
| 8296 | Bowl stand: single | MEQ - General | 3 | 2 | |
| 8297 | Bracket: suction bottle | MEQ - General | 2 | 4 | to patient supply units |
| 8306 | IV pole: mobile | MEQ - General | 3 | 2 | |
| 8309 | Oxygen flowmeter | MEQ - General | 3 | 4 | to patient supply units |
| 8318 | Suction adapter | MEQ - General | 3 | 4 | to patient supply units |
| 8321 | Suction bottle | MEQ - General | 3 | 4 | to patient supply units |
| 8343 | Cabinet: storage, instrument, OR, double door, recessed | MEQ - Furniture | 2 | 1 | Optional |
| 8385 | Carrier stand, suction canisters | MEQ - General | 3 | 1 | |
| 8398 | Trolley: resuscitation | MEQ - Furniture | 3 | 1 | |
| 8408 | Kick bucket | MEQ - General | 3 | 2 | |
| 8411 | Stool: adjustable, OR | MEQ - Furniture | 3 | 2 | |
| 8412 | Stool: adjustable, OR, with backrest | MEQ - Furniture | 3 | 1 | for anaesthetist |
| 8593 | Bracket: patient monitor | MEQ - General | 2 | 1 | for cardiac monitor, mounted on anaesthesia supply unit |
| 8594 | Linen carrier: dirty, single | MEQ - Furniture | 3 | 2 | |
| 8603 | Headlight: surgical | MEQ - General | 3 | 1 | |
| 8620 | Trolley: instrument | MEQ - Furniture | 3 | 3 | |
| 8622 | Trolley: gowns | MEQ - Furniture | 3 | 1 | |
| 8627 | Trolley: anaesthetic | MEQ - Furniture | 3 | 1 | |
| 8630 | Table: mayo | MEQ - Furniture | 3 | 1 |
| ID | Description | Grp | Qty | Ele | Data | CdW | HtW | WmW | Tap | Dns | Gas | Selection / Remarks |
| 6468 | Camera: in room | 2 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | PTZ, optional, part of integration system |
| 8472 | Infusion pump: syringe | 3 | 2 | yes | opt | ___ | ___ | ___ | ___ | ___ | ___ | Qty TBC by project |
| 8473 | Infusion pump: rapid, blood/ solution warming, on stand | 3 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | Qty TBC by project |
| 8548 | Light: surgical, single, ceiling, with two monitor arms & camera | 2 | 1 | yes | opt | ___ | ___ | ___ | ___ | ___ | ___ | light configurations may change depending on OR integration system requirements |
| 8767 | Defibrillator: with monitor | 3 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | |
| 8714 | Anaesthesia unit: standard | 3 | 1 | yes | opt | ___ | ___ | ___ | ___ | ___ | ___ | |
| 8786 | Supply unit: ceiling, double arm | 2 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | surgical supply unit |
| 8822 | Warming cabinet: dual compartment, freestanding, 500L | 3 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | optional |
| 8779 | Monitor: physiologic, operating theatre/ cardiac | 3 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | on anaesthesia supply unit |
| 8939 | Endoscopy tower: laparoscopy | 3 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | includes video processor, light source, insufflator, suction/ irrigator, high frequency generator (electrosurgical unit), smoke evacuator, monitor, endoscopes, and optional equipment cart |
| 8941 | Integration system: OR | 2 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | optional, includes 2 display monitors and 1 control monitor in the surgical field, 2 display monitor on the wall, and 1 control monitor on the nurse workstation |
| 8953 | Hypo-hyperthermia unit: general | 3 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | |
| 8966 | Monitor: video, medical grade, 19-inch | 2 | 2 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | optional, control monitors part of integration system |
| 8967 | Monitor: video, medical grade, 26-inch | 2 | 2 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | optional, display monitors part of integration system |
| 8970 | Monitor: video, medical grade, 55-inch | 2 | 2 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | optional, wall mounted part of integration system |
| 8973 | Pump: suction/ aspirator, portable | 3 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | |
| 8989 | Infusion pump: single channel | 3 | 2 | yes | opt | ___ | ___ | ___ | ___ | ___ | ___ | Qty TBC by project |
| 9023 | Tracking system: instrument tray | 3 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | optional, workstation part of CSSD instrument tracking system |
| 9222 | Control panel: surgical, recessed | 2 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | includes slave analogue clock, elapsed time clock, temperature and humidity indicators and controls, IPS and UPS systems alarms, medical gas alarms, AGSS controls, theatre lamp controls, general lighting controls and power sockets as required |
| 9547 | Medication dispensing system: automated, anaesthesia | 3 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | optional, quantity and modules depend on service requirements; with this option anaesthetic trolley may not be required |
| 9597 | Supply unit: ceiling, anaesthesia, tandem, double arm | 2 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | anaesthesia supply unit |
| 10173 | Cabinet: server, OR integration | 2 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | optional, part of integration system |
| 10389 | Light: surgical, single, ceiling, with monitor arm | 2 | 1 | yes | opt | ___ | ___ | ___ | ___ | ___ | ___ | light configurations may change depending on OR integration system requirements |
| 11400 | Computer: PC & monitor | 3 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | for nursing & medical staff documentation |
| 8928 | Tissue ablation unit: ultrasonic | 3 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | |
| 8961 | Monitor: physiologic, intracranial pressure (ICP) | 3 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | |
| 9069 | Operating table: mobile, electric, neuro | 3 | 1 | yes | opt | ___ | ___ | ___ | ___ | ___ | ___ | |
| 9600 | Operating microscope: neuro, mobile | 3 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | |
| 10025 | Image guided system: surgical navigation, neuro | 3 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | |
| 13363 | Pump: suction/ aspirator, surgical, mobile | 3 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | |
| 54520 | Telephone: handset, handsfree | 3 | 1 | ___ | yes | ___ | ___ | ___ | ___ | ___ | ___ | on bench |
| ID | Description | Service Category | Qty | Selection / Remarks |
| 1006 | Voice / Data outlet: double | Communications | 2 | to nurse documentation station |
| 1005 | Voice / Data outlet: single | Communications | 2 | 1- telephone; 1- anaesthesia medication dispensing unit |
| 1379 | Audio/ Video outlet | Communications | 8 | to supply units; 2- per anaesthetic arm, 4- surgical supply unit |
| 1947 | Carbon Dioxide (CO2) | Medical Gases | 1 | 1- surgical supply unit (optional) |
| 8010 | Staff/ Nurse assist call | Nurse Call | 1 | + indicator button & light; to anaesthesia supply unit |
| 2024 | Music system | Communications | 1 | optional |
| 5005 | Air conditioning: special | HVAC | HEPA filtered | |
| 5040 | Pressure: positive | HVAC | ||
| 2242 | General LED: colour corrected | Lighting | variable lighting level | |
| 6074 | Special: 'Laser In Use' lights | Lighting | outside room entries, if laser to be used (optional) | |
| 7000 | Oxygen (O2) | Medical Gases | 4 | 1- per anaesthetic supply unit arm; 2- surgical supply unit |
| 7010 | Nitrous Oxide (N2O) | Medical Gases | 2 | 1- per anaesthetic supply unit arm |
| 7020 | Medical Air (MA) | Medical Gases | 2 | 1- anaesthesia supply unit; 1- surgical supply unit |
| 7040 | Suction | Medical Gases | 4 | 1- per anaesthetic supply unit arm; 2- surgical supply unit |
| 7070 | Scavenge | Medical Gases | 2 | 1- per anaesthetic supply unit arm |
| 8080 | Emergency call | Nurse Call | 1 | + indicator button & light; to anaesthesia supply unit |
| 8090 | Orderly/ Porter call | Nurse Call | 1 | optional; to anaesthetia supply unit |
| 2576 | PO: Cleaner | Power | 1 | |
| 9030 | Cardiac protected/ IPS | Power | ||
| 2723 | PO: Cardiac Protected/IPS, single | Power | 24 | to supply units; 6- per anaesthetic arm, 12- surgical arm |
| 2724 | Direct connection: Emergency power | Power | 2 | to supply units |
| 2728 | PO: Single phase, high current, 32 Amp | Power | 1 | optional; for laser on wall |
| 1006 | Voice / Data outlet: double | Communications | 8 | to supply units; 2- per anaesthetic arm, 4- surgical supply unit |
| 2756 | Cable conduit | Electrical | 1 | optional (part of integration system); for integration system server cabinet |
| 2578 | PO: Emergency power, double | Power | 2 | for walls |
| 2578 | PO: Emergency power, double | Power | 2 | 1- resuscitation trolley; 1- warming cabinet (optional) |
| 2726 | PO: UPS, double | Power | 2 | for walls |
| 2760 | Direct connection: Voice/ Data | Communications | 2 | 1- in room camera (optional, part of integration system), 1 - operating light camera attachment |
| 2760 | Direct connection: Voice/ Data | Communications | 1 | for surgical control panel (to be integrated with BMS & lighting controls) |
| 2761 | Direct connection: Tool Air | Medical Gases | 2 | 1 per supply unit (for brakes) |
| 2757 | Direct connection: Uninterrupted power | Power | 3 | 1- surgical control panel, 2- operating lights (1 each) |
| 2757 | Direct connection: Uninterrupted power | Power | 1 | optional (part of integration system); ; for in room camera |
| 2726 | PO: UPS, double | Power | 2 | for nurse documentation station |
| 2726 | PO: UPS, double | Power | 2 | optional (part of integration system); for integration system server cabinet |
| 2726 | PO: UPS, double | Power | 1 | optional; anaesthesia medication dispensing unit |
| 12011 | Radiation shielding | Shielding | for walls, floor, ceiling, doors & glazing as specified by Radiation Consultant | |
| 1006 | Voice / Data outlet: double | Communications | 3 | optional (part of integration system); 1- 19" wall mounted control monitor, 2- 55" wall monitors (1 each) |
| 1006 | Voice / Data outlet: double | Communications | 3 | optional (part of integration system); for 1- 19" control monitor and 2- 26" display monitors within the surgical field (1 each) |
| 2726 | PO: UPS, double | Power | 3 | optional (part of integration system); 1- 19" wall mounted control monitor, 2- 55" wall monitors (1 each) |
| 2726 | PO: UPS, double | Power | 3 | optional (part of integration system); for 1- 19" control monitor and 2- 26" display monitors within the surgical field (1 each) |
| 6005 | Dimmable | Lighting | ||
| 1006 | Voice / Data outlet: double | Communications | 2 | for walls |
| 1379 | Audio/ Video outlet | Communications | 3 | optional (part of integration system); 1- 19" wall mounted control monitor, 2- 55" wall monitors (1 each) |
| 1379 | Audio/ Video outlet | Communications | 3 | optional (part of integration system); for 1- 19" control monitor and 2- 26" display monitors within the surgical field (1 each) |
| 2694 | PO: UPS, single | Power | 2 | optional; to loudspeaker and on-air lamp (part of integration system - refer to manufacturer's specifications) |
| 6870 | Surgical Air (SA7) | Medical Gases | 2 | 2- surgical supply unit |
| 6909 | Wave pad access | Security | 2 per door |