1 Bed Room - Standard, 18m2, Outboard Ensuite

Room Code PET-CT-I
Net Room Area Briefed 48
Hours of Operation 8am to 6pm, daily
Occupancy 1 patient; up to 3 staff assisting
Description / Special Requirements The PET/CT Scanning Room provides an enclosed, radiation shielded room with a hybrid PET camera and CT Scanning unit for non-invasive scanning procedures. The patients have been injected with a radionucliede and are generally awake during the scanning procedure. A Control room and a Computer Equipmment room will be located adjacent. The PET Scanning room will include a handwashing basin. CCTV cameras will be required for patient observation with monitors in the Control Room. Acoustics: Medium Acoustic privacy is required Body Protected electrical area Additional Design Considerations: - Radiation shielding as advised by Radiation Consultant - Unistrut ceiling able to carry moving loads may be required - Cable ducts between Control Room and Computer Room may be required - 'X-ray in Use' lights are required outside each entry door - operable by the CT /PET equipment - Power should be on emergency supply Doors may need to be motorised due to the weight from the lead sheilding - seek Radiation Consultants advice
Amendment 19.06.2019 First Draft 03.09.2023 RDS updated

Fabric and outline specifications

ID Fabric Material Finish Specification Selection Remarks
1000 Floor finish Vinyl Standard slip resistant Seamless, coved
2000 Skirting Vinyl Prefinished Floor vinyl coved, 150mmH
8010 Door protection Composite Prefinished PVC Protection plate to 900mm AFFL
1045 Floor finish Vinyl, non slip Textured Seamless, coved under basin
5010 Ceiling Plasterboard Paint, washable Flush set, suspended at 3000mm AFFL
9130 Doors Solid Core Paint 1 1/2 leaf, with lead shielding patient entry/exit 1600mm clear opening
8040 Door protection Composite Prefinished PVC To door frame
2767 Cornice Plasterboard Paint Square set
3022 Wall finish Resinate, 6mm Prefinished Splashback to basin, other smooth impervious finish also acceptable
3000 Wall finish Paint Acrylic, washable
4031 Wall protection Composite Prefinished PVC Corner guards to 1500mm AFFL as required; other heights also acceptable as per project standardisation

Fittings and Furniture (FF)

ID Description Category Group Qty Selection / Remarks
6152 Dispenser: disposable glove Furniture/ Fitting 2 1 near door
6154 Dispenser: paper/ hand towel Furniture/ Fitting 2 1 to basin
6158 Dispenser: soap antiseptic Furniture/ Fitting 2 1 to basin
8291 Air flowmeter MEQ - General 3 1
8297 Bracket: suction bottle MEQ - General 2 2
8309 Oxygen flowmeter MEQ - General 3 2
8318 Suction adapter MEQ - General 3 2
8321 Suction bottle MEQ - General 3 2
8635 Lead screen: mobile MEQ - Imaging 3 1 optional
8611 Waste bin: radioactive, 20 litres MEQ - Nuclear Medicine 3 1
1050 Bench: laminate Furniture/ Fitting 1 1 with inset sink optional
9817 Lead screen: mobile, PET MEQ - Nuclear Medicine 3 1
8402 Footstool: 2-step MEQ - Furniture 3 1
10061 Waste bin: General, 20 Litres Furniture/ Fitting 3 1

Fixtures, Equipment and associated Services (FE)

ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
3100 Basin: scrub, Type A 1 1 ___ ___ yes ___ yes yes yes ___
7300 Camera: CCTV security 1 yes ___ ___ ___ ___ ___ ___ ___ part of PET/ CT scanning system configurations
40404 Tapware: sensor 1 1 yes ___ yes yes yes ___ ___ ___ straight spout
9109 Injector: contrast media, mobile, dual head, CT 3 1 yes yes ___ ___ ___ ___ ___ ___
54510 Telephone: handset, standard 3 1 ___ yes ___ ___ ___ ___ ___ ___
8929 Scanning unit: PET/ CT, 64-slice 2 1 yes yes ___ ___ ___ ___ ___ ___
8782 Monitor: physiologic, vital signs, on stand 3 1 yes opt ___ ___ ___ ___ ___ ___ optional

Services

ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 3 1- patient services panel; 1- bench; 1- wall
1040 Intercom Communications 1 handsfree to control room
5000 Airconditioning HVAC Include local climate control, relative negative pressure required
6001 General: colour corrected Lighting variable lighting/ selective switching
6076 Special: 'X-ray In Use' lights Lighting 1
7000 Oxygen (O2) Medical Gases 2 patient services panel
7010 Nitrous Oxide (N2O) Medical Gases 1 patient services panel
7020 Medical Air (MA) Medical Gases 1 patient services panel
7040 Suction Medical Gases 2 patient services panel
7070 Scavenge Medical Gases 1 patient services panel
8080 Emergency call Nurse Call 1 + indicator button & light
2579 PO: Emergency power, single Power 3 to patient services panels
2576 PO: Cleaner Power 1 As required
9040 Body protected Power
2233 Direct connection: Emergency power Power 1 to sensor tap
12011 Radiation shielding Shielding to walls, floor, ceiling, doors & glazing as specified by Radiation Consultant
2473 Power over Ethernet (PoE) Power 1 1 - to CCTV
2502 Clean Agent Gas Suppression System Fire Services
8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light
11505 Floor duct for power & data Services Ducts 1 between equipment room, control room and scanning room
2578 PO: Emergency power, double Power 1 1- bench
2556 Trunking: 200mm x 70mm Electrical Installations 1 between equipment room, control room and scanning room
2578 PO: Emergency power, double Power 4 to walls (including injector)
11000 Wall panel Services Panels 1 flush mounted
6005 Dimmable Lighting
1080 Clock: master clock Communications 1 battery/ POE/ electrical connection TBC