Print Download PDF Version
1 Bed Room - Standard, 18m2, Outboard Ensuite
Room Code
PBTR-A12-I
Net Room Area Briefed
12
Hours of Operation
24 Hours
Occupancy
1 patient; 1 - 2 staff
Description / Special Requirements
The Patient Bed Bay Acute Treatment may be used for assessment and treatment of patients with acute conditions and will be located within the Emergency Unit. The Bay may have partition side walls; glazing is recommended. The Patient Bay will have close access to a staff handwashing basin.
Body Protected electrical area
Amendment
24.10.10, - First Draft
Fabric and outline specifications
ID
Fabric
Material
Finish
Specification
Selection
Remarks
5010
Ceiling
Plasterboard
Paint, washable
Flush set, suspended
7055
Observation
Alum/ Glass
Powdercoat
Internal window, double glazed
to partition walls, if provided
4031
Wall protection
Composite
Prefinished PVC
Corner guards to 1500 AFFL
As required
6025
Cornice
Aluminium
Powdercoat
shadow line
1000
Floor finish
Vinyl
Standard slip resistant
Seamless, coved
2000
Skirting
Vinyl
Prefinished
Floor vinyl coved, 150mmH
3000
Wall finish
Paint
Acrylic, washable
3092
Wall protection
MDF
Laminate
Bed protection wall panel
4020
Wall protection
Composite
Prefinished PVC
Crash rail at 900 AFFL
As required
Fittings and Furniture (FF)
ID
Description
Category
Group
Qty
Selection / Remarks
150
Air flowmeter
Furniture/ Fitting
3
1
1090
Bench: laminate, free standing
Furniture/ Fitting
3
1
optional
1252
Blind: Venetian integral
Furniture/ Fitting
1
2
to internal windows if provided
1465
Bracket: suction bottle
Furniture/ Fitting
2
2
1470
Bracket: sharps
Furniture/ Fitting
2
1
2650
Chair: visitor, patient
Furniture/ Fitting
3
1
4600
Curtain track: bed screen
Metalwork
1
1
5000
Curtain: bed screen
Furniture/ Fitting
3
1
6152
Dispenser: disposable glove
Furniture/ Fitting
2
1
10700
IV hanger for ceiling track
Metalwork
1
1
11200
IV track: ceiling mounted
Metalwork
1
1
12900
Louvred panel: for storage-bins
Metalwork
1
2
optional, for storage
15100
Bracket: monitor
Furniture/ Fitting
3
1
optional, may have ergonomic arm
16250
Oxygen flowmeter
Furniture/ Fitting
3
2
19700
Sharps bin
Furniture/ Fitting
3
1
19800
Shelf: laminate
Furniture/ Fitting
1
1
above services panel, optional
21755
Storage bins
Furniture/ Fitting
3
10
optional, for storage on louvred panel
21950
Suction adapter
Furniture/ Fitting
3
2
22000
Suction bottle
Furniture/ Fitting
3
2
23952
Trolley: small
Furniture/ Fitting
3
2
1 trolley under bench
Fixtures, Equipment and associated Services (FE)
ID
Description
Grp
Qty
Ele
Data
CdW
HtW
WmW
Tap
Dns
Gas
Selection / Remarks
3725
Bed: emergency, electric
3
1
yes
___
___
___
___
___
___
___
15900
Diagnostic set: wall mounted
3
1
yes
___
___
___
___
___
___
___
optional
32150
Light: procedure, ceiling
1
1
yes
___
___
___
___
___
___
___
36050
Monitor: cardiac
3
1
yes
opt
___
___
___
___
___
___
optional
Services
ID
Description
Service Category
Qty
Selection / Remarks
1006
Voice / Data outlet: double
Communications
1
services panel, 1 outlet for telephone
1120
Monitor connection facilities and cabling
Communications
1
optional, if networked monitoring required
5000
Airconditioning
HVAC
6001
General: colour corrected
Lighting
7000
Oxygen (O2)
Medical Gases
2
services panel
7010
Nitrous Oxide (N2O)
Medical Gases
1
services panel, optional
7020
Medical Air (MA)
Medical Gases
1
services panel
7040
Suction
Medical Gases
2
services panel
7070
Scavenge
Medical Gases
1
services panel, if N2O provided
8000
Patient/ Staff call
Nurse Call
1
+ indicator button & light
8005
Patient call handset
Nurse Call
1
call button on the handset
8010
Staff/ Nurse assist call
Nurse Call
1
+ indicator button & light
8080
Emergency call
Nurse Call
1
+ indicator button & light
9000
GPO: Single
Power
3
services panel
9000
GPO: Single
Power
1
for electric bed
9010
GPO: Emergency power, single
Power
4
services panel, 1 for monitor, if required
9040
Body protected
Power
9060
GPO: Special: for equipment
Power
1
procedure light
11000
Wall panel
Services Panels
1