A Single Bed Bay for patient requiring critical care nursing and medical treatment; Visual access to Staff Station is required; Screen curtains are required for patient privacy. Maximum natural light is required to patient beds.
Acoustics: Acoustic privacy is required.
Cardiac Protected Electrical Area/ IPS - Isolated Power Supply
Amendment
24.10.2010 First Draft
09.01.2017 Fabric, FF, FE & Services updated
Fabric and outline specifications
ID
Fabric
Material
Finish
Specification
Selection
Remarks
1000
Floor finish
Vinyl
Standard slip resistant
Seamless, coved
2000
Skirting
Vinyl
Prefinished
Floor vinyl coved, 150mmH
3000
Wall finish
Paint
Acrylic, washable
5010
Ceiling
Plasterboard
Paint, washable
Flush set, suspended
7055
Observation
Alum/ Glass
Powdercoat
Internal window, double glazed
to partition walls, with integral Venetians
7001
Windows
desirable
4031
Wall protection
Composite
Prefinished PVC
Corner guards to 1500 AFFL
3022
Wall finish
Resinate, 6mm
Prefinished
Splashback
to basin, tiles also acceptable
6025
Cornice
Aluminium
Powdercoat
shadow line
square set also acceptable
Fittings and Furniture (FF)
ID
Description
Category
Group
Qty
Selection / Remarks
150
Air flowmeter
Furniture/ Fitting
3
2
to services pendants
1252
Blind: Venetian integral
Furniture/ Fitting
1
3
to external and internal windows, controls to both sides of internal windows