An single Bed Bay for patient requiring high level nursing care, observation and medical treatment; Visual access to Staff Station is required; Screen curtains are required for patient privacy. Maximum natural light is required to patient beds.
Acoustics: Acoustic privacy is required.
Cardiac Protected Electrical Area
Amendment
03.03.2016 First Draft
24.05.2023 RDS reviewed
20.05.2025 RDS reviewed
Fabric and outline specifications
ID
Fabric
Material
Finish
Specification
Selection
Remarks
3000
Wall finish
Paint
Acrylic, washable
5010
Ceiling
Plasterboard
Paint, washable
Flush set, suspended
7001
Windows
natural light & outlook desirable
3022
Wall finish
Resinate, 6mm
Prefinished
Splashback
to basin
2000
Skirting
Vinyl
Prefinished
Floor vinyl coved, 150mmH
2767
Cornice
Plasterboard
Paint
Square set
1000
Floor finish
Vinyl
Standard slip resistant
Seamless, coved
Fittings and Furniture (FF)
ID
Description
Category
Group
Qty
Selection / Remarks
1252
Blind: Venetian integral
Furniture/ Fitting
1
1
to external windows
2610
Chair: visitor, stackable
Furniture/ Fitting
3
1
2926
Dispenser: hand sanitiser
Furniture/ Fitting
2
1
4600
Curtain track: bed screen
Metalwork
1
1
5000
Curtain: bed screen
Furniture/ Fitting
3
1
6152
Dispenser: disposable glove
Furniture/ Fitting
2
1
near entry
6154
Dispenser: paper/ hand towel
Furniture/ Fitting
2
1
to basin
6158
Dispenser: soap antiseptic
Furniture/ Fitting
2
1
to basin
8291
Air flowmeter
MEQ - General
3
2
8297
Bracket: suction bottle
MEQ - General
1
4
mounted on pendant
8309
Oxygen flowmeter
MEQ - General
3
4
8318
Suction adapter
MEQ - General
3
4
8321
Suction bottle
MEQ - General
3
4
8332
Table: overbed
MEQ - Furniture
3
1
8404
Bracket: sharps disposal
MEQ - General
3
1
21700
Stool: adjustable, mobile, high
Furniture/ Fitting
3
1
for staff
8593
Bracket: patient monitor
MEQ - General
2
1
8608
Waste bin: clinical, 120 litres
MEQ - Furniture
3
1
8724
Trolley: multi-purpose
MEQ - Furniture
3
1
8594
Linen carrier: dirty, single
MEQ - Furniture
3
1
9117
Sharps disposal: wall mounted, 7L
MEQ - General
2
1
10061
Waste bin: General, 20 Litres
Furniture/ Fitting
3
1
23400
Bracket: television, ceiling
Metalwork
1
1
Fixtures, Equipment and associated Services (FE)
ID
Description
Grp
Qty
Ele
Data
CdW
HtW
WmW
Tap
Dns
Gas
Selection / Remarks
3031
Television: flat screen
3
1
yes
___
___
___
___
___
___
___
3100
Basin: scrub, Type A
1
1
___
___
yes
___
yes
yes
yes
___
8989
Infusion pump: single channel
3
2
yes
opt
___
___
___
___
___
___
Qty TBC by project
10132
Clock: master clock
3
1
yes
opt
___
___
___
___
___
___
15985
Dialysis station
1
1
___
___
yes
___
yes
yes
yes
___
optional; with RO water outlet & tundish drain
40404
Tapware: sensor
1
1
yes
___
yes
yes
yes
___
___
___
straight spout
54520
Telephone: handset, handsfree
3
1
___
yes
___
___
___
___
___
___
wall mounted
8472
Infusion pump: syringe
3
4
yes
opt
___
___
___
___
___
___
Qty TBC by project
8485
Monitor: physiologic, critical care
3
1
yes
yes
___
___
___
___
___
___
8733
Bed: ICU, electric
3
1
yes
opt
___
___
___
___
___
___
8758
Sequential compression device
3
1
yes
___
___
___
___
___
___
___
optional, may be kept in store
8764
Chair: recliner, electric
3
1
yes
___
___
___
___
___
___
___
8788
Supply unit: ceiling, tandem, double arm
2
1
yes
yes
___
___
___
___
___
___
8988
Infusion pump: enteral feeding
3
1
yes
opt
___
___
___
___
___
___
Qty TBC by project
9005
Ventilator: adult/ paediatric
3
1
yes
yes
___
___
___
___
___
___
9456
Light: procedure, single, ceiling mounted
2
1
yes
___
___
___
___
___
___
___
optional, could be part of the pendant configurations
Services
ID
Description
Service Category
Qty
Selection / Remarks
1006
Voice / Data outlet: double
Communications
3
1- wall, 2- services pendant
2559
IPTV
Communications
1
5000
Airconditioning
HVAC
2242
General LED: colour corrected
Lighting
6060
Special: night lights
Lighting
7000
Oxygen (O2)
Medical Gases
4
to services pendant
7020
Medical Air (MA)
Medical Gases
2
to services pendant
7040
Suction
Medical Gases
4
to services pendant
8000
Patient to Staff call
Nurse Call
1
+ indicator button & light; to services pendant
8005
Patient call handset
Nurse Call
1
call button on the handset
8010
Staff/ Nurse assist call
Nurse Call
1
+ indicator button & light; to services pendant
8080
Emergency call
Nurse Call
1
+ indicator button & light; to services pendant
2577
PO: Double
Power
1
to wall
2578
PO: Emergency power, double
Power
1
optional; to dialysis station
2576
PO: Cleaner
Power
1
9030
Cardiac protected/ IPS
Power
1005
Voice / Data outlet: single
Communications
1
to wall phone
2724
Direct connection: Emergency power
Power
3
1- for sensor operated tapware; 1- to procedure light; 1- services pendant