Print Download PDF Version
Patient Bay - Holding, 10m2
Room Code
PBTR-H-10-I
Net Room Area Briefed
10
Hours of Operation
24 Hours
Occupancy
1 patient; 1-2 staff intermittently
Description / Special Requirements
A patient Bed Bay used for holding of patients prior to procedures, observation of patients following procedures or for assessment and treatment of patients with non acute conditions. The Patient Bay will have close access to a staff handwashing basin.
Body Protected electrical area
Amendment
24.10.2010 First Issue
30.05.2016 Revisions to FF, Services
01.09.2022 FF, FE & Services updated
03.09.2023 RDS updated
Fabric and outline specifications
ID
Fabric
Material
Finish
Specification
Selection
Remarks
3000
Wall finish
Paint
Acrylic, washable
5010
Ceiling
Plasterboard
Paint, washable
Flush set, suspended
3092
Wall protection
MDF
Laminate
Bed protection wall panel
1000
Floor finish
Vinyl
Standard slip resistant
Seamless, coved
2767
Cornice
Plasterboard
Paint
Square set
2000
Skirting
Vinyl
Prefinished
Floor vinyl coved, 150mmH
Fittings and Furniture (FF)
ID
Description
Category
Group
Qty
Selection / Remarks
8291
Air flowmeter
MEQ - General
3
1
optional, required if air outlet provided
8297
Bracket: suction bottle
MEQ - General
2
1
required if suction outlet provided
2650
Chair: visitor, patient
Furniture/ Fitting
3
1
optional
4600
Curtain track: bed screen
Metalwork
1
1
5000
Curtain: bed screen
Furniture/ Fitting
3
1
2926
Dispenser: hand sanitiser
Furniture/ Fitting
2
1
6152
Dispenser: disposable glove
Furniture/ Fitting
2
1
8309
Oxygen flowmeter
MEQ - General
3
1
required if oxygen outlet provided
8318
Suction adapter
MEQ - General
3
1
required if suction outlet provided
8321
Suction bottle
MEQ - General
3
1
required if suction outlet provided
8404
Bracket: sharps disposal
MEQ - General
2
1
8982
Stretcher: procedure/ recovery
MEQ - Furniture
3
spatial provision required
9117
Sharps disposal: wall mounted, 7L
MEQ - General
2
1
Fixtures, Equipment and associated Services (FE)
ID
Description
Grp
Qty
Ele
Data
CdW
HtW
WmW
Tap
Dns
Gas
Selection / Remarks
8542
Light: examination, single, ceiling mounted
1
1
yes
___
___
___
___
___
___
___
optional
Services
ID
Description
Service Category
Qty
Selection / Remarks
9040
Body protected
Power
2579
PO: Emergency power, single
Power
3
to bedhead
2582
PO: Single
Power
1
to bedhead, low level for bed
2582
PO: Single
Power
3
to bedhead
8080
Emergency call
Nurse Call
1
+ indicator button & light
8010
Staff/ Nurse assist call
Nurse Call
1
+ indicator button & light
8005
Patient call handset
Nurse Call
1
call button on the handset
8000
Patient to Staff call
Nurse Call
1
+ indicator button & light
7040
Suction
Medical Gases
1
optional, dependant on use of the bay
7020
Medical Air (MA)
Medical Gases
1
optional, dependant on use of the bay
7000
Oxygen (O2)
Medical Gases
1
optional, dependant on use of the bay
6030
Special: downlights
Lighting
over bed/ trolley
6001
General: colour corrected
Lighting
5000
Airconditioning
HVAC
1006
Voice / Data outlet: double
Communications
1
to bedhead
2724
Direct connection: Emergency power
Power
1
to exam light
11000
Wall panel
Services Panels
1