1 Bed Room - Standard, 18m2, Outboard Ensuite

Room Code PBTR-H-10-I
Net Room Area Briefed 10
Hours of Operation 24 Hours
Occupancy 1 patient; 1-2 staff intermittently
Description / Special Requirements A patient Bed Bay used for holding of patients prior to procedures, observation of patients following procedures or for assessment and treatment of patients with non acute conditions. The Patient Bay will have close access to a staff handwashing basin. Body Protected electrical area
Amendment 24.10.2010 First Issue 30.05.2016 Revisions to FF, Services 01.09.2022 FF, FE & Services updated 03.09.2023 RDS updated

Fabric and outline specifications

ID Fabric Material Finish Specification Selection Remarks
3000 Wall finish Paint Acrylic, washable
5010 Ceiling Plasterboard Paint, washable Flush set, suspended
3092 Wall protection MDF Laminate Bed protection wall panel
1000 Floor finish Vinyl Standard slip resistant Seamless, coved
2767 Cornice Plasterboard Paint Square set
2000 Skirting Vinyl Prefinished Floor vinyl coved, 150mmH

Fittings and Furniture (FF)

ID Description Category Group Qty Selection / Remarks
8291 Air flowmeter MEQ - General 3 1 optional, required if air outlet provided
8297 Bracket: suction bottle MEQ - General 2 1 required if suction outlet provided
2650 Chair: visitor, patient Furniture/ Fitting 3 1 optional
4600 Curtain track: bed screen Metalwork 1 1
5000 Curtain: bed screen Furniture/ Fitting 3 1
2926 Dispenser: hand sanitiser Furniture/ Fitting 2 1
6152 Dispenser: disposable glove Furniture/ Fitting 2 1
8309 Oxygen flowmeter MEQ - General 3 1 required if oxygen outlet provided
8318 Suction adapter MEQ - General 3 1 required if suction outlet provided
8321 Suction bottle MEQ - General 3 1 required if suction outlet provided
8404 Bracket: sharps disposal MEQ - General 2 1
8982 Stretcher: procedure/ recovery MEQ - Furniture 3 spatial provision required
9117 Sharps disposal: wall mounted, 7L MEQ - General 2 1

Fixtures, Equipment and associated Services (FE)

ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
8542 Light: examination, single, ceiling mounted 1 1 yes ___ ___ ___ ___ ___ ___ ___ optional

Services

ID Description Service Category Qty Selection / Remarks
9040 Body protected Power
2579 PO: Emergency power, single Power 3 to bedhead
2582 PO: Single Power 1 to bedhead, low level for bed
2582 PO: Single Power 3 to bedhead
8080 Emergency call Nurse Call 1 + indicator button & light
8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light
8005 Patient call handset Nurse Call 1 call button on the handset
8000 Patient to Staff call Nurse Call 1 + indicator button & light
7040 Suction Medical Gases 1 optional, dependant on use of the bay
7020 Medical Air (MA) Medical Gases 1 optional, dependant on use of the bay
7000 Oxygen (O2) Medical Gases 1 optional, dependant on use of the bay
6030 Special: downlights Lighting over bed/ trolley
6001 General: colour corrected Lighting
5000 Airconditioning HVAC
1006 Voice / Data outlet: double Communications 1 to bedhead
2724 Direct connection: Emergency power Power 1 to exam light
11000 Wall panel Services Panels 1 as required for medical gases