Print Download PDF Version
Patient Bay - Holding, Enclosed, 12m2
Room Code
PBHE-12-I
Net Room Area Briefed
12
Hours of Operation
24 Hours
Occupancy
1 patient; 1 - 2 staff intermittently
Description / Special Requirements
An enclosed Patient Bed Bay used for holding patients prior to procedures, observation of patients following procedures and/or assessment and treatment of patients with non acute conditions.
Each bay must be large enough to accommodate an adult bed with additional space for monitoring equipment and to ensure access for staff in case of emergency.
Each bay or cubicle shall have a minimum clearance of 91.44 centimeters (3 feet) between walls or partitions and the sides and foot of stretchers or patient beds.
The Enclosed Patient Bay may be used for isolation of patients and will contain a staff handwashing basin.
Patient toilets and emergency equipment should be readily accessible.
Body Protected electrical area
Amendment
24.10.2010 First Draft
31.01.2017 Description, Fabric, FF, FE, Services updated
03.09.2023 RDS updated
Fabric and outline specifications
ID
Fabric
Material
Finish
Specification
Selection
Remarks
4020
Wall protection
Composite
Prefinished PVC
Crash rail at 900mm AFFL
1000
Floor finish
Vinyl
Standard slip resistant
Seamless, coved
2000
Skirting
Vinyl
Prefinished
Floor vinyl coved, 150mmH
5010
Ceiling
Plasterboard
Paint, washable
Flush set, suspended
3022
Wall finish
Resinate, 6mm
Prefinished
Splashback
to basin, other smooth impervious finish also acceptable
3000
Wall finish
Paint
Acrylic, washable
3092
Wall protection
MDF
Laminate
Bed protection wall panel
7001
Windows
desirable
9010
Doors
Alum/ Toughened glass
Powdercoat/ paint
Single leaf, fully glazed
1200mm clear opening, sliding, surface mounted
7035
Observation
Alum/ Glass
Powdercoat
Internal window
optional to front and side walls
2767
Cornice
Plasterboard
Paint
Square set
Fittings and Furniture (FF)
ID
Description
Category
Group
Qty
Selection / Remarks
1252
Blind: Venetian integral
Furniture/ Fitting
1
2
to internal & external windows
2650
Chair: visitor, patient
Furniture/ Fitting
3
1
optional
4600
Curtain track: bed screen
Metalwork
1
1
5000
Curtain: bed screen
Furniture/ Fitting
3
1
6152
Dispenser: disposable glove
Furniture/ Fitting
2
1
6154
Dispenser: paper/ hand towel
Furniture/ Fitting
2
1
to basin
6158
Dispenser: soap antiseptic
Furniture/ Fitting
2
1
to basin
8291
Air flowmeter
MEQ - General
3
1
optional
8297
Bracket: suction bottle
MEQ - General
2
1
8309
Oxygen flowmeter
MEQ - General
3
1
8318
Suction adapter
MEQ - General
3
1
8321
Suction bottle
MEQ - General
3
1
8332
Table: overbed
MEQ - Furniture
3
1
optional
8404
Bracket: sharps disposal
MEQ - General
2
1
8982
Stretcher: procedure/ recovery
MEQ - Furniture
3
0
spatial provision required
9117
Sharps disposal: wall mounted, 7L
MEQ - General
2
1
10061
Waste bin: General, 20 Litres
Furniture/ Fitting
3
1
Fixtures, Equipment and associated Services (FE)
ID
Description
Grp
Qty
Ele
Data
CdW
HtW
WmW
Tap
Dns
Gas
Selection / Remarks
2800
Basin: handwash, Type B
1
1
___
___
yes
___
yes
yes
yes
___
8542
Light: examination, single, ceiling mounted
2
1
yes
___
___
___
___
___
___
___
optional, depending on use of the bay
40404
Tapware: sensor
1
1
yes
___
yes
yes
yes
___
___
___
straight spout
Services
ID
Description
Service Category
Qty
Selection / Remarks
1006
Voice / Data outlet: double
Communications
1
to bedhead
5000
Airconditioning
HVAC
2242
General LED: colour corrected
Lighting
7000
Oxygen (O2)
Medical Gases
1
7020
Medical Air (MA)
Medical Gases
1
optional
7040
Suction
Medical Gases
1
8000
Patient to Staff call
Nurse Call
1
+ indicator button & light
8005
Patient call handset
Nurse Call
1
call button on the handset
8010
Staff/ Nurse assist call
Nurse Call
1
+ indicator button & light
8080
Emergency call
Nurse Call
1
+ indicator button & light
2582
PO: Single
Power
3
to bedhead
2582
PO: Single
Power
1
to bedhead, low level for bed
2579
PO: Emergency power, single
Power
3
to bedhead
2576
PO: Cleaner
Power
1
9040
Body protected
Power
11000
Wall panel
Services Panels
1
flush mounted, patient services
6030
Special: downlights
Lighting
over bed/ trolley
2724
Direct connection: Emergency power
Power
2
1 - to sensor operated tapware, 1 - exam light (optional)
6005
Dimmable
Lighting
for night lighting