Print Download PDF Version
1 Bed Room - Standard, 18m2, Outboard Ensuite
Room Code
PBTR-RS2-12-I
Net Room Area Briefed
12
Hours of Operation
24 Hours
Occupancy
1 patient; 1 staff
Description / Special Requirements
A Patient Bed Bay used for the recovery stage 2, of patients from anaesthetic, located within the Operating Unit or Day Procedures Unit. A clinical handwashing basin will be provided for each 4 Recovery Bed Bays. Recovery Bed Bays will require direct observation from the Staff Station.
Cardiac Protected electrical area
Amendment
Fabric and outline specifications
ID
Fabric
Material
Finish
Specification
Selection
Remarks
1000
Floor finish
Vinyl
Standard slip resistant
Seamless, coved
7001
Windows
desirable
5010
Ceiling
Plasterboard
Paint, washable
Flush set, suspended
3092
Wall protection
MDF
Laminate
Bed protection wall panel
2000
Skirting
Vinyl
Prefinished
Floor vinyl coved, 150mmH
2767
Cornice
Plasterboard
Paint
Square set
3000
Wall finish
Paint
Acrylic, washable
Fittings and Furniture (FF)
ID
Description
Category
Group
Qty
Selection / Remarks
1252
Blind: Venetian integral
Furniture/ Fitting
1
1
to external window
4600
Curtain track: bed screen
Metalwork
1
1
5000
Curtain: bed screen
Furniture/ Fitting
3
1
6152
Dispenser: disposable glove
Furniture/ Fitting
2
1
8291
Air flowmeter
MEQ - General
3
1
optional
8297
Bracket: suction bottle
MEQ - General
2
1
8309
Oxygen flowmeter
MEQ - General
3
1
8318
Suction adapter
MEQ - General
3
1
8321
Suction bottle
MEQ - General
3
1
8593
Bracket: patient monitor
MEQ - General
3
1
8404
Bracket: sharps disposal
MEQ - General
2
1
8306
IV pole: mobile
MEQ - General
3
1
8982
Stretcher: procedure/ recovery
MEQ - Furniture
3
1
8405
Sharps disposal: wall mounted, 11L
MEQ - General
2
1
Fixtures, Equipment and associated Services (FE)
ID
Description
Grp
Qty
Ele
Data
CdW
HtW
WmW
Tap
Dns
Gas
Selection / Remarks
8989
Infusion pump: single channel
3
1
yes
opt
___
___
___
___
___
___
on IV pole
8472
Infusion pump: syringe
3
1
yes
opt
___
___
___
___
___
___
on IV pole
8776
Monitor: physiologic, acute care
3
1
yes
yes
___
___
___
___
___
___
on bracket
8542
Light: examination, single, ceiling mounted
2
1
yes
___
___
___
___
___
___
___
Services
ID
Description
Service Category
Qty
Selection / Remarks
1006
Voice / Data outlet: double
Communications
1
to services panel
5000
Airconditioning
HVAC
2242
General LED: colour corrected
Lighting
7000
Oxygen (O2)
Medical Gases
1
services panel
7020
Medical Air (MA)
Medical Gases
1
services panel; optional
7040
Suction
Medical Gases
1
services panel
8000
Patient to Staff call
Nurse Call
1
+ indicator button & light
8005
Patient call handset
Nurse Call
1
call button on the handset
8010
Staff/ Nurse assist call
Nurse Call
1
+ indicator button & light
8080
Emergency call
Nurse Call
1
+ indicator button & light
2579
PO: Emergency power, single
Power
4
3 - services panel, 1 - for monitor, if required
2576
PO: Cleaner
Power
1
may serve a group of beds
9030
Cardiac protected/ IPS
Power
11000
Wall panel
Services Panels
1
2724
Direct connection: Emergency power
Power
1
to examination light
1005
Voice / Data outlet: single
Communications
1
to patient monitor
2582
PO: Single
Power
1
at low level for stretcher/ bed
2582
PO: Single
Power
3
3 - services panel