Patient Chair Bay, 6m2

Room Code PBC-6-I
Net Room Area Briefed 6
Hours of Operation 0800 Hours to 1800 Hours, daily
Occupancy 1 patient, 1support person, 1 staff assisting
Description / Special Requirements The Patient Chair Bay - is used for treatment of patients that do not require a bed and may be located in Emergency Units, Recovery Stages 2/3 and Day Therapy units. Medical Gases may be shared between bays, depending on the patient profile. One staff handwashing basin should be provided to each of 4 bays (refer to Bay-Handwashing Type B). Body Protected electrical area
Amendment 27.05.2016 First Issue

Fabric and outline specifications

ID Fabric Material Finish Specification Selection Remarks
7001 Windows External windows desirable
3092 Wall protection MDF Laminate Bed protection wall panel
2000 Skirting Vinyl Prefinished Floor vinyl coved, 150mmH
3000 Wall finish Paint Acrylic, washable
1000 Floor finish Vinyl Standard slip resistant Seamless, coved
5010 Ceiling Plasterboard Paint, washable Flush set, suspended
6030 Cornice Aluminium Powdercoat 24mm shadow angle

Fittings and Furniture (FF)

ID Description Category Group Qty Selection / Remarks
150 Air flowmeter Furniture/ Fitting 3 1
1260 Blind: holland Metalwork 3 1 to external windows; cleanable
1465 Bracket: suction bottle Furniture/ Fitting 2 1
2200 Chair: recliner Furniture/ Fitting 3 1
2650 Chair: visitor, patient Furniture/ Fitting 3 1
4600 Curtain track: bed screen Metalwork 1 1
5000 Curtain: bed screen Furniture/ Fitting 3 1
6152 Dispenser: disposable glove Furniture/ Fitting 2 1
6387 Storage bins: for louvred panels Furniture/ Fitting 3 3
6547 Louvred panel: small for storage-bins Furniture/ Fitting 1 1
6174 Dispenser: hand gel Furniture/ Fitting 2 1
16250 Oxygen flowmeter Furniture/ Fitting 3 1
21950 Suction adapter Furniture/ Fitting 3 1
22000 Suction bottle Furniture/ Fitting 3 1
23400 Bracket: television, ceiling Metalwork 1 1 optional: ceiling mounted

Fixtures, Equipment and associated Services (FE)

ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
3031 Television: flat screen 3 1 yes ___ ___ ___ ___ ___ ___ ___ optional
31700 Light: examination, ceiling 1 1 yes ___ ___ ___ ___ ___ ___ ___ optional

Services

ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 1 optional
5000 Airconditioning HVAC
2189 General LED Lighting
6050 Special: reading Lighting
7000 Oxygen (O2) Medical Gases 1 may be shared between 2 bays depending on use of the bay
7020 Medical Air (MA) Medical Gases 1 may be shared between 2 bays depending on use of the bay
7040 Suction Medical Gases 1 may be shared between 2 bays depending on use of the bay
8000 Patient/ Staff call Nurse Call 1 + indicator button & light
8005 Patient call handset Nurse Call 1 call button on the handset.
8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light
8080 Emergency call Nurse Call 1 + indicator button & light
2582 PO: Single Power 3 to patient services panel
2579 PO: Emergency power, single Power 1 to patient services panel
9040 Body protected Power
2587 PO: Special: for equipment Power 1 optional, to ceiling mounted TV
1090 TV: MATV Communications 1 optional
6200 Light switches Lighting 1 to reading light