The Procedure Room may be required for the performance of procedures that do not require the full facilities of the Operating Suite. This may include suturing of wounds, dressings, administration of local anaesthesia and use of medical gases in connection with the procedures being performed. General anaesthesia will not be administered in this room.
Body Protected electrical area.
Note: If cardiac procedures such as indwelling cardiac pacing electrodes, intracardiac catheters or pulmonary catheters inserted into the ventricles are to be undertaken then the room should be Cardiac Protected.
Acoustics: Sound attenuation level - Medium. Acoustic privacy required.
Additional design considerations:
- Lead sheilding may be required depending on use of mobile imaging
equipment
- Bariatric patient treatments may require access to mobile bariatric lifter
Amendment
24.10.2010 First Draft
21.04.2011 Room Fabric and Services modified
30.05.2016 Revisions to Description, Fabric, Services
Fabric and outline specifications
ID
Fabric
Material
Finish
Specification
Selection
Remarks
1000
Floor finish
Vinyl
Standard slip resistant
Seamless, coved
2000
Skirting
Vinyl
Prefinished
Floor vinyl coved, 150mmH
3000
Wall finish
Paint
Acrylic, washable
5010
Ceiling
Plasterboard
Paint, washable
Flush set, suspended
8010
Door protection
Composite
Prefinished PVC
Protection plate to 900 AFFL
8040
Door protection
Composite
Prefinished PVC
To door frame
9125
Doors
Solid Core/ Glass
Paint
1 1/2 leaf, observation panel
1500mm clear opening, cover to glazing
9004
Doors
Solid Core/ Glass
Paint
Single leaf, observation panel
920mm clear opening, optional door to Clean Utility