1 Bed Room - Standard, 18m2, Outboard Ensuite

Room Code PROC-25-I
Net Room Area Briefed 25
Hours of Operation 24 Hours
Occupancy 1 patient; 2-4 staff
Description / Special Requirements The Procedure Room may be required for the performance of procedures that do not require the full facilities of the Operating Suite. This may include suturing of wounds, dressings, administration of local anaesthesia and use of medical gases in connection with the procedures being performed. General anaesthesia will not be administered in this room. Body Protected electrical area. Note: If cardiac procedures such as indwelling cardiac pacing electrodes, intracardiac catheters or pulmonary catheters inserted into the ventricles are to be undertaken then the room should be Cardiac Protected. Acoustics: Sound attenuation level - Medium. Acoustic privacy required. Additional design considerations: - Lead sheilding may be required depending on use of mobile imaging equipment - Bariatric patient treatments may require access to mobile bariatric lifter - Provide sufficient clearances around all sides of the bed, to comply with required Guidelines
Amendment 30.05.2016 First Issue 03.09.2023 RDS updated

Fabric and outline specifications

ID Fabric Material Finish Specification Selection Remarks
8040 Door protection Composite Prefinished PVC To door frame
9127 Doors Solid Core/ Safety glass Paint 1 1/2 leaf, observation panel 1600mm clear opening, cover to glazing
9006 Doors Solid Core/ Safety glass Paint Single leaf, observation panel 920mm clear opening, optional door to Clean Utility
2767 Cornice Plasterboard Paint Square set
3000 Wall finish Paint Acrylic, washable
5010 Ceiling Plasterboard Paint, washable Flush set, suspended
8010 Door protection Composite Prefinished PVC Protection plate to 900mm AFFL
5007 Ceiling Plasterboard Paint Bulkhead between above bench joinery and ceiling
1000 Floor finish Vinyl Standard slip resistant Seamless, coved
3052 Wall finish Vinyl Prefinished Wall vinyl to 1500mm AFFL
2000 Skirting Vinyl Prefinished Floor vinyl coved, 150mmH
1045 Floor finish Vinyl, non slip Textured Seamless, coved

Fittings and Furniture (FF)

ID Description Category Group Qty Selection / Remarks
1050 Bench: laminate Furniture/ Fitting 1 1
2926 Dispenser: hand sanitiser Furniture/ Fitting 2 1
4360 Cupboard: door ht adj. shelves Furniture/ Fitting 1 1 lockable; optional
4420 Cupboard: under bench, lockable Furniture/ Fitting 1 1 adjustable shelves; optional
4470 Cupboard: wall mounted, lockable Furniture/ Fitting 1 1 over bench, adjustable shelves; optional
4600 Curtain track: bed screen Metalwork 1 1 to door opening
5000 Curtain: bed screen Furniture/ Fitting 3 1
6152 Dispenser: disposable glove Furniture/ Fitting 2 1
6154 Dispenser: paper/ hand towel Furniture/ Fitting 2 1 to basin
6158 Dispenser: soap antiseptic Furniture/ Fitting 2 1 to basin
8291 Air flowmeter MEQ - General 3 1
8297 Bracket: suction bottle MEQ - General 2 2
8306 IV pole: mobile MEQ - General 3 1
8309 Oxygen flowmeter MEQ - General 3 2
8318 Suction adapter MEQ - General 3 2
8321 Suction bottle MEQ - General 3 2
8404 Bracket: sharps disposal MEQ - General 2 1 wall mounted
8593 Bracket: patient monitor MEQ - General 3 1
8616 Trolley: procedure MEQ - Furniture 3 1
8607 Waste bin: clinical, 50 litres MEQ - Furniture 3 1
8982 Stretcher: procedure/ recovery MEQ - Furniture 3 1
9117 Sharps disposal: wall mounted, 7L MEQ - General 2 1
21680 Stool: adjustable, mobile Furniture/ Fitting 3 1
24100 Waste bin: paper, 20 Litre Furniture/ Fitting 3 1 to basin

Fixtures, Equipment and associated Services (FE)

ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
3100 Basin: scrub, Type A 1 1 ___ ___ yes ___ yes yes yes ___
8989 Infusion pump: single channel 3 1 yes opt ___ ___ ___ ___ ___ ___ Qty TBC by project
9056 Refrigerator: drugs, under-bench, 150L 3 1 yes yes ___ ___ ___ ___ ___ ___ optional
9456 Light: procedure, single, ceiling mounted 2 1 yes ___ ___ ___ ___ ___ ___ ___
10132 Clock: master clock 3 1 yes opt ___ ___ ___ ___ ___ ___
11400 Computer: PC & monitor 3 1 yes yes ___ ___ ___ ___ ___ ___
40404 Tapware: sensor 1 1 yes ___ yes yes yes ___ ___ ___ straight spout
8776 Monitor: physiologic, acute care 3 1 yes yes ___ ___ ___ ___ ___ ___
54520 Telephone: handset, handsfree 3 1 ___ yes ___ ___ ___ ___ ___ ___

Services

ID Description Service Category Qty Selection / Remarks
9040 Body protected Power
7070 Scavenge Medical Gases 1 patient services panel; optional; include if N2O is provided
7010 Nitrous Oxide (N2O) Medical Gases 1 patient services panel; optional; for analgesia use; not for anaesthesia
11000 Wall panel Services Panels 1 patient services panel
2579 PO: Emergency power, single Power 4 3 - patient services panel, 1- patient monitor
2577 PO: Double Power 3 2- bench (computer); 1- wall
2582 PO: Single Power 4 3 - patient services panel, 1- at low level close to stretcher
8080 Emergency call Nurse Call 1 + indicator button & light
8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light
8005 Patient call handset Nurse Call 1 call button on the handset
8000 Patient to Staff call Nurse Call 1 + indicator button & light
7040 Suction Medical Gases 2 patient services panel
7020 Medical Air (MA) Medical Gases 1 patient services panel
7000 Oxygen (O2) Medical Gases 2 patient services panel
2242 General LED: colour corrected Lighting
5000 Airconditioning HVAC
2724 Direct connection: Emergency power Power 2 1 - sensor operated tapware, 1 - procedure light
1080 Clock: master clock Communications 1 battery/ POE/ electrical connection TBC
1005 Voice / Data outlet: single Communications 2 1- under-bench refrigerator; 1- patient monitor
1006 Voice / Data outlet: double Communications 2 1- patient services panel; 1- bench (computer)
2578 PO: Emergency power, double Power 2 1- under-bench refrigerator; 1- bench