The Procedure Room may be required for the performance of procedures that do not require the full facilities of the Operating Suite. This may include suturing of wounds, dressings, administration of local anaesthesia and use of medical gases in connection with the procedures being performed. General anaesthesia will not be administered in this room.
Body Protected electrical area.
Note: If cardiac procedures such as indwelling cardiac pacing electrodes, intracardiac catheters or pulmonary catheters inserted into the ventricles are to be undertaken then the room should be Cardiac Protected.
Acoustics: Sound attenuation level - Medium. Acoustic privacy required.
Additional design considerations:
- Lead sheilding may be required depending on use of mobile imaging
equipment
- Bariatric patient treatments may require access to mobile bariatric lifter
- Provide sufficient clearances around all sides of the bed, to comply
with required Guidelines
Amendment
30.05.2016 First Issue
03.09.2023 RDS updated
Fabric and outline specifications
ID
Fabric
Material
Finish
Specification
Selection
Remarks
8040
Door protection
Composite
Prefinished PVC
To door frame
9127
Doors
Solid Core/ Safety glass
Paint
1 1/2 leaf, observation panel
1600mm clear opening, cover to glazing
9006
Doors
Solid Core/ Safety glass
Paint
Single leaf, observation panel
920mm clear opening, optional door to Clean Utility
2767
Cornice
Plasterboard
Paint
Square set
3000
Wall finish
Paint
Acrylic, washable
5010
Ceiling
Plasterboard
Paint, washable
Flush set, suspended
8010
Door protection
Composite
Prefinished PVC
Protection plate to 900mm AFFL
5007
Ceiling
Plasterboard
Paint
Bulkhead
between above bench joinery and ceiling
1000
Floor finish
Vinyl
Standard slip resistant
Seamless, coved
3052
Wall finish
Vinyl
Prefinished
Wall vinyl to 1500mm AFFL
2000
Skirting
Vinyl
Prefinished
Floor vinyl coved, 150mmH
1045
Floor finish
Vinyl, non slip
Textured
Seamless, coved
Fittings and Furniture (FF)
ID
Description
Category
Group
Qty
Selection / Remarks
1050
Bench: laminate
Furniture/ Fitting
1
1
2926
Dispenser: hand sanitiser
Furniture/ Fitting
2
1
4360
Cupboard: door ht adj. shelves
Furniture/ Fitting
1
1
lockable; optional
4420
Cupboard: under bench, lockable
Furniture/ Fitting
1
1
adjustable shelves; optional
4470
Cupboard: wall mounted, lockable
Furniture/ Fitting
1
1
over bench, adjustable shelves; optional
4600
Curtain track: bed screen
Metalwork
1
1
to door opening
5000
Curtain: bed screen
Furniture/ Fitting
3
1
6152
Dispenser: disposable glove
Furniture/ Fitting
2
1
6154
Dispenser: paper/ hand towel
Furniture/ Fitting
2
1
to basin
6158
Dispenser: soap antiseptic
Furniture/ Fitting
2
1
to basin
8291
Air flowmeter
MEQ - General
3
1
8297
Bracket: suction bottle
MEQ - General
2
2
8306
IV pole: mobile
MEQ - General
3
1
8309
Oxygen flowmeter
MEQ - General
3
2
8318
Suction adapter
MEQ - General
3
2
8321
Suction bottle
MEQ - General
3
2
8404
Bracket: sharps disposal
MEQ - General
2
1
wall mounted
8593
Bracket: patient monitor
MEQ - General
3
1
8616
Trolley: procedure
MEQ - Furniture
3
1
8607
Waste bin: clinical, 50 litres
MEQ - Furniture
3
1
8982
Stretcher: procedure/ recovery
MEQ - Furniture
3
1
9117
Sharps disposal: wall mounted, 7L
MEQ - General
2
1
21680
Stool: adjustable, mobile
Furniture/ Fitting
3
1
24100
Waste bin: paper, 20 Litre
Furniture/ Fitting
3
1
to basin
Fixtures, Equipment and associated Services (FE)
ID
Description
Grp
Qty
Ele
Data
CdW
HtW
WmW
Tap
Dns
Gas
Selection / Remarks
3100
Basin: scrub, Type A
1
1
___
___
yes
___
yes
yes
yes
___
8989
Infusion pump: single channel
3
1
yes
opt
___
___
___
___
___
___
Qty TBC by project
9056
Refrigerator: drugs, under-bench, 150L
3
1
yes
yes
___
___
___
___
___
___
optional
9456
Light: procedure, single, ceiling mounted
2
1
yes
___
___
___
___
___
___
___
10132
Clock: master clock
3
1
yes
opt
___
___
___
___
___
___
11400
Computer: PC & monitor
3
1
yes
yes
___
___
___
___
___
___
40404
Tapware: sensor
1
1
yes
___
yes
yes
yes
___
___
___
straight spout
8776
Monitor: physiologic, acute care
3
1
yes
yes
___
___
___
___
___
___
54520
Telephone: handset, handsfree
3
1
___
yes
___
___
___
___
___
___
Services
ID
Description
Service Category
Qty
Selection / Remarks
9040
Body protected
Power
7070
Scavenge
Medical Gases
1
patient services panel; optional; include if N2O is provided
7010
Nitrous Oxide (N2O)
Medical Gases
1
patient services panel; optional; for analgesia use; not for anaesthesia
11000
Wall panel
Services Panels
1
patient services panel
2579
PO: Emergency power, single
Power
4
3 - patient services panel, 1- patient monitor
2577
PO: Double
Power
3
2- bench (computer); 1- wall
2582
PO: Single
Power
4
3 - patient services panel, 1- at low level close to stretcher