Room Code | RAD-BUNK-I |
Net Room Area Briefed | 150 |
Hours of Operation | 8am to 8pm, daily |
Occupancy | 1 patient, up to 4 staff |
Description / Special Requirements | The Radiotherapy Bunker room will contain a medical linear accelerator used used primarily to treat cancer. The Linear Accelerator uses a high energy radiation beam to localise treatment on a tumour. Radiation sheilding will be required, most commonly concrete is used as the primary sheilding material. A Control Room will be located next to to the Bunker Room. Additional Design Requirements: - Radiation sheilding to walls and glazing as advised by Radiation Consultant - Laser positioning lights will be required to manufacturers details - 'Beam on' Warning lights will be required at room entrance Body Protected electrical area |
Amendment | 24.10.2010 First Draft 21.04.2011 Room Fabric and FF modified 29.05.2014 General amendments to Fabric, FF, FE and Services 21.06.2019 Room area updated 03.09.2023 RDS updated |
ID | Fabric | Material | Finish | Specification | Selection | Remarks |
1000 | Floor finish | Vinyl | Standard slip resistant | Seamless, coved | ||
8010 | Door protection | Composite | Prefinished PVC | Protection plate to 900mm AFFL | ||
8040 | Door protection | Composite | Prefinished PVC | To door frame | ||
4031 | Wall protection | Composite | Prefinished PVC | Corner guards to 1500mm AFFL | as required; other heights also acceptable as per project standardisation | |
2000 | Skirting | Vinyl | Prefinished | Floor vinyl coved, 150mmH | ||
3000 | Wall finish | Paint | Acrylic, washable | |||
1045 | Floor finish | Vinyl, non slip | Textured | Seamless, coved | around basin | |
4159 | Cornice | Aluminium | Powdercoat | Angle flush against wall, in line with ceiling grid | ||
5032 | Ceiling | Plasterboard | Prefinished | Drop-in tiles, 600x 600 mm | allows access to in-ceiling services | |
9001 | Doors | Solid Core | Paint | Single leaf | to Linac Equipment 850mm clear opening | |
3022 | Wall finish | Resinate, 6mm | Prefinished | Splashback | to basin, other smooth impervious finish also acceptable |
ID | Description | Category | Group | Qty | Selection / Remarks |
1050 | Bench: laminate | Furniture/ Fitting | 1 | 1 | L shaped |
4410 | Cupboard: under bench | Furniture/ Fitting | 1 | 3 | under bench, 2 sides |
4430 | Cupboard: drawer unit | Furniture/ Fitting | 1 | 1 | under bench, storage |
6152 | Dispenser: disposable glove | Furniture/ Fitting | 2 | 1 | to basin |
6154 | Dispenser: paper/ hand towel | Furniture/ Fitting | 2 | 1 | to basin |
6158 | Dispenser: soap antiseptic | Furniture/ Fitting | 2 | 1 | to basin |
8297 | Bracket: suction bottle | MEQ - General | 2 | 1 | |
8309 | Oxygen flowmeter | MEQ - General | 3 | 1 | |
8318 | Suction adapter | MEQ - General | 3 | 1 | |
8321 | Suction bottle | MEQ - General | 3 | 1 | |
20000 | Shelving unit: adjustable | Furniture/ Fitting | 1 | 3 | |
20012 | Shelving unit: fixed shelves | Furniture/ Fitting | 1 | 1 | tray and block storage |
23410 | Bracket: television, wall mount | Metalwork | 2 | 1 | |
8291 | Air flowmeter | MEQ - General | 3 | 1 | |
10061 | Waste bin: General, 20 Litres | Furniture/ Fitting | 3 | 1 |
ID | Description | Grp | Qty | Ele | Data | CdW | HtW | WmW | Tap | Dns | Gas | Selection / Remarks |
3100 | Basin: scrub, Type A | 1 | 1 | ___ | ___ | yes | ___ | yes | yes | yes | ___ | |
7300 | Camera: CCTV security | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | part of radiotherapy equipment; to view patient | |
9323 | Radiotherapy system: LINAC | 2 | 1 | yes | yes | yes | ___ | ___ | ___ | yes | ___ | services according to manufacturer's specifications |
40404 | Tapware: sensor | 1 | 1 | yes | ___ | yes | yes | yes | ___ | ___ | ___ | straight spout |
9107 | Light: radiation warning | 1 | yes | opt | ___ | ___ | ___ | ___ | ___ | ___ | part of radiotherapy equipment; final qty as per manufacturer's specifications | |
9105 | Laser positioning lights | 2 | yes | opt | ___ | ___ | ___ | ___ | ___ | ___ | part of radiotherapy equipment; final qty as per manufacturer's specifications, usually between 2-5 | |
8968 | Monitor: video, medical grade, HD, 32-inch | 3 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | wall mounted |
ID | Description | Service Category | Qty | Selection / Remarks |
1006 | Voice / Data outlet: double | Communications | 3 | 2- at low level on the wall; 1- 32" video monitor |
1040 | Intercom | Communications | 1 | handsfree, for patient communication |
2001 | Emergency Stop button | Power | 6 | one in corridor |
2043 | Last Person Out Button | Communications | 2 | one inside bunker and one at entrance |
2242 | General LED: colour corrected | Lighting | ||
6076 | Special: 'X-ray In Use' lights | Lighting | ||
6095 | Special: "Beam On" lights | Lighting | ||
6005 | Dimmable | Lighting | ||
2576 | PO: Cleaner | Power | 1 | |
9040 | Body protected | Power | ||
5000 | Airconditioning | HVAC | ||
2724 | Direct connection: Emergency power | Power | 3 | 1 - for sensor operated tapware, 2 - CCTV camera (POE connection also acceptable) |
8080 | Emergency call | Nurse Call | 1 | + indicator button & light |
8010 | Staff/ Nurse assist call | Nurse Call | 1 | + indicator button & light |
7000 | Oxygen (O2) | Medical Gases | 1 | patient services panel |
7040 | Suction | Medical Gases | 1 | patient services panel |
2579 | PO: Emergency power, single | Power | 3 | patient services panel |
11000 | Wall panel | Services Panels | 1 | |
7020 | Medical Air (MA) | Medical Gases | 1 | patient services panel |
1006 | Voice / Data outlet: double | Communications | 3 | 1- patient services panel; 2- bench |
6839 | Trunking: 300mm x 300mm | Electrical Installations | 1 | between treatment room, control room, and equipment room |
2757 | Direct connection: Uninterrupted power | Power | 5 | to positioning lasers; wall mounted; depending on the requirements (usually between 2 - 5) |
2578 | PO: Emergency power, double | Power | 8 | 2- at low level on the wall; 1- 32" video monitor; 3- bench; 2- service area |
2473 | Power over Ethernet (PoE) | Power | 2 | to CCTV |
2791 | PO: Special: 3 phase | Power | 1 | linear accelerator, according to manufacturer's specifications |
11505 | Floor duct for power & data | Services Ducts | 1 | between treatment room, control room, and equipment room |
12011 | Radiation shielding | Shielding | to walls, floor, ceiling, doors & glazing as specified by Radiation Consultant | |
4030 | Drainage | Hydraulics | 1 | as per manufacturer's specification |
2792 | Clean Agent Gas Fire Suppression | Fire Services | 1 | |
1379 | Audio/ Video outlet | Communications | 1 | to 32" video monitor |
7010 | Nitrous Oxide (N2O) | Medical Gases | 1 | patient services panel |
7070 | Scavenge | Medical Gases | 1 | patient services panel |