Radiotherapy Bunker Control Room

Room Code RAD-BCTR-I
Net Room Area Briefed 17
Hours of Operation 8am to 8pm, daily
Occupancy Up to 3 staff
Description / Special Requirements Room adjacent to Linear Accelerator Bunker for remote control of equipment. The Control Room will accommodate the control console, CCTV moniotrs and printers Additional Design Considerations: - Radiation shielding as advised by Radiation Consultant - Cable ducts from Bunker Room and Compute room may be required
Amendment 24.10.2010 First Draft 21.04.2011 FF modified 03.09.2023 RDS updated

Fabric and outline specifications

ID Fabric Material Finish Specification Selection Remarks
2000 Skirting Vinyl Prefinished Floor vinyl coved, 150mmH
3000 Wall finish Paint Acrylic, washable
9001 Doors Solid Core Paint Single leaf 920mm clear opening
1219 Door Protection Composite Prefinished PVC Kickplate, 300mm high
1000 Floor finish Vinyl Standard slip resistant Seamless, coved
5062 Ceiling Acoustic Prefinished Drop-in tiles, 600x600 mm
4159 Cornice Aluminium Powdercoat Angle flush against wall, in line with ceiling grid

Fittings and Furniture (FF)

ID Description Category Group Qty Selection / Remarks
1050 Bench: laminate Furniture/ Fitting 1 2 at 900H
1950 Chair: ergonomic, high Furniture/ Fitting 3 3
3400 Coathook Metalwork 1 2
17252 Pedestal drawer unit: mobile, 840mmH Furniture/ Fitting 3 1 under bench
20000 Shelving unit: adjustable Furniture/ Fitting 1 1 for books, manuals, over bench

Fixtures, Equipment and associated Services (FE)

ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
11400 Computer: PC & monitor 3 1 yes yes ___ ___ ___ ___ ___ ___ flat screen
35860 Monitor: CCTV 3 2 yes yes ___ ___ ___ ___ ___ ___ Qty TBC depending on the configurations of the radiotherapy equipment
41100 Printer: networked 3 1 yes yes ___ ___ ___ ___ ___ ___
54510 Telephone: handset, standard 3 2 ___ yes ___ ___ ___ ___ ___ ___ on bench
9092 Control console 2 1 yes yes ___ ___ ___ ___ ___ ___ radiotherapy control console

Services

ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 5 3- control console equipment; 2- wall
1040 Intercom Communications 1 with handsfree microphone to bunker room
5000 Airconditioning HVAC
2189 General LED Lighting
6055 Special: task light, built in Lighting under O/H shelving
2578 PO: Emergency power, double Power 2 to wall
2726 PO: UPS, double Power 6 to control console equipment