The Radiotherapy Simulator Room - MRI will accommodate a simulator which will duplicate the beam geometry of the medical linear accelerator. The Simulator is used in treatment planning to localise the treatment field. Radiofrequency sheilding will be required. A Control Room will be located adjacent to the Simulator Room. A staff handwashin basin will be located outside the room in close proximity. Fixtures and fittings to be non magnetic.
Body Protected electrical area
Acoutsics: acoustic privacy required for ambient noise emitted by scanning equipment
Special Design Requirements:
- The MRI suite shall be planned to conform to staged access and
control zones complying with local authority requirements to prevent
unscreened persons accessing the 5-gauass volume around the
MRI scanner and to minimise radiofrequency interference from other
equipment
- Electromagnetic sheilding (radio frequency enclosure) as advised by
RF Shielding Consultant
- Structural assessment may be required to ensure the floor is designed
to acommodate the weight of the equipment
- Floor to ceiling cable duct with removable covers may be required
- Underfloor cable trays between Control area and MRI table and floor to
ceiling duct may be required
- Warning lights outside each entry door
- Power to be on emergency supply - all power to MRI to pass through
MRI isolation transformer
- Installation of the MRI including services requirements such as
cryogen venting, emergency exhaust, passive pressure relief systems,
shall conform to local authority requirements and manufacturer's
specifications
Amendment
01.02.2011 First Draft
15.03.2017 Description & services updated
Fabric and outline specifications
ID
Fabric
Material
Finish
Specification
Selection
Remarks
2000
Skirting
Vinyl
Prefinished
Floor vinyl coved, 150mmH
7025
Observation
Lead glass
Clear
Internal window
to Control Room
9110
Doors
Solid Core
Paint
1 1/2 leaf
patient entry/ exit; 1400mm clear opening
5010
Ceiling
Plasterboard
Paint, washable
Flush set, suspended
at 3000mm height
1000
Floor finish
Vinyl
Standard slip resistant
Seamless, coved
3000
Wall finish
Paint
Acrylic, washable
2767
Cornice
Plasterboard
Paint
Square set
Fittings and Furniture (FF)
ID
Description
Category
Group
Qty
Selection / Remarks
8321
Suction bottle
MEQ - General
3
2
non-magnetic
8417
Air flowmeter: MRI
MEQ - General
3
1
to patient services panel; non-magnetic
8642
Bracket: suction bottle, MRI
MEQ - General
2
2
non-magnetic
9481
Board: patient transfer, MRI
MEQ - General
3
1
8651
Cabinet: storage, MRI coils
MEQ - Imaging
2
part of MRI system configurations
2926
Dispenser: hand sanitiser
Furniture/ Fitting
2
1
8419
Footstool: MRI
MEQ - Furniture
3
1
8423
IV pole: mobile, MRI
MEQ - General
3
1
8418
Oxygen flowmeter: MRI
MEQ - General
3
2
to patient services panel; non-magnetic
8424
Suction adapter: MRI
MEQ - General
3
2
to patient services panel; non-magnetic
9183
Trolley: multi-purpose, MRI
MEQ - Furniture
3
1
8421
Wheelchair: MRI
MEQ - General
3
1
or can be kept in store
Fixtures, Equipment and associated Services (FE)
ID
Description
Grp
Qty
Ele
Data
CdW
HtW
WmW
Tap
Dns
Gas
Selection / Remarks
9105
Laser positioning lights
2
yes
opt
___
___
___
___
___
___
Qty (3), part of MRI system configurations; quantity as per manufacturer's recommendation
7300
Camera: CCTV security
1
yes
___
___
___
___
___
___
___
part of MRI system configurations; to view patient, optional
9079
Scanning unit: MRI, 1.5-tesla, RT
2
1
yes
yes
___
___
___
___
yes
___
with patient table and control console
9111
Injector: contrast media, mobile, dual head, MRI
3
1
yes
yes
___
___
___
___
___
___
8777
Monitor: physiologic, MRI, on stand
3
1
yes
opt
___
___
___
___
___
___
9007
Ventilator: adult/ paediatric, MRI, on stand
3
1
yes
opt
___
___
___
___
___
___
or can be kept in store
9052
Anaesthesia unit: MRI
3
1
yes
opt
___
___
___
___
___
___
or can be kept in store
Services
ID
Description
Service Category
Qty
Selection / Remarks
1006
Voice / Data outlet: double
Communications
2
1- patient services panel; 1- wall
1040
Intercom
Communications
1
speakers and mic are mounted to the gantry
5000
Airconditioning
HVAC
2242
General LED: colour corrected
Lighting
6005
Dimmable
Lighting
7000
Oxygen (O2)
Medical Gases
2
patient services panel; non magnetic outlet
7010
Nitrous Oxide (N2O)
Medical Gases
1
patient services panel; non magnetic outlet
7020
Medical Air (MA)
Medical Gases
1
patient services panel; non magnetic outlet
7040
Suction
Medical Gases
2
patient services panel; non magnetic outlet
7070
Scavenge
Medical Gases
1
patient services panel; non magnetic outlet
12020
Faraday cage
Shielding
to walls, floor, ceiling, doors & glazing as specified by Radiation Consultant
11000
Wall panel
Services Panels
1
9040
Body protected
Power
2578
PO: Emergency power, double
Power
3
walls
2579
PO: Emergency power, single
Power
4
patient services panel
8080
Emergency call
Nurse Call
1
8010
Staff/ Nurse assist call
Nurse Call
1
2411
Special: "MRI In Use" light
Lighting
1
to outside of room entry
2234
Direct connection: Uninterrupted power
Power
3
laser positioning lights (qty as per manufacturer's recommendation)