TheTreatment Planning/ Dosimetry room houses workstations and computer equipment used by the dosimetrists to determine treatment plans for each patient.
Acoustics: Sound attenuation - medium; Acoustic privacy is required
Amendment
24.10.2010 First Draft
21.04.2011 Room Fabric, FF, FE and Services modified
03.09.2023 RDS updated
Fabric and outline specifications
ID
Fabric
Material
Finish
Specification
Selection
Remarks
3000
Wall finish
Paint
Acrylic, washable
1088
Skirting
Timber
Paint
150mmH x 20mm thick nominal
MDF also acceptable; or floor vinyl coved skirting if vinyl is used
5062
Ceiling
Acoustic
Prefinished
Drop-in tiles, 600x600 mm
1144
Floor finish
Carpet
Synthetic
Carpet tiles
vinyl also acceptable
1219
Door Protection
Composite
Prefinished PVC
Kickplate, 300mm high
4159
Cornice
Aluminium
Powdercoat
Angle flush against wall, in line with ceiling grid
9127
Doors
Solid Core/ Safety glass
Paint
1 1/2 leaf, observation panel
920mm clear opening, glazing optional
Fittings and Furniture (FF)
ID
Description
Category
Group
Qty
Selection / Remarks
1050
Bench: laminate
Furniture/ Fitting
1
2
1120
Bench: workstation
Furniture/ Fitting
1
6
2100
Chair: ergonomic, office
Furniture/ Fitting
3
6
4410
Cupboard: under bench
Furniture/ Fitting
1
1
4460
Cupboard: wall mounted
Furniture/ Fitting
1
1
over bench
17250
Pedestal drawer unit: mobile, 660mmH
Furniture/ Fitting
3
6
under each workstation
20000
Shelving unit: adjustable
Furniture/ Fitting
1
6
above workstation benches
10061
Waste bin: General, 20 Litres
Furniture/ Fitting
3
6
Fixtures, Equipment and associated Services (FE)
ID
Description
Grp
Qty
Ele
Data
CdW
HtW
WmW
Tap
Dns
Gas
Selection / Remarks
10132
Clock: master clock
3
1
yes
opt
___
___
___
___
___
___
11400
Computer: PC & monitor
3
6
yes
yes
___
___
___
___
___
___
11900
Computer: server
3
1
yes
yes
___
___
___
___
___
___
41100
Printer: networked
3
1
yes
yes
___
___
___
___
___
___
54510
Telephone: handset, standard
3
6
___
yes
___
___
___
___
___
___
Services
ID
Description
Service Category
Qty
Selection / Remarks
1006
Voice / Data outlet: double
Communications
9
1 per workstation, 1 - for printer; 1 - to server; 1 - on bench