1 Bed Room - Standard, 18m2, Outboard Ensuite

Room Code RAD-TRP-I
Net Room Area Briefed 56
Hours of Operation Available 24 Hours
Occupancy 6 workstations
Description / Special Requirements TheTreatment Planning/ Dosimetry room houses workstations and computer equipment used by the dosimetrists to determine treatment plans for each patient. Acoustics: Sound attenuation - medium; Acoustic privacy is required
Amendment 24.10.2010 First Draft 21.04.2011 Room Fabric, FF, FE and Services modified 03.09.2023 RDS updated

Fabric and outline specifications

ID Fabric Material Finish Specification Selection Remarks
3000 Wall finish Paint Acrylic, washable
1088 Skirting Timber Paint 150mmH x 20mm thick nominal MDF also acceptable; or floor vinyl coved skirting if vinyl is used
5062 Ceiling Acoustic Prefinished Drop-in tiles, 600x600 mm
1144 Floor finish Carpet Synthetic Carpet tiles vinyl also acceptable
1219 Door Protection Composite Prefinished PVC Kickplate, 300mm high
4159 Cornice Aluminium Powdercoat Angle flush against wall, in line with ceiling grid
9127 Doors Solid Core/ Safety glass Paint 1 1/2 leaf, observation panel 920mm clear opening, glazing optional

Fittings and Furniture (FF)

ID Description Category Group Qty Selection / Remarks
1050 Bench: laminate Furniture/ Fitting 1 2
1120 Bench: workstation Furniture/ Fitting 1 6
2100 Chair: ergonomic, office Furniture/ Fitting 3 6
4410 Cupboard: under bench Furniture/ Fitting 1 1
4460 Cupboard: wall mounted Furniture/ Fitting 1 1 over bench
17250 Pedestal drawer unit: mobile, 660mmH Furniture/ Fitting 3 6 under each workstation
20000 Shelving unit: adjustable Furniture/ Fitting 1 6 above workstation benches
10061 Waste bin: General, 20 Litres Furniture/ Fitting 3 6

Fixtures, Equipment and associated Services (FE)

ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
10132 Clock: master clock 3 1 yes opt ___ ___ ___ ___ ___ ___
11400 Computer: PC & monitor 3 6 yes yes ___ ___ ___ ___ ___ ___
11900 Computer: server 3 1 yes yes ___ ___ ___ ___ ___ ___
41100 Printer: networked 3 1 yes yes ___ ___ ___ ___ ___ ___
54510 Telephone: handset, standard 3 6 ___ yes ___ ___ ___ ___ ___ ___

Services

ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 9 1 per workstation, 1 - for printer; 1 - to server; 1 - on bench
5000 Airconditioning HVAC
2189 General LED Lighting
6055 Special: task light, built in Lighting under O/H joinery
2577 PO: Double Power 15 2 per workstation, 1 - printer, 2 - bench
2726 PO: UPS, double Power 1 to server
1080 Clock: master clock Communications 1 battery/ POE/ electrical connection TBC