1 Bed Room - Standard, 18m2, Outboard Ensuite

Room Code REWM-I
Net Room Area Briefed 20
Hours of Operation Available 24 Hours
Occupancy 2 - 3
Description / Special Requirements The Respiratory Workroom provides an area for the repair, maintenance and calibration of respiratory and biomedical equipment, in the Intensive Care Unit. The room will also serve as a work base for biomedical technicians visiting the Unit. The room should be accessible from inside the Unit and the external corridor.
Amendment 24.10.2010 First Draft 21.06.2019 Room name updated

Fabric and outline specifications

ID Fabric Material Finish Specification Selection Remarks
1000 Floor finish Vinyl Standard slip resistant Seamless, coved
8010 Door protection Composite Prefinished PVC Protection plate to 900mm AFFL
8040 Door protection Composite Prefinished PVC To door frame
5062 Ceiling Acoustic Prefinished Drop-in tiles, 600x600 mm
3000 Wall finish Paint Acrylic, washable
2000 Skirting Vinyl Prefinished Floor vinyl coved, 150mmH
4159 Cornice Aluminium Powdercoat Angle flush against wall, in line with ceiling grid
9127 Doors Solid Core/ Safety glass Paint 1 1/2 leaf, observation panel 1400mm clear opening
4020 Wall protection Composite Prefinished PVC Crash rail at 900mm AFFL
3052 Wall finish Vinyl Prefinished Wall vinyl to 1500mm AFFL

Fittings and Furniture (FF)

ID Description Category Group Qty Selection / Remarks
1050 Bench: laminate Furniture/ Fitting 1 1
1950 Chair: ergonomic, high Furniture/ Fitting 3 2
4420 Cupboard: under bench, lockable Furniture/ Fitting 1 1
4470 Cupboard: wall mounted, lockable Furniture/ Fitting 1 1 over bench
6152 Dispenser: disposable glove Furniture/ Fitting 2 1
6154 Dispenser: paper/ hand towel Furniture/ Fitting 2 1 to basin
6158 Dispenser: soap antiseptic Furniture/ Fitting 2 1 to basin
10061 Waste bin: General, 20 Litres Furniture/ Fitting 3 1

Fixtures, Equipment and associated Services (FE)

ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
54510 Telephone: handset, standard 3 2 ___ yes ___ ___ ___ ___ ___ ___ to bench, optional
9117 Analyser/ tester: gas flow 3 1 yes opt ___ ___ ___ ___ ___ ___
9116 Analyser/ tester: electrical safety, automated 3 1 yes opt ___ ___ ___ ___ ___ ___

Services

ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 5
5005 Air conditioning: special HVAC positive pressure, filtered
2189 General LED Lighting
6055 Special: task light, built in Lighting under O/H cupboards
7000 Oxygen (O2) Medical Gases 1 for testing/ calibrating equipment
7010 Nitrous Oxide (N2O) Medical Gases 1 for testing/ calibrating equipment
7020 Medical Air (MA) Medical Gases 1 for testing/ calibrating equipment (MA4)
7040 Suction Medical Gases 1 for testing/ calibrating equipment
7070 Scavenge Medical Gases 1 for testing/ calibrating equipment
2577 PO: Double Power 5
11000 Wall panel Services Panels 1 flush mounted
2578 PO: Emergency power, double Power 2
6870 Surgical Air (SA7) Medical Gases 1 for testing/ calibrating equipment
2576 PO: Cleaner Power 1