1 Bed Room - Standard, 18m2, Outboard Ensuite

Room Code SPECT-CT-I
Net Room Area Briefed 48
Hours of Operation Available 24 Hours
Occupancy 1 patient; up to 3 staff assisting
Description / Special Requirements Imaging Room for SPECT & CT scanning procedures using a SPECT/CT hybrid camera system with an adjacent Control Room and Computer Room. The Control Room may serve two Scanning rooms simultaneously. Acoustics: Acoustic privacy is required Body Protected electrical area Additional Design Considerations: - Radiation shielding as advised by Radiation Consultant - Cable ducts between Control Room and Computer Room may be required - 'X-ray in Use' lights are required outside each entry door - Uninterruptible power supply is required to the cameras and associated computer modules to prevent data loss and/or damage during power surges or loss of supply. - Individual room temperature and humidity control is required. - Lighting should be placed to avoid lights shining directly into the patient's eyes and should be dimmable.
Amendment 25.06.2019 First Draft 03.09.2023 RDS updated

Fabric and outline specifications

ID Fabric Material Finish Specification Selection Remarks
7025 Observation Lead glass Clear Internal window to control room
8010 Door protection Composite Prefinished PVC Protection plate to 900mm AFFL
8040 Door protection Composite Prefinished PVC To door frame
9130 Doors Solid Core Paint 1 1/2 leaf, with lead shielding patient entry/ exit 1600mm clear opening
2000 Skirting Vinyl Prefinished Floor vinyl coved, 150mmH
5010 Ceiling Plasterboard Paint, washable Flush set, suspended at 3000 mm AFFL
4020 Wall protection Composite Prefinished PVC Crash rail at 900mm AFFL
2767 Cornice Plasterboard Paint Square set
3000 Wall finish Paint Acrylic, washable
1000 Floor finish Vinyl Standard slip resistant Seamless, coved
3022 Wall finish Resinate, 6mm Prefinished Splashback to basin, other smooth impervious finish also acceptable

Fittings and Furniture (FF)

ID Description Category Group Qty Selection / Remarks
1050 Bench: laminate Furniture/ Fitting 1 1 with inset sink, optional
2150 Chair: patient Furniture/ Fitting 3 1
4360 Cupboard: door ht adj. shelves Furniture/ Fitting 1 1 optional
4410 Cupboard: under bench Furniture/ Fitting 1 1 optional
4470 Cupboard: wall mounted, lockable Furniture/ Fitting 1 1 over bench; adjustable shelves; optional
6152 Dispenser: disposable glove Furniture/ Fitting 2 1
6154 Dispenser: paper/ hand towel Furniture/ Fitting 2 2 to basin & sink
6158 Dispenser: soap antiseptic Furniture/ Fitting 2 1 to basin
8291 Air flowmeter MEQ - General 3 1 to services panel
8297 Bracket: suction bottle MEQ - General 2 2
8309 Oxygen flowmeter MEQ - General 3 2 to services panel
8318 Suction adapter MEQ - General 3 2 to services panel
8321 Suction bottle MEQ - General 3 2
23400 Bracket: television, ceiling Metalwork 2 1 or wall mounted; optional
8635 Lead screen: mobile MEQ - Imaging 3 1
10061 Waste bin: General, 20 Litres Furniture/ Fitting 3 1

Fixtures, Equipment and associated Services (FE)

ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
2800 Basin: handwash, Type B 1 1 ___ ___ yes ___ yes yes yes ___
9566 Scanning unit: SPECT/ CT, 16-slice 2 1 yes yes ___ ___ ___ ___ ___ ___ including computer modules
40404 Tapware: sensor 1 1 yes ___ yes yes yes ___ ___ ___ straight spout
40405 Tapware: sink mixer 1 1 ___ ___ yes yes yes ___ ___ ___ provide hot water; optional
47800 Sink, SS: single in bench 1 1 ___ ___ yes opt opt yes yes ___ optional; confirm sink dimensions
54510 Telephone: handset, standard 3 1 ___ yes ___ ___ ___ ___ ___ ___
7300 Camera: CCTV security 1 yes ___ ___ ___ ___ ___ ___ ___ part of SPECT/ CT scanning system configurations
8782 Monitor: physiologic, vital signs, on stand 3 1 yes opt ___ ___ ___ ___ ___ ___
9109 Injector: contrast media, mobile, dual head, CT 3 1 yes yes ___ ___ ___ ___ ___ ___

Services

ID Description Service Category Qty Selection / Remarks
5080 Humidity control HVAC 45% to 80%
2242 General LED: colour corrected Lighting
6055 Special: task light, built in Lighting under O/H cupboards (if cupboards required)
6005 Dimmable Lighting
7000 Oxygen (O2) Medical Gases 2 patient services panel
7020 Medical Air (MA) Medical Gases 1 patient services panel
7040 Suction Medical Gases 2 patient services panel
8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light
8080 Emergency call Nurse Call 1 + indicator button & light
2579 PO: Emergency power, single Power 3 to patient services panels
2578 PO: Emergency power, double Power 4 to walls (including injector)
2576 PO: Cleaner Power 1
9040 Body protected Power
5070 Temperature control HVAC 22 degrees C +/- 2 degrees
5005 Air conditioning: special HVAC 24 Hour with standby capacity
1040 Intercom Communications 1 handsfree to control room
1006 Voice / Data outlet: double Communications 3 1- bench; 1- patient services panel; 1- wall
2724 Direct connection: Emergency power Power 1 for sensor operated tapware
12011 Radiation shielding Shielding to walls, floor, ceiling, doors & glazing as specified by Radiation Consultant
2556 Trunking: 200mm x 70mm Electrical Installations 1 between equipment room, control room and scanning room
6076 Special: 'X-ray In Use' lights Lighting 1
11505 Floor duct for power & data Services Ducts 1 between equipment room, control room and scanning room
2473 Power over Ethernet (PoE) Power 1 1- CCTV
2578 PO: Emergency power, double Power 1 1- bench
11000 Wall panel Services Panels 1 flush mounted
1080 Clock: master clock Communications 1 battery/ POE/ electrical connection TBC
7010 Nitrous Oxide (N2O) Medical Gases 1
7070 Scavenge Medical Gases 1