1 Bed Room - Standard, 18m2, Outboard Ensuite

Room Code SECL-I
Net Room Area Briefed 14
Hours of Operation 24 Hours
Occupancy 1 patient; 1-2 staff intermittently
Description / Special Requirements A Seclusion Room provides for the sole confinement of a distressed or agitated person requiring separation for short periods at any hour of the day or night on an involuntary basis. The Seclusion Room will be observable from the Staff Station. An external outlook is desirable. All glazing (including external windows) must comply to relevant safety standard. Acoustics: Sound attenuation level high; Acoustic privacy is required Additional Design Considerations: - An internal observation window is required - A second room egress door is required
Amendment 24.10.2010 First Draft 21.04.2011 Outline specifications and FF modified 21.06.2019 Room area updated 03.09.2023 RDS updated

Fabric and outline specifications

ID Fabric Material Finish Specification Selection Remarks
9006 Doors Solid Core/ Safety glass Paint Single leaf, observation panel 1100mm clear opening, lockable from outside. with integral blinds
7001 Windows fixed laminated toughened glass if provided
8010 Door protection Composite Prefinished PVC Protection plate to 900mm AFFL
3072 Wall finish Vinyl Cushioned Wall vinyl full height
1010 Floor finish Vinyl Cushioned Seamless, coved
5010 Ceiling Plasterboard Paint, washable Flush set, suspended 3000 mm height
9006 Doors Solid Core/ Safety glass Paint Single leaf, observation panel 500mm clear outward opening, optional
8040 Door protection Composite Prefinished PVC To door frame
1253 Observation Alum/ Toughened glass Powdercoat Internal window, double glazed with integral venetians; optional
2000 Skirting Vinyl Prefinished Floor vinyl coved, 150mmH
2767 Cornice Plasterboard Paint Square set 90mm plasterboard cornice

Fittings and Furniture (FF)

ID Description Category Group Qty Selection / Remarks
1252 Blind: Venetian integral Furniture/ Fitting 1 2 to internal & external windows, controls outside room
3930 Mirror: convex Metalwork 1 1 if CCTV not provided
13350 Mattress: foam Furniture/ Fitting 3 1 foam, on floor

Fixtures, Equipment and associated Services (FE)

ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
7300 Camera: CCTV security 1 1 yes ___ ___ ___ ___ ___ ___ ___ recessed in ceiling dome

Services

ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC with vandal proof outlet
6030 Special: downlights Lighting vandal proof
6060 Special: night lights Lighting vandal proof
2724 Direct connection: Emergency power Power 1 for CCTV camera (POE connection also acceptable)
10005 Duress alarm Security 1 outside room near door
6005 Dimmable Lighting