Print Download PDF Version
1 Bed Room - Standard, 18m2, Outboard Ensuite
Room Code
SHD-I
Net Room Area Briefed
4
Hours of Operation
24 Hours
Occupancy
1 patient; 1-2 staff assisting as required
Description / Special Requirements
The Shower - Accessible is a room containing a shower for use by disabled persons or patients, either independently or with nurse assistance.
Acoustics: Sound attenuation level - high; Acoustic privacy required.
Body Protected electrical area
Additional Design Considerations:
- Access is required for commode chairs
- The floor must not have a raised hob
- The door will require escape hardware to allow staff access in an
emergency
Amendment
24.10.2010 First Draft
26.05.2011 Fabric modified
03.09.2023 RDS updated
Fabric and outline specifications
ID
Fabric
Material
Finish
Specification
Selection
Remarks
3795
Ceiling
Plasterboard
Prefinished
Water resistant, drop-in tiles, 600x600mm
8010
Door protection
Composite
Prefinished PVC
Protection plate to 900mm AFFL
8040
Door protection
Composite
Prefinished PVC
To door frame
9001
Doors
Solid Core
Paint
Single leaf
920mm clear; outward opening; privacy latch; emergency release
3000
Wall finish
Paint
Acrylic, washable
4159
Cornice
Aluminium
Powdercoat
Angle flush against wall, in line with ceiling grid
2000
Skirting
Vinyl
Prefinished
Floor vinyl coved, 150mmH
or other coved skirting to match floor
3035
Wall finish
Vinyl
Prefinished
Wall vinyl full height
other smooth impervious finish also acceptable; to wet areas
1020
Floor finish
Vinyl, non-slip
Safety
Seamless, coved
other non-slip impervious floor finish suitable for barefeet also acceptable
Fittings and Furniture (FF)
ID
Description
Category
Group
Qty
Selection / Remarks
1002
Bench seat: fold up/down
Furniture/ Fitting
1
1
3400
Coathook
Metalwork
1
2
1 at 1200H for wheelchair users
4800
Curtain track: shower
Metalwork
1
1
5300
Curtain: shower
Furniture/ Fitting
3
1
6152
Dispenser: disposable glove
Furniture/ Fitting
2
1
8450
Grab rail: Shower
Metalwork
1
1
L shaped, optional
8450
Grab rail: Shower
Metalwork
1
1
T bar
20603
Soap/ shampoo holder: recessed
Furniture/ Fitting
1
1
23700
Towel rail
Metalwork
1
1
with grab rail strength/ fixings
Fixtures, Equipment and associated Services (FE)
ID
Description
Grp
Qty
Ele
Data
CdW
HtW
WmW
Tap
Dns
Gas
Selection / Remarks
40406
Tapware: shower mixer
1
1
___
___
yes
yes
yes
___
___
___
47400
Shower: hand-held
1
1
___
___
yes
___
yes
yes
yes
___
Services
ID
Description
Service Category
Qty
Selection / Remarks
4033
Floor waste
Hydraulics
1
5019
Exhaust
HVAC
2189
General LED
Lighting
8000
Patient to Staff call
Nurse Call
1
+ indicator button & light, water proof
8010
Staff/ Nurse assist call
Nurse Call
1
+ indicator button & light, water proof
8080
Emergency call
Nurse Call
1
+ indicator button & light
5015
Ventilation
HVAC