Print Download PDF Version
Shower - Decontamination
Room Code
SHDEC-I
Net Room Area Briefed
8
Hours of Operation
24 Hours
Occupancy
1 - 2
Description / Special Requirements
The Decontamination Shower is provided to shower patients who arrive in the Unit contaminated with toxic and/or infectious substances. The room will include a flexible water hose, floor drain and contaminated water trap. The shower should be accessible from the ambulance bay (external) without entering any other part of the Unit. A Personal Protective Equipment Bay may be located in close proximity.
Amendment
24.10.2010 First Draft
21.04.2011 Room Fabric and FE modified
01.09.2022 Fabric, FF, FE & Services updated
03.09.2023 RDS updated
Fabric and outline specifications
ID
Fabric
Material
Finish
Specification
Selection
Remarks
1175
Floor finish
Tiles
Non-slip
Ceramic
non-slip vinyl also acceptable
2145
Skirting
Tiles
To match floor
Coved
3080
Wall finish
Tiles
Glazed
Full height
to wet areas
6025
Cornice
Aluminium
Powdercoat
shadow line
8040
Door protection
Composite
Prefinished PVC
To door frame
3795
Ceiling
Plasterboard
Prefinished
Water resistant, drop-in tiles, 600x600mm
8010
Door protection
Composite
Prefinished PVC
Protection plate to 900mm AFFL
9006
Doors
Solid Core/ Safety glass
Paint
Single leaf, observation panel
920mm clear; outward opening; privacy latch; emergency release; sliding cover to observation panel
Fittings and Furniture (FF)
ID
Description
Category
Group
Qty
Selection / Remarks
6152
Dispenser: disposable glove
Furniture/ Fitting
2
1
Fixtures, Equipment and associated Services (FE)
ID
Description
Grp
Qty
Ele
Data
CdW
HtW
WmW
Tap
Dns
Gas
Selection / Remarks
47605
Shower: decontamination
1
2
___
___
yes
___
yes
yes
yes
___
in lockable cabinets
54520
Telephone: handset, handsfree
3
2
___
yes
___
___
___
___
___
___
hospital phones, recessed in waterproof lockable cabinets
Services
ID
Description
Service Category
Qty
Selection / Remarks
1005
Voice / Data outlet: single
Communications
2
for hospital phones
4030
Drainage
Hydraulics
1
to contaminated water trap
5015
Ventilation
HVAC
5019
Exhaust
HVAC
6001
General: colour corrected
Lighting
7000
Oxygen (O2)
Medical Gases
1
in lockable recess, optional
7020
Medical Air (MA)
Medical Gases
1
in lockable recess, optional
7040
Suction
Medical Gases
1
in lockable recess, optional
8080
Emergency call
Nurse Call
1
11000
Wall panel
Services Panels
1
recessed, lockable cover, if gases required
2666
PO: Single, waterproof
Power
4
2 to each telephone box