1 Bed Room - Standard, 18m2, Outboard Ensuite

Room Code STFS-10-I
Net Room Area Briefed 10
Hours of Operation 24 Hours
Occupancy 1 - 2 intermittently
Description / Special Requirements The Files Store is a secure room for the storage of departmental files or patient clinical records in static metal shelving or compactus shelving. If compactus shelving is installed, the track may be recessed into the floor; (recessed into the floor is the preferred option to maximise accessibility for staff). Structural Engineer's advice must be sought if compactus is to be used, (floor load bearing capacity and potential deflection effect on walls, door etc.)
Amendment 24.10.10, - First Draft 15.02.2016 RDS checked to ensure match with Layout sheets dated 31.10.12 18.05.2016 Documentation amendment: Fabric: skirting changed, door frame protection added.

Fabric and outline specifications

ID Fabric Material Finish Specification Selection Remarks
5030 Ceiling Plasterboard Prefinished Drop-in tiles, 600x1200 mm
9001 Doors Solid Core Paint Single leaf 920mm clear opening; lockable
6025 Cornice Aluminium Powdercoat shadow line
8010 Door protection Composite Prefinished PVC Protection plate to 900AFFL
1149 Floor finish Carpet 90/10 Wool/ Nylon Broadloom, 48 oz. vinyl also acceptable
3000 Wall finish Paint Acrylic, washable
8040 Door protection Composite Prefinished PVC To door frame
2010 Skirting Vinyl Prefinished Feather edged, 150mmH

Fittings and Furniture (FF)

ID Description Category Group Qty Selection / Remarks
13660 Metal shelving: 900x400x2100 Furniture/ Fitting 3 9 or compactus filing unit
24400 Whiteboard Furniture/ Fitting 2 1 optional, 900 x 900.

Fixtures, Equipment and associated Services (FE)

ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
54510 Telephone: handset, standard 3 1 ___ yes ___ ___ ___ ___ ___ ___ optional, wall mounted.

Services

ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 1 1 outlet for telephone
1050 Telephone: wall mounted, PABX Communications 1 for wall phone
5000 Airconditioning HVAC
6000 General fluorescent Lighting
9001 GPO: Double Power 1