1 Bed Room - Standard, 18m2, Outboard Ensuite

Room Code STPS-8-I
Net Room Area Briefed 8
Hours of Operation 24 Hours
Occupancy 1-2 intermittently
Description / Special Requirements A room for the photocopier and for secure storage of paper and stationery supplies. The facsimile and printer may also be located in this area if required.
Amendment 24.10.10, - First Draft

Fabric and outline specifications

ID Fabric Material Finish Specification Selection Remarks
1149 Floor finish Carpet 90/10 Wool/ Nylon Broadloom, 48 oz. vinyl also acceptable
3000 Wall finish Paint Acrylic, washable
949496 Skirting Timber Paint 150mmH x 20mm thick, nominal or floor vinyl coved skirting
5060 Ceiling Acoustic Prefinished Drop-in tiles, 600x1200
9001 Doors Solid Core Paint Single leaf 920mm clear opening; lockable
8000 Door protection Vinyl Prefinished Kickplate, 300mm high
6025 Cornice Aluminium Powdercoat shadow line

Fittings and Furniture (FF)

ID Description Category Group Qty Selection / Remarks
1050 Bench: laminate Furniture/ Fitting 1 1
4360 Cupboard: door ht adj. shelves Furniture/ Fitting 1 1 stationery storage, lockable
4420 Cupboard: under bench, lockable Furniture/ Fitting 1 1 adjustable shelves, paper storage
20000 Shelving unit: adjustable Furniture/ Fitting 1 1 over bench
24114 Waste bin: fliptop, 50 Litre Furniture/ Fitting 3 1

Fixtures, Equipment and associated Services (FE)

ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
20800 Facsimile machine 3 1 yes yes ___ ___ ___ ___ ___ ___ optional
39800 Photocopier 3 1 yes ___ ___ ___ ___ ___ ___ ___
41100 Printer: networked 3 1 yes yes ___ ___ ___ ___ ___ ___ optional

Services

ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 2 1 outlet over bench for telephone
5000 Airconditioning HVAC
5019 Exhaust HVAC over photocopier
6000 General fluorescent Lighting
6055 Special: task light, built in Lighting 1 under O/H shelves
9001 GPO: Double Power 3