Room for undertaking patient diagnostic stress testing procedures. The Stress Testing room should be located close to patient toilet and change rooms.
Acoustics: Acoustic privacy required
Body Protected electrical area
Amendment
24.10.2010 First Draft
06.09.2022 Cornice changed to aluminium shadow line.
06.09.2022 Updated door with observation panel
03.09.2023 RDS updated
Fabric and outline specifications
ID
Fabric
Material
Finish
Specification
Selection
Remarks
1000
Floor finish
Vinyl
Standard slip resistant
Seamless, coved
3022
Wall finish
Resinate, 6mm
Prefinished
Splashback
to basin, other smooth impervious finish also acceptable
3000
Wall finish
Paint
Acrylic, washable
5062
Ceiling
Acoustic
Prefinished
Drop-in tiles, 600x600 mm
2000
Skirting
Vinyl
Prefinished
Floor vinyl coved, 150mmH
8010
Door protection
Composite
Prefinished PVC
Protection plate to 900mm AFFL
8040
Door protection
Composite
Prefinished PVC
To door frame
6025
Cornice
Aluminium
Powdercoat
shadow line
9004
Doors
Solid Core/ Glass
Paint
Single leaf, observation panel
920mm clear opening
Fittings and Furniture (FF)
ID
Description
Category
Group
Qty
Selection / Remarks
2150
Chair: patient
Furniture/ Fitting
3
1
2100
Chair: ergonomic, office
Furniture/ Fitting
3
1
3400
Coathook
Metalwork
1
1
4700
Curtain track: privacy screen
Metalwork
1
1
to entry door
5250
Curtain: privacy screen
Furniture/ Fitting
3
1
to entry door
6152
Dispenser: disposable glove
Furniture/ Fitting
2
1
6154
Dispenser: paper/ hand towel
Furniture/ Fitting
2
1
to basin
6158
Dispenser: soap antiseptic
Furniture/ Fitting
2
1
to basin
10061
Waste bin: General, 20 Litres
Furniture/ Fitting
3
1
8318
Suction adapter
MEQ - General
3
1
8321
Suction bottle
MEQ - General
3
1
8297
Bracket: suction bottle
MEQ - General
2
1
8309
Oxygen flowmeter
MEQ - General
3
1
8398
Trolley: resuscitation
MEQ - Furniture
3
1
8402
Footstool: 2-step
MEQ - Furniture
3
1
8605
Waste bin: clinical, 20 litres
MEQ - Furniture
3
1
Fixtures, Equipment and associated Services (FE)
ID
Description
Grp
Qty
Ele
Data
CdW
HtW
WmW
Tap
Dns
Gas
Selection / Remarks
2800
Basin: handwash, Type B
1
1
___
___
yes
___
yes
yes
yes
___
10132
Clock: master clock
3
1
yes
opt
___
___
___
___
___
___
40404
Tapware: sensor
1
1
yes
___
yes
yes
yes
___
___
___
straight spout
54510
Telephone: handset, standard
3
1
___
yes
___
___
___
___
___
___
to computer table
8767
Defibrillator: with monitor
3
1
yes
___
___
___
___
___
___
___
9066
Testing system: stress
3
1
yes
yes
___
___
___
___
___
___
8895
Table: examination/ treatment, electric
3
1
yes
___
___
___
___
___
___
___
9065
Treadmill: stress testing
3
1
yes
yes
___
___
___
___
___
___
Services
ID
Description
Service Category
Qty
Selection / Remarks
1006
Voice / Data outlet: double
Communications
2
1- patient service panel; 1- stress testing system/ treadmill
5000
Airconditioning
HVAC
2242
General LED: colour corrected
Lighting
8000
Patient to Staff call
Nurse Call
2
+ indicator button & light
8005
Patient call handset
Nurse Call
2
call button on the handset
8010
Staff/ Nurse assist call
Nurse Call
1
+ indicator button & light
8080
Emergency call
Nurse Call
1
+ indicator button & light
2577
PO: Double
Power
2
to wall
2576
PO: Cleaner
Power
1
9040
Body protected
Power
2724
Direct connection: Emergency power
Power
1
sensor operated tapware
1080
Clock: master clock
Communications
1
battery/ POE/ electrical connection TBC
7000
Oxygen (O2)
Medical Gases
1
to patient service panel
7040
Suction
Medical Gases
1
to patient service panel
11000
Wall panel
Services Panels
1
2578
PO: Emergency power, double
Power
1
to stress testing system
2579
PO: Emergency power, single
Power
3
2- patient service panel; 1- treadmill
2582
PO: Single
Power
3
2- patient service panel; 1- at low level for exam table