Toilet - Patient
Room Code
WCPT-I
Net Room Area Briefed
4
Hours of Operation
24 Hours
Occupancy
1 patient; 1 staff assisting as required
Description / Special Requirements
Room containing a toilet and handbasin for patients in multi-bed rooms or adjacent to communal patient areas. The door will be fitted with escape hardware to allow staff access in an emergency.
Acoustics: Sound attenuation level - High. Acoustic privacy required.
Body protected electrical area
Amendment
24.10.2010 First Draft
05.05.2011 Services remarks modified
28.10.2014 FF, FE & Services updated
06.09.2022 Updated floor to vinyl and backsplash to resinate
03.09.2023 RDS updated
Fabric and outline specifications
ID
Fabric
Material
Finish
Specification
Selection
Remarks
3000
Wall finish
Paint
Acrylic, washable
8040
Door protection
Composite
Prefinished PVC
To door frame
both sides
4159
Cornice
Aluminium
Powdercoat
Angle flush against wall, in line with ceiling grid
8010
Door protection
Composite
Prefinished PVC
Protection plate to 900mm AFFL
both sides
3795
Ceiling
Plasterboard
Prefinished
Water resistant, drop-in tiles, 600x600mm
9001
Doors
Solid Core
Paint
Single leaf
920mm clear outward opening, privacy latch, emergency release
2000
Skirting
Vinyl
Prefinished
Floor vinyl coved, 150mmH
or other coved skirting to match floor
3022
Wall finish
Resinate, 6mm
Prefinished
Splashback
to basin, other smooth impervious finish also acceptable
1000
Floor finish
Vinyl
Standard slip resistant
Seamless, coved
other non-slip impervious floor finish also acceptable
Fittings and Furniture (FF)
ID
Description
Category
Group
Qty
Selection / Remarks
3400
Coathook
Metalwork
1
2
1 @ 1200 AFFL for wheelchair users
6152
Dispenser: disposable glove
Furniture/ Fitting
2
1
optional
6154
Dispenser: paper/ hand towel
Furniture/ Fitting
2
1
to basin
6156
Dispenser: soap
Furniture/ Fitting
2
1
to basin
6160
Dispenser: toilet paper
Furniture/ Fitting
2
1
8400
Grab rail: WC
Metalwork
1
2
1 behind toilet, 1 to side
8500
Grab rail: WC, hinged
Metalwork
1
1
optional, drop down rail
10800
Hook: for IV flasks
Metalwork
1
1
optional
13700
Mirror
Metalwork
1
1
19100
Waste bin: sanitary
Furniture/ Fitting
3
1
optional
10061
Waste bin: General, 20 Litres
Furniture/ Fitting
3
1
Fixtures, Equipment and associated Services (FE)
ID
Description
Grp
Qty
Ele
Data
CdW
HtW
WmW
Tap
Dns
Gas
Selection / Remarks
3003
Bidet handset
1
1
___
___
___
___
yes
yes
___
___
near toilet; optional
5603
Basin: ensuite
1
1
___
___
yes
___
yes
yes
yes
___
with integral vanity shelf, or vanity basin
40402
Tapware: basin mixer
1
1
___
___
yes
yes
yes
___
___
___
basin mounted
55605
Toilet suite: patient
1
1
___
___
yes
___
___
yes
yes
___
Services
ID
Description
Service Category
Qty
Selection / Remarks
4033
Floor waste
Hydraulics
1
5019
Exhaust
HVAC
2189
General LED
Lighting
sensor light optional
8000
Patient to Staff call
Nurse Call
1
+ indicator button & light; may be located on drop down rail beside toilet if provided
8010
Staff/ Nurse assist call
Nurse Call
1
+ indicator button & light
8080
Emergency call
Nurse Call
1
+ indicator button & light
2577
PO: Double
Power
1
may be water proof according to relevant electrical authority requirements or located outside rooom entry
9040
Body protected
Power