Print Download PDF Version
Toilet - Public, 3m2
Room Code
WCPU-3-I
Net Room Area Briefed
3
Hours of Operation
24 Hours
Occupancy
1
Description / Special Requirements
A room containing a toilet and handbasin for public or visitor use located adjacent to common areas such as waiting, reception and visitor lounge areas.
Acoustics: Sound attenuation level - high; Acoustic privacy is required.
Amendment
24.10.2010 First Draft
05.05.2011 Services Remarks modified
27.07.2015 FE modified
05.09.2022 Fabrics, FF, FE, Services updated
03.09.2023 RDS updated
Fabric and outline specifications
ID
Fabric
Material
Finish
Specification
Selection
Remarks
3795
Ceiling
Plasterboard
Prefinished
Water resistant, drop-in tiles, 600x600mm
9001
Doors
Solid Core
Paint
Single leaf
920mm clear opening, privacy latch, emergency release
6025
Cornice
Aluminium
Powdercoat
shadow line
1219
Door Protection
Composite
Prefinished PVC
Kickplate, 300mm high
3000
Wall finish
Paint
Acrylic, washable
1045
Floor finish
Vinyl, non slip
Textured
Seamless, coved
tiles also acceptable
2000
Skirting
Vinyl
Prefinished
Floor vinyl coved, 150mmH
or tile coved skirting if tile floor is used
3022
Wall finish
Resinate, 6mm
Prefinished
Splashback
to basin, other smooth impervious finish also acceptable
Fittings and Furniture (FF)
ID
Description
Category
Group
Qty
Selection / Remarks
3400
Coathook
Metalwork
1
1
6154
Dispenser: paper/ hand towel
Furniture/ Fitting
2
1
to basin
6156
Dispenser: soap
Furniture/ Fitting
1
1
to basin
6160
Dispenser: toilet paper
Furniture/ Fitting
1
1
13700
Mirror
Metalwork
1
1
19100
Waste bin: sanitary
Furniture/ Fitting
3
1
19910
Shelf: vanity
Furniture/ Fitting
1
1
10061
Waste bin: General, 20 Litres
Furniture/ Fitting
3
1
Fixtures, Equipment and associated Services (FE)
ID
Description
Grp
Qty
Ele
Data
CdW
HtW
WmW
Tap
Dns
Gas
Selection / Remarks
40402
Tapware: basin mixer
1
1
___
___
yes
yes
yes
___
___
___
2850
Basin: handwash, Type C
1
1
___
___
yes
___
yes
yes
yes
___
3003
Bidet handset
1
1
___
___
___
___
yes
yes
___
___
optional
55600
Toilet suite: standard
1
1
___
___
yes
___
___
yes
yes
___
Services
ID
Description
Service Category
Qty
Selection / Remarks
4033
Floor waste
Hydraulics
1
5015
Ventilation
HVAC
5019
Exhaust
HVAC
2189
General LED
Lighting
light switch near door outside room; may also use motion sensor
2577
PO: Double
Power
1
locate near door outside room; optional