A room located within the Medical Imaging Unit to accommodate the laser imager equipment along with a workstation area for viewing, and reporting of images.
Acoustics: Sound attenuation level - Medium; acoustic privacy required.
Amendment
24.10.2010 First Draft
02.05.2011 Fabric, FF & FE remarks updated
14.06.2019 Room name updated
21.02.2024 RLS reviewed
Fabric and outline specifications
ID
Fabric
Material
Finish
Specification
Selection
Remarks
9007
Doors
Solid Core/ Safety glass
Paint
Single leaf, half glazed
920mm clear opening, glazing optional
1088
Skirting
Timber
Paint
150mmH x 20mm thick nominal
MDF also acceptable; or floor vinyl coved skirting if vinyl is used
3000
Wall finish
Paint
Acrylic, washable
5062
Ceiling
Acoustic
Prefinished
Drop-in tiles, 600x600 mm
1219
Door Protection
Composite
Prefinished PVC
Kickplate, 300mm high
1144
Floor finish
Carpet
Synthetic
Carpet tiles
vinyl also acceptable
4159
Cornice
Aluminium
Powdercoat
Angle flush against wall, in line with ceiling grid