1 Bed Room - Standard, 18m2, Outboard Ensuite

Room Code VRB-6-I
Net Room Area Briefed 6
Hours of Operation 24 Hours
Occupancy 2
Description / Special Requirements a Bay within a Clinical or Diagnostic Unit for reviewing and reporting of patient imaging film or computerised images and to write reports.
Amendment 18.06.2019 First Draft 24.05.2023 RDS reviewed

Fabric and outline specifications

ID Fabric Material Finish Specification Selection Remarks
4031 Wall protection Composite Prefinished PVC Corner guards to 1500mm AFFL as required; other heights also acceptable as per project standardisation
1000 Floor finish Vinyl Standard slip resistant Seamless, coved
2000 Skirting Vinyl Prefinished Floor vinyl coved, 150mmH
4159 Cornice Aluminium Powdercoat Angle flush against wall, in line with ceiling grid
3000 Wall finish Paint Acrylic, washable
5062 Ceiling Acoustic Prefinished Drop-in tiles, 600x600 mm flush set plasterboard also acceptable

Fittings and Furniture (FF)

ID Description Category Group Qty Selection / Remarks
1050 Bench: laminate Furniture/ Fitting 1 1
2100 Chair: ergonomic, office Furniture/ Fitting 3 2
17255 Pedestal filing unit: mobile, 660mmH Furniture/ Fitting 3 1 under bench
24100 Waste bin: paper, 20 Litre Furniture/ Fitting 3 1 under bench
20000 Shelving unit: adjustable Furniture/ Fitting 1 3

Fixtures, Equipment and associated Services (FE)

ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
11400 Computer: PC & monitor 3 1 yes yes ___ ___ ___ ___ ___ ___
11415 Computer: PACS 3 1 yes yes ___ ___ ___ ___ ___ ___ for computerised images
41100 Printer: networked 3 1 yes yes ___ ___ ___ ___ ___ ___
54510 Telephone: handset, standard 3 2 ___ yes ___ ___ ___ ___ ___ ___
9143 Laser imager, benchtop 3 1 yes yes ___ ___ ___ ___ ___ ___

Services

ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 3 1 per computer/ PACS workstation, 1 - printer
5000 Airconditioning HVAC
2189 General LED Lighting
6055 Special: task light, built in Lighting under O/H shelving
2577 PO: Double Power 1 1 - printer
6005 Dimmable Lighting for image viewing
2578 PO: Emergency power, double Power 2 2 per computer workstation
2726 PO: UPS, double Power 2 2 per PACS workstation
1005 Voice / Data outlet: single Communications 1 to laser imager
2582 PO: Single Power 1 to laser imager