The Water Treatment Plant Room is a lockable room for water treatment systems used in dialysis, including booster pumps, particle filters, water softeners, carbon filters and reverse osmosis systems.
Refer to Manufacturer's Specifications for details of Reverse Osmosis (RO) Water Treatment Plant equipment. In particular this equipment will incorporate a heat disinfection function, and water saving features. The Water Treatment Plant Room should be located in close proximity to the Renal Dialysis Unit to permit short tubing runs to each Treatment Bay, and permit staff to monitor and service the water treatment systems.
Special Design Requirements:
- Ventilation, exhaust and/or airconditioning must be deisgned to
accommodate the heat loads of the specified equipment.
- High level sound isolation is required to ensure noise generated
from this room does not invade Treatment spaces
- Structural Engineer's assessment must be sought for floor load
bearing capacity with respect to water treatment and pre-
treatment plant equipment
- Service access will be required aound the perimeter of all plant
equipment
- Pipework and components installed after the water inlet within
this room shall not contain brass or copper
Amendment
24.10.2010 First Draft
03.09.2023 RDS updated
Fabric and outline specifications
ID
Fabric
Material
Finish
Specification
Selection
Remarks
1280
Floor finish
Concrete
Trowel
Sealed
3000
Wall finish
Paint
Acrylic, washable
8040
Door protection
Composite
Prefinished PVC
To door frame
9110
Doors
Solid Core
Paint
1 1/2 leaf
1600mm clear opening, lockable
5021
Ceiling
Plasterboard
Paint, washable
Water resistant, flush set, suspended
min height 2400mm; water resistant drop in tile ceiling also acceptable
2155
Skirting
Concrete
Sealed
Coved concrete to 150 AFFL
2767
Cornice
Plasterboard
Paint
Square set
8010
Door protection
Composite
Prefinished PVC
Protection plate to 900mm AFFL
Fittings and Furniture (FF)
ID
Description
Category
Group
Qty
Selection / Remarks
1050
Bench: laminate
Furniture/ Fitting
1
1
work bench
21680
Stool: adjustable, mobile
Furniture/ Fitting
3
1
under bench
Fixtures, Equipment and associated Services (FE)
ID
Description
Grp
Qty
Ele
Data
CdW
HtW
WmW
Tap
Dns
Gas
Selection / Remarks
42295
Pump: pressure booster
3
2
yes
___
___
___
___
___
___
___
as needed to achieve required water pressure
61295
Water treatment plant
3
3
yes
___
yes
___
___
___
yes
___
RO Plant; details according to Manufacturer's Specifications
Services
ID
Description
Service Category
Qty
Selection / Remarks
1002
Alarm
Communications
1
to Staff Station - Renal Unit for Plant Equipment status/ malfunction
4010
Cold water: outlet
Hydraulics
1
inlet for RO Water Treatment Plant Equipment
4033
Floor waste
Hydraulics
1
floor waste must be capable of high flow rates and high temperature water (up to 95 degrees C) from the RO Water Plant
5000
Airconditioning
HVAC
A/C & exhaust system to accommodate heat loads generated by plant eqeuipment
5019
Exhaust
HVAC
heat extraction will be required
2189
General LED
Lighting
2578
PO: Emergency power, double
Power
4
for use of hand tools in the room, on a separate circuit
2587
PO: Special: for equipment
Power
1