1 Bed Room - Standard, 18m2, Outboard Ensuite

Room Code WTPL-I
Net Room Area Briefed 15
Hours of Operation 24 Hours
Occupancy 1 - 2
Description / Special Requirements The Water Treatment Plant Room is a lockable room for water treatment systems used in dialysis, including booster pumps, particle filters, water softeners, carbon filters and reverse osmosis systems. Refer to Manufacturer's Specifications for details of Reverse Osmosis (RO) Water Treatment Plant equipment. In particular this equipment will incorporate a heat disinfection function, and water saving features. The Water Treatment Plant Room should be located in close proximity to the Renal Dialysis Unit to permit short tubing runs to each Treatment Bay, and permit staff to monitor and service the water treatment systems. Special Design Requirements: - Ventilation, exhaust and/or airconditioning must be deisgned to accommodate the heat loads of the specified equipment. - High level sound isolation is required to ensure noise generated from this room does not invade Treatment spaces - Structural Engineer's assessment must be sought for floor load bearing capacity with respect to water treatment and pre- treatment plant equipment - Service access will be required aound the perimeter of all plant equipment - Pipework and components installed after the water inlet within this room shall not contain brass or copper
Amendment 24.10.2010 First Draft 03.09.2023 RDS updated

Fabric and outline specifications

ID Fabric Material Finish Specification Selection Remarks
1280 Floor finish Concrete Trowel Sealed
3000 Wall finish Paint Acrylic, washable
8040 Door protection Composite Prefinished PVC To door frame
9110 Doors Solid Core Paint 1 1/2 leaf 1600mm clear opening, lockable
5021 Ceiling Plasterboard Paint, washable Water resistant, flush set, suspended min height 2400mm; water resistant drop in tile ceiling also acceptable
2155 Skirting Concrete Sealed Coved concrete to 150 AFFL
2767 Cornice Plasterboard Paint Square set
8010 Door protection Composite Prefinished PVC Protection plate to 900mm AFFL

Fittings and Furniture (FF)

ID Description Category Group Qty Selection / Remarks
1050 Bench: laminate Furniture/ Fitting 1 1 work bench
21680 Stool: adjustable, mobile Furniture/ Fitting 3 1 under bench

Fixtures, Equipment and associated Services (FE)

ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
42295 Pump: pressure booster 3 2 yes ___ ___ ___ ___ ___ ___ ___ as needed to achieve required water pressure
61295 Water treatment plant 3 3 yes ___ yes ___ ___ ___ yes ___ RO Plant; details according to Manufacturer's Specifications

Services

ID Description Service Category Qty Selection / Remarks
1002 Alarm Communications 1 to Staff Station - Renal Unit for Plant Equipment status/ malfunction
4010 Cold water: outlet Hydraulics 1 inlet for RO Water Treatment Plant Equipment
4033 Floor waste Hydraulics 1 floor waste must be capable of high flow rates and high temperature water (up to 95 degrees C) from the RO Water Plant
5000 Airconditioning HVAC A/C & exhaust system to accommodate heat loads generated by plant eqeuipment
5019 Exhaust HVAC heat extraction will be required
2189 General LED Lighting
2578 PO: Emergency power, double Power 4 for use of hand tools in the room, on a separate circuit
2587 PO: Special: for equipment Power 1 3 phase, according to Manufacturer's specifications
2587 PO: Special: for equipment Power 2 pumps, as required