1 Bed Room - Intensive Care, Isolation - Negative Pressure, 25m2

Print
Edit it in Health Facility Briefing System (HFBS)
Edit this room data or print a PDF using the HFBS - Health Facility Briefing System. Customise this room data for your project, or add it to an existing health facility brief in HFBS Briefing Module. Edit Briefing
Room Layout Sheet
Download a PDF Room Layout Sheet (RLS) for this standard component. Free View
Other Files
Buy an editable Revit Room Layout Sheet (RLS) for this standard component. $64.99
Online Room Data Sheet
Room Code 1BR-ICU-IS-N-25-I
Net Room Area Briefed 25
Hours of Operation 24 Hours
Occupancy 1 patient, 1-2 visitors, Up to 6-8 staff
Description / Special Requirements An enclosed single Bed Bay for a patient requiring critical care nursing and medical treatment, suitable for Levels 5 & 6 health care facilities. Visual access to Staff Station is required. Integral venetians or smart glass on internal observation windows are required for patient privacy. Maximum natural light is required to patient beds. A staff write-up bay may be located immediately adjacent to the room entry. Acoustics: Acoustic privacy is required. Cardiac Protected Electrical Area
Amendment
ID Fabric Material Finish Specification Selection Remarks
1000 Floor finish Vinyl Standard slip resistant Seamless, coved
3000 Wall finish Paint Acrylic, washable
5010 Ceiling Plasterboard Paint, washable Flush set, suspended
1253 Observation Alum/ Toughened glass Powdercoat Internal window, double glazed with integral venetians; to write-up bay walls
7001 Windows natural light & outlook desirable
3022 Wall finish Resinate, 6mm Prefinished Splashback to basin
6170 Doors Alum/ Toughened glass Powdercoat/ Paint Triple leaf, fully glazed, sliding
2000 Skirting Vinyl Prefinished Floor vinyl coved, 150mmH
2767 Cornice Plasterboard Paint Square set
ID Description Category Group Qty Selection / Remarks
1090 Bench: laminate, free standing Furniture/ Fitting 3 1
1252 Blind: Venetian integral Furniture/ Fitting 1 3 to internal & external windows; internal observation window, 2-way control; smart glass also acceptable for internal window
2610 Chair: visitor, stackable Furniture/ Fitting 3 1
2926 Dispenser: hand sanitiser Furniture/ Fitting 2 1
4600 Curtain track: bed screen Metalwork 1 1
5000 Curtain: bed screen Furniture/ Fitting 3 1
6152 Dispenser: disposable glove Furniture/ Fitting 2 1 near entry
6154 Dispenser: paper/ hand towel Furniture/ Fitting 2 1 to basin
6158 Dispenser: soap antiseptic Furniture/ Fitting 2 1 to basin
8291 Air flowmeter MEQ - General 3 2 to patient supply unit
8297 Bracket: suction bottle MEQ - General 2 4 to patient supply unit
8309 Oxygen flowmeter MEQ - General 3 4 to patient supply unit
8318 Suction adapter MEQ - General 3 4 to patient supply unit
8321 Suction bottle MEQ - General 3 4 to patient supply unit
8332 Table: overbed MEQ - Furniture 3 1
8404 Bracket: sharps disposal MEQ - General 2 1
8593 Bracket: patient monitor MEQ - General 2 1
8594 Linen carrier: dirty, single MEQ - Furniture 3 1
8724 Trolley: multi-purpose MEQ - Furniture 3 1
8608 Waste bin: clinical, 120 litres MEQ - Furniture 3 1
9117 Sharps disposal: wall mounted, 7L MEQ - General 2 1
10061 Waste bin: General, 20 Litres Furniture/ Fitting 3 1
21700 Stool: adjustable, mobile, high Furniture/ Fitting 3 1 for staff
23410 Bracket: television, wall mount Metalwork 2 1
ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
3031 Television: flat screen 3 1 yes ___ ___ ___ ___ ___ ___ ___
3100 Basin: scrub, Type A 1 1 ___ ___ yes ___ yes yes yes ___
8472 Infusion pump: syringe 3 4 yes opt ___ ___ ___ ___ ___ ___ Qty TBC by project
8733 Bed: ICU, electric 3 1 yes opt ___ ___ ___ ___ ___ ___
8758 Sequential compression device 3 1 yes ___ ___ ___ ___ ___ ___ ___
8988 Infusion pump: enteral feeding 3 1 yes opt ___ ___ ___ ___ ___ ___ Qty TBC by project
8989 Infusion pump: single channel 3 2 yes opt ___ ___ ___ ___ ___ ___ Qty TBC by project
8485 Monitor: physiologic, critical care 3 1 yes yes ___ ___ ___ ___ ___ ___
8764 Chair: recliner, electric 3 1 yes ___ ___ ___ ___ ___ ___ ___
8788 Supply unit: ceiling, tandem, double arm 2 1 yes yes ___ ___ ___ ___ ___ ___
9005 Ventilator: adult/ paediatric 3 1 yes yes ___ ___ ___ ___ ___ ___
9456 Light: procedure, single, ceiling mounted 2 1 yes ___ ___ ___ ___ ___ ___ ___ optional, could be part of the patient supply unit configurations
10132 Clock: master clock 3 1 yes opt ___ ___ ___ ___ ___ ___
15985 Dialysis station 1 1 ___ ___ yes ___ ___ yes yes ___
40404 Tapware: sensor 1 1 yes ___ yes yes yes ___ ___ ___ straight spout
54520 Telephone: handset, handsfree 3 1 ___ yes ___ ___ ___ ___ ___ ___ wall phone
ID Description Service Category Qty Selection / Remarks
1006 Voice / Data outlet: double Communications 3 1- wall, 2- patient supply unit
2559 IPTV Communications 1
5000 Airconditioning HVAC
2242 General LED: colour corrected Lighting
6060 Special: night lights Lighting
7000 Oxygen (O2) Medical Gases 4 to patient supply unit
7020 Medical Air (MA) Medical Gases 2 to patient supply unit
7040 Suction Medical Gases 4 to patient supply unit
8000 Patient to Staff call Nurse Call 1 + indicator button & light; to patient supply unit
8005 Patient call handset Nurse Call 1 call button on the handset
8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light; to patient supply unit
8080 Emergency call Nurse Call 1 + indicator button & light; to patient supply unit
2577 PO: Double Power 1 1- wall
2576 PO: Cleaner Power 1
9030 Cardiac protected/ IPS Power
2724 Direct connection: Emergency power Power 3 1 - for sensor operated tapware; 1- procedure light, 1- patient supply unit
2723 PO: Cardiac Protected/IPS, single Power 24 to patient supply unit
1005 Voice / Data outlet: single Communications 1 to wall phone
1080 Clock: master clock Communications 1 battery/ POE/ electrical connection TBC
4045 Reverse osmosis (RO) water outlet Hydraulics 1 to dialysis station
2578 PO: Emergency power, double Power 1 to dialysis station
2582 PO: Single Power 2 to recliner chair, 1- TV
2761 Direct connection: Tool Air Medical Gases 1 to patient supply unit (for brakes)
4037 Tundish drain Hydraulics 1 to dialysis station
7010 Nitrous Oxide (N2O) Medical Gases 1 optional; to patient supply unit
7070 Scavenge Medical Gases 1 optional; to patient supply unit
5050 Pressure: negative HVAC
0 0