Room Code | 2BR-MH-32-I |
Net Room Area Briefed | 32 |
Hours of Operation | 24 Hours |
Occupancy | 2 patient, 1 - 2 visitors, 1 - 2 staff intermittently |
Description / Special Requirements | A 2 Bed Room for general mental health patients; natural light and outlook is essential; The room is to be internally lockable with a master keyed lock from the outside; All fittings are to have a breaking strain of not more than 15kg. All glazing (including external windows) is to comply with standards for Mental Health Facilities. The 2 Bed Room - Mental Health may vary in configuration to suit different Ensuite options including: - 2 BR-MH-A-U Inboard Ensuite - 2 BR-MH-B-U Shared Ensuite with access off the corridor - 2 BR-MH-D-U Back to Back Ensuites Additional Design Considerations: - Fittings and Furniture: . removable drawers must not to be installed . hooks are not recommended, however if hooks are required, they must be collapsible with a breaking strain of not more than 15kg - Door & Joinery Hardware . door hardware and joinery hardware must not provide ligature points -Windows and frames . windows must comply with relevant glazing safety standards . window frames must ensure that glazing will stay in place in the event of an attack; the window must prevent escape after being broken Acoustics: Acoustic privacy is required. Body Protected Electrical Area |
Amendment | 24.10.2010 First Draft 22.02.2016 Document review 20.01.2023 RDS reviewed 03.01.2025 Area revised from 30m2 to 32m2. Description, Fabrics, FF, FE, Services modified |
ID | Fabric | Material | Finish | Specification | Selection | Remarks |
7001 | Windows | natural light & outlook essential | ||||
3000 | Wall finish | Paint | Acrylic, washable | |||
9006 | Doors | Solid Core/ Safety glass | Paint | Single leaf, observation panel | 1200mm clear inward & outward opening; lockable; glazing with integral venetians,control to corridor side; sensor to top of door; no ligature points | |
3092 | Wall protection | MDF | Laminate | Bed protection wall panel | ||
2767 | Cornice | Plasterboard | Paint | Square set | ||
5040 | Ceiling | Fibre cement | Paint, washable | Flush set, suspended | ||
1475 | Ceiling | Laminate | Prefinished | Bulkhead | above wardrobes | |
1010 | Floor finish | Vinyl | Cushioned | Seamless, coved | carpet also acceptable | |
2000 | Skirting | Vinyl | Prefinished | Floor vinyl coved, 150mmH | MDF skirting if carpet used | |
3067 | Wall finish | Laminate | Prefinished | for TV where required |
ID | Description | Category | Group | Qty | Selection / Remarks |
690 | Bed: domestic, single | Furniture/ Fitting | 3 | 2 | heavy |
1252 | Blind: Venetian integral | Furniture/ Fitting | 1 | 2 | to external window & door glazing; blind control to door glazing outside the room |
5910 | Desk: built in | Furniture/ Fitting | 1 | 2 | laminate |
9814 | Chair | Funiture/ Fitting | 3 | 2 | suitable for mental health use |
23410 | Bracket: television, wall mount | Metalwork | 1 | 2 | vandal proof |
20012 | Shelving unit: fixed shelves | Furniture/ Fitting | 1 | 2 | door height |
2972 | Velcro board | Furniture/ Fitting | 2 | 1 | or frameless fixed artwork; optional |
22690 | Table: bedside | Furniture/ Fitting | 3 | 2 | fixed to wall |
ID | Description | Grp | Qty | Ele | Data | CdW | HtW | WmW | Tap | Dns | Gas | Selection / Remarks |
3031 | Television: flat screen | 3 | 2 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | TV should be inside a recessed vandal proof cabinet |
ID | Description | Service Category | Qty | Selection / Remarks |
2576 | PO: Cleaner | Power | 1 | |
2582 | PO: Single | Power | 13 | 4 per bed at bedhead; 1 per desk; 1 - on wall; 1 per TV, vandal proof |
8010 | Staff/ Nurse assist call | Nurse Call | 1 | + indicator button & light |
8000 | Patient to Staff call | Nurse Call | 2 | + indicator buttons & light; 1 per bed |
2189 | General LED | Lighting | ||
5000 | Airconditioning | HVAC | with vandal proof outlet | |
8080 | Emergency call | Nurse Call | 1 | |
10005 | Duress alarm | Security | 1 | |
9040 | Body protected | Power | ||
1087 | Special: reading, vandal proof | Lighting | 2 | may be ceiling recessed |
6060 | Special: night lights | Lighting | vandal proof | |
2559 | IPTV | Communications | 2 |