6 Bed Room - Standard, 75m2

Print
Edit it in Health Facility Briefing System (HFBS)
Edit this room data or print a PDF using the HFBS - Health Facility Briefing System. Customise this room data for your project, or add it to an existing health facility brief in HFBS Briefing Module. Edit Briefing
Room Layout Sheet
Download a PDF Room Layout Sheet (RLS) for this standard component. Free View
Other Files
Buy an edible Revit Room Layout Sheet (RLS) for this standard component. $64.99
Online Room Data Sheet
Room Code 6BR-ST-75-I
Net Room Area Briefed 75
Hours of Operation 24 Hours
Occupancy Up to 6 patients; 1-2 visitors each; 1-2 staff
Description / Special Requirements A 6 Bed Room will accommodate six patients with similar nursing needs for the delivery of nursing and medical care and treatment. Each space will be individually curtained and allow for treatment of patients either in bed or sitting beside the bed in a comfortable chair; natural light and outlook is essential; patients require the ability to view out of the window from either the chair or bed. Each room is to have direct access to a staff handwash basin within the room, and close access to patient toilet and shower facilities. Acoustics: Acoustic privacy is required. Body Protected electrical area
Amendment 19.05.2022 First Issue
ID Fabric Material Finish Specification Selection Remarks
1000 Floor finish Vinyl Standard slip resistant Seamless, coved
2000 Skirting Vinyl Prefinished Floor vinyl coved, 150mmH
3092 Wall protection MDF Laminate Bed protection wall panel
8010 Door protection Composite Prefinished PVC Protection plate to 900mm AFFL
1045 Floor finish Vinyl, non slip Textured Seamless, coved under basin
3067 Wall finish Laminate Prefinished wall panels
5010 Ceiling Plasterboard Paint, washable Flush set, suspended
7001 Windows natural light & outlook essential
8040 Door protection Composite Prefinished PVC To door frame
4031 Wall protection Composite Prefinished PVC Corner guards to 1500mm AFFL as required; other heights also acceptable as per project standardisation
3000 Wall finish Paint Acrylic, washable
2767 Cornice Plasterboard Paint Square set
3022 Wall finish Resinate, 6mm Prefinished Splashback integral with basin
9127 Doors Solid Core/ Safety glass Paint 1 1/2 leaf, observation panel Min. 1350mm clear opening; 1400mm clear opening ideal
ID Description Category Group Qty Selection / Remarks
8291 Air flowmeter MEQ - General 3 6 medical air
1252 Blind: Venetian integral Furniture/ Fitting 1 1 to external window; roller or vertical blinds also acceptable
8297 Bracket: suction bottle MEQ - General 2 6
4600 Curtain track: bed screen Metalwork 1 6
5000 Curtain: bed screen Furniture/ Fitting 3 6
2926 Dispenser: hand sanitiser Furniture/ Fitting 2 1
6152 Dispenser: disposable glove Furniture/ Fitting 2 1 near basin
6154 Dispenser: paper/ hand towel Furniture/ Fitting 2 1 to basin
6158 Dispenser: soap antiseptic Furniture/ Fitting 2 1 to basin
8322 Locker: bedside MEQ - Furniture 3 6 mobile, 2 lockable top drawers
8332 Table: overbed MEQ - Furniture 3 6
8309 Oxygen flowmeter MEQ - General 3 6
8318 Suction adapter MEQ - General 3 6
8321 Suction bottle MEQ - General 3 6
2655 Chair: visitor Furniture/ Fitting 3 6
8605 Waste bin: clinical, 20 litres MEQ - Furniture 3 1
8306 IV pole: mobile MEQ - General 3 6
24102 Waste bin: general Furniture/ Fitting 3 1 to basin; foot pedal operated
ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
40404 Tapware: sensor 1 1 yes ___ yes yes yes ___ ___ ___ straight spout; optional; elbow action lever taps also acceptable
7266 Basin: with integral vanity 1 1 ___ ___ yes ___ yes yes yes ___ Type D
54510 Telephone: handset, standard 3 6 ___ yes ___ ___ ___ ___ ___ ___ optional
8734 Bed: inpatient, electric, with foam mattress 3 6 yes ___ ___ ___ ___ ___ ___ ___
ID Description Service Category Qty Selection / Remarks
9040 Body protected Power
2576 PO: Cleaner Power 1
2579 PO: Emergency power, single Power 24 4/ bed
2582 PO: Single Power 24 4/ bed
8080 Emergency call Nurse Call 6 + indicator button & light
8010 Staff/ Nurse assist call Nurse Call 6 + indicator button & light
8005 Patient call handset Nurse Call 6 call button & light switch on the handset
8000 Patient to Staff call Nurse Call 6 + indicator button & light
7040 Suction Medical Gases 6 1/ bed
7020 Medical Air (MA) Medical Gases 6 1/ bed
7000 Oxygen (O2) Medical Gases 6 1/ bed
6060 Special: night lights Lighting
6050 Special: reading Lighting 6 up/ down light
2242 General LED: colour corrected Lighting
5000 Airconditioning HVAC
1006 Voice / Data outlet: double Communications 6 1/ bed
2724 Direct connection: Emergency power Power 1 sensor operated tapware, optional
1412 Special: examination downlight Lighting over bed
2582 PO: Single Power 6 6- at low level for patient beds
0 0