Ablution Room (Prayer Room)

Print
Edit it in Health Facility Briefing System (HFBS)
Edit this room data or print a PDF using the HFBS - Health Facility Briefing System. Customise this room data for your project, or add it to an existing health facility brief in HFBS Briefing Module. Edit Briefing
Room Layout Sheet
Download a PDF Room Layout Sheet (RLS) for this standard component. Free View
Other Files
Buy an edible AutoCAD DWG Room Layout Sheet (RLS) for this standard component. $2.99
Buy an edible Revit Room Layout Sheet (RLS) for this standard component. $64.99
Online Room Data Sheet
Room Code ABLU-I
Net Room Area Briefed 13
Hours of Operation 24 Hours
Occupancy 2-10
Description / Special Requirements The Ablution room is an airlock entry prior to the Prayer Room where visitors and patients can wash-up prior to entering the prayer room. Separate Ablution Room shall be provided for male and female and direct access to prayer room is recommeded. Acoustics: Sound attenuation level - medium; acoustic privacy required. Body Protected Electrical Area
Amendment 24.10.2010 First Draft 22.02.2016 Document review 20.02.2023 RDS reviewed
ID Fabric Material Finish Specification Selection Remarks
2145 Skirting Tiles To match floor Coved or floor vinyl coved skirting if vinyl is used
3000 Wall finish Paint Acrylic, washable
4159 Cornice Aluminium Powdercoat Angle flush against wall, in line with ceiling grid
1175 Floor finish Tiles Non-slip Ceramic non-slip vinyl floor also acceptable; recessed tiled basin hob 150x100mm
9001 Doors Solid Core Paint Single leaf 920mm clear
8010 Door protection Composite Prefinished PVC Protection plate to 900mm AFFL
8040 Door protection Composite Prefinished PVC To door frame
3090 Wall finish Tiles Glazed vinyl also acceptable; to 1000mm high around wash-up area
3795 Ceiling Plasterboard Prefinished Water resistant, drop-in tiles, 600x600mm
ID Description Category Group Qty Selection / Remarks
2655 Chair: visitor Furniture/ Fitting 3 1
3400 Coathook Metalwork 1 6
6154 Dispenser: paper/ hand towel Furniture/ Fitting 2 2 to each wash-up station
6156 Dispenser: soap Furniture/ Fitting 2 1 shared by wash-up stations
9813 Mirror: full-height dressing Funiture/ Fitting 1 1
19750 Rack: shoe Furniture/ Fitting 1 1 for 20 pairs of shoes
21699 Stool: fixed Furniture/ Fitting 1 2 marble seat fixed for each washing station
10061 Waste bin: General, 20 Litres Furniture/ Fitting 3 1
ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
480 Ablutions washing outlet & tap 1 2 ___ ___ yes ___ yes yes yes ___ per washing station
3003 Bidet handset 1 2 ___ ___ ___ ___ yes yes ___ ___ washing area; optional
ID Description Service Category Qty Selection / Remarks
4033 Floor waste Hydraulics 2
5000 Airconditioning HVAC
5019 Exhaust HVAC
2576 PO: Cleaner Power 1
2189 General LED Lighting
0 0