Edit it in Health Facility Briefing System (HFBS) | |||
---|---|---|---|
Edit this room data or print a PDF using the HFBS - Health Facility Briefing System. Customise this room data for your project, or add it to an existing health facility brief in HFBS Briefing Module. | Edit Briefing |
Room Layout Sheet | |||
---|---|---|---|
Download a PDF Room Layout Sheet (RLS) for this standard component. | Free | View |
Other Files | |||
---|---|---|---|
Buy an edible AutoCAD DWG Room Layout Sheet (RLS) for this standard component. | $2.99 | ||
Buy an edible Revit Room Layout Sheet (RLS) for this standard component. | $64.99 |
Online Room Data Sheet |
---|
Room Code | ANRM-I |
Net Room Area Briefed | 6 |
Hours of Operation | 24 Hours |
Occupancy | 1 - 2 |
Description / Special Requirements | Anteroom or airlock associated with an Isolation room for maintenance of air pressurisation and for staff and visitors to change and dispose of protective gear used on entering or exit; a staff handwashing basin will be located within the room; glazing is recommended for patient visibility. Pressurisation - negative or positive depending on type of Isolation room. An air pressure monitoring device may be included to identify the room pressure. Body Protected electrical area |
Amendment | 24.10.2010 First Draft 01.09.2014 General revisions 28.10.2014 Modification to Room Fabric, FF, Services 07.06.2019 Room area updated 03.15.2022 Modification to FF |
ID | Fabric | Material | Finish | Specification | Selection | Remarks |
5010 | Ceiling | Plasterboard | Paint, washable | Flush set, suspended | ||
3022 | Wall finish | Resinate, 6mm | Prefinished | Splashback | to basin; other smooth impervious finish also acceptable | |
3000 | Wall finish | Paint | Acrylic, washable | |||
1000 | Floor finish | Vinyl | Standard slip resistant | Seamless, coved | ||
8010 | Door protection | Composite | Prefinished PVC | Protection plate to 900mm AFFL | ||
9007 | Doors | Solid Core/ Safety glass | Paint | Single leaf, half glazed | 920mm clear opening, self closer; integral venetian to obs panel of internal door required if leading to patient bedroom | |
2767 | Cornice | Plasterboard | Paint | Square set | ||
2000 | Skirting | Vinyl | Prefinished | Floor vinyl coved, 150mmH | ||
8040 | Door protection | Composite | Prefinished PVC | To door frame |
ID | Description | Category | Group | Qty | Selection / Remarks |
2926 | Dispenser: hand sanitiser | Furniture/ Fitting | 2 | 1 | |
3400 | Coathook | Metalwork | 1 | 2 | on wall |
6152 | Dispenser: disposable glove | Furniture/ Fitting | 2 | 1 | |
6154 | Dispenser: paper/ hand towel | Furniture/ Fitting | 2 | 1 | to basin |
6158 | Dispenser: soap antiseptic | Furniture/ Fitting | 2 | 1 | to basin |
8594 | Linen carrier: dirty, single | MEQ - Furniture | 3 | 1 | |
5897 | Cabinet: PPE | Furniture/ Fitting | 1 | 1 | |
8607 | Waste bin: clinical, 50 litres | MEQ - Furniture | 3 | 1 | |
10061 | Waste bin: General, 20 Litres | Furniture/ Fitting | 3 | 1 |
ID | Description | Grp | Qty | Ele | Data | CdW | HtW | WmW | Tap | Dns | Gas | Selection / Remarks |
2800 | Basin: handwash, Type B | 1 | 1 | ___ | ___ | yes | ___ | yes | yes | yes | ___ | |
40404 | Tapware: sensor | 1 | 1 | yes | ___ | yes | yes | yes | ___ | ___ | ___ | straight spout |
ID | Description | Service Category | Qty | Selection / Remarks |
2724 | Direct connection: Emergency power | Power | 1 | sensor operated tapware |
2576 | PO: Cleaner | Power | 1 | |
2190 | Air pressure monitoring device | HVAC | optional | |
5015 | Ventilation | HVAC | ||
5019 | Exhaust | HVAC | to negative pressure rooms | |
5000 | Airconditioning | HVAC | no A/C provided to anteroom requiring negative pressure; exhaust only to achieve negative pressure | |
2189 | General LED | Lighting |