Room Code | CHST-F-G-I |
Net Room Area Briefed | 40 |
Hours of Operation | 24 Hours |
Occupancy | Up to 15 |
Description / Special Requirements | Staff Change areas are provided for staff to change into appropriate work clothing, to store their street clothing and to perform personal ablutions. Secure storage for personal property will be required. Change Rooms should be divided into Male and Female areas on a proportional basis. Showers and Toilets will be included within the general Staff Change area. Secured, staff only access to Change Rooms is required. The area may increase according to the number of staff showers/ toilets and lockers to be accommodated; Allow an additional 2 m2 for each additional toilet, 1 m2 for each additional basin, and 0.5 m2 for each additional locker. Acoustics: Sound attenuation level - medium; acoustic privacy required. |
Amendment | 24.10.10, - First Draft 05.05.11, - FF & Services modified |
ID | Fabric | Material | Finish | Specification | Selection | Remarks |
3000 | Wall finish | Paint | Acrylic, washable | |||
8000 | Door protection | Vinyl | Prefinished | Kickplate, 300mm high | ||
9001 | Doors | Solid Core | Paint | Single leaf | 910mm clear; Secure staff only access | |
6025 | Cornice | Aluminium | Powdercoat | shadow line | ||
3080 | Wall finish | Tiles | Glazed | Full height | to wet areas; vinyl also acceptable | |
3085 | Wall finish | Tiles | Glazed | Splashback | vinyl also acceptable | |
1175 | Floor finish | Tiles | Non-slip | Ceramic | non slip vinyl floor also acceptable | |
5060 | Ceiling | Acoustic | Prefinished | Drop-in tiles, 600x1200 | ||
2145 | Skirting | Tiles | To match floor | Coved | or floor vinyl coved skirting |
ID | Description | Category | Group | Qty | Selection / Remarks |
530 | Basin vanity top | Furniture/ Fitting | 1 | 1 | with integral upturn |
1000 | Bench seat | Furniture/ Fitting | 1 | 2 | under lockers |
1000 | Bench seat | Furniture/ Fitting | 1 | 1 | to shower cubicle |
3350 | Clock: battery operated | Furniture/ Fitting | 3 | 1 | |
3400 | Coathook | Metalwork | 1 | 5 | 1 to each cubicle |
4800 | Curtain track: shower | Metalwork | 1 | 1 | ro shower cubicle |
5300 | Curtain: shower | Furniture/ Fitting | 3 | 1 | |
6154 | Dispenser: paper/ hand towel | Furniture/ Fitting | 2 | 2 | |
6156 | Dispenser: soap | Furniture/ Fitting | 2 | 3 | 1 between 2 basins |
6160 | Dispenser: toilet paper | Furniture/ Fitting | 1 | 4 | |
12509 | Locker: 2 tier | Furniture/ Fitting | 3 | 41 | 82 compartments; may also use 3 tier or 4 tier lockers |
13700 | Mirror | Metalwork | 1 | 2 | above basin |
13700 | Mirror | Metalwork | 1 | 1 | dressing |
19100 | Waste bin: sanitary | Furniture/ Fitting | 3 | 4 | |
20055 | Partitions: shower | Furniture/ Fitting | 1 | 1 | |
20650 | Soap/ shampoo holder | Furniture/ Fitting | 1 | 1 | to shower cubicle |
23610 | Partitions: toilet | Furniture/ Fitting | 1 | 4 | |
24100 | Waste bin: paper, 20 Litre | Furniture/ Fitting | 3 | 1 |
ID | Description | Grp | Qty | Ele | Data | CdW | HtW | WmW | Tap | Dns | Gas | Selection / Remarks |
3003 | Bidet handset | 1 | 4 | ___ | ___ | ___ | ___ | yes | yes | ___ | ___ | |
3120 | Basin: vanity | 1 | 4 | ___ | ___ | yes | ___ | yes | yes | yes | ___ | every 2nd basin is optional |
47500 | Shower: fixed rose | 1 | 1 | ___ | ___ | yes | ___ | yes | yes | yes | ___ | |
55600 | Toilet suite: standard | 1 | 4 | ___ | ___ | yes | ___ | ___ | yes | yes | ___ |
ID | Description | Service Category | Qty | Selection / Remarks |
4033 | Floor waste | Hydraulics | 6 | |
5000 | Airconditioning | HVAC | ||
5019 | Exhaust | HVAC | to toilet/ shower area | |
2189 | General LED | Lighting | ||
2587 | PO: Special: for equipment | Power | 1 | for hair dryer & shaver use only; to comply with relevant electric safety guidelines |