Room Code COEQ-12-I
Net Room Area Briefed 12
Hours of Operation 24 Hours
Occupancy N/A
Description / Special Requirements A secure room for computer equipment modules associated with imaging equipment, also known as a Computer Equipment Room. The room will be located adjacent to the Imaging Procedure room or the Control Room. Modules which may be installed in this room include control cabinets, power cabinets, transformer cabinet and heat exchange units. Room temperature must be maintained for heat generating equipment. Cable ducts from Procedure Room and the Technical Equipment Room may be required. Special Design Requirements: - Computer equipment may require protection from power surges and spikes - Consideration should be given to provision of an uninterruptible power supply where loss of data input may compromise patient care or patient information - The computer equipment room should be sized and equipment installed to manufacturer's requirements - A raised access floor may be required for cabling access
Amendment 24.10.2010 First Draft 06.05.2011 Services Remarks modified 30.03.2017 Description & Services updated 02.07.2019 Room name, room size & rom code updated 31.05.2023 RDS reviewed
ID Fabric Material Finish Specification Selection Remarks
1000 Floor finish Vinyl Standard slip resistant Seamless, coved
2000 Skirting Vinyl Prefinished Floor vinyl coved, 150mmH
4159 Cornice Aluminium Powdercoat Angle flush against wall, in line with ceiling grid
3000 Wall finish Paint Acrylic, washable
9001 Doors Solid Core Paint Single leaf 920mm clear opening, lockable
1219 Door Protection Composite Prefinished PVC Kickplate, 300mm high
5062 Ceiling Acoustic Prefinished Drop-in tiles, 600x600 mm
ID Description Category Group Qty Selection / Remarks
ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
ID Description Service Category Qty Selection / Remarks
2502 Clean Agent Gas Suppression System Fire Services
5000 Airconditioning HVAC
2189 General LED Lighting
9029 Electrical Isolator: 3PH+N Power 1 connected to imaging equipment (as applicable), please refer to manufacturer's requirements
11505 Floor duct for power & data Services Ducts 1 connected to imaging equipment (as applicable), please refer to manufacturer's requirements
12030 Lead lining Shielding 1 as applicable
2556 Trunking: 200mm x 70mm Electrical Installations 1 connected to imaging equipment (as applicable), please refer to manufacturer's requirements
4015 Chilled water supply Hydraulics 1 optional, to match with manufacturer's requirements
4030 Drainage Hydraulics 1 optional, to match with manufacturer's requirements