Room Code DISP-10-I
Net Room Area Briefed 10
Hours of Operation 24 Hours
Occupancy 1 - 2 intermittently
Description / Special Requirements The Disposal Room provides for the temporary holding of medical waste, general waste, sharps, soiled linen and recyclables prior to removal. The Disposal Room should be located in close proximity to a handwashing basin or be provided within the room (optional) if waste will be handled in this area. The room should be lockable.
Amendment 24.10.2010 First Draft 03.09.2014 Description, Fabric and FF updated 30.11.2014 Room Fabric and Services modified
ID Fabric Material Finish Specification Selection Remarks
9001 Doors Solid Core Paint Single leaf 1100mm clear opening, lockable; optional 1 1/2 leaf door & glazed viewing panel to door
1000 Floor finish Vinyl Standard slip resistant Seamless, coved
5030 Ceiling Plasterboard Prefinished Drop-in tiles, 600x1200 mm
8010 Door protection Composite Prefinished PVC Protection plate to 900 AFFL
8040 Door protection Composite Prefinished PVC To door frame
2000 Skirting Vinyl Prefinished Floor vinyl coved, 150mmH
3000 Wall finish Paint Acrylic, washable
3040 Wall finish Vinyl Prefinished Wall vinyl to 1200AFFL
6025 Cornice Aluminium Powdercoat shadow line
ID Description Category Group Qty Selection / Remarks
5830 Dispenser: antiseptic hand rub Furniture/ Fitting 2 1
6152 Dispenser: disposable glove Furniture/ Fitting 2 1 optional
6154 Dispenser: paper/ hand towel Furniture/ Fitting 2 1 to hand basin, if provided
6156 Dispenser: soap Furniture/ Fitting 2 1 to hand basin, if provided
23925 Trolley: soiled linen collection Furniture/ Fitting 3 1
24100 Waste bin: paper, 20 Litre Furniture/ Fitting 3 1 to hand basin, if provided
24102 Waste bin: general Furniture/ Fitting 3 1 240 Litre
24107 Waste bin: cytotoxic Furniture/ Fitting 3 1 in cancer treatment areas as required
24125 Waste bin: clinical Furniture/ Fitting 3 2 240 Litre or waste skip
ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
2800 Basin: handwash, Type B 1 1 ___ ___ yes ___ yes yes yes ___ optional; default = no hand basin; tapware: lever or handsfree
ID Description Service Category Qty Selection / Remarks
5000 Airconditioning HVAC
5019 Exhaust HVAC
2189 General LED Lighting