| Edit it in Health Facility Briefing System (HFBS) | |||
|---|---|---|---|
|
Edit this room data or print a PDF using the HFBS - Health Facility Briefing System. Customise this room data for your project, or add it to an existing health facility brief in HFBS Briefing Module. | Edit Briefing | |
| Room Layout Sheet | |||
|---|---|---|---|
|
|
Download a PDF Room Layout Sheet (RLS) for this standard component. | Free | View |
| Other Files | |||
|---|---|---|---|
|
|
Buy an editable Revit Room Layout Sheet (RLS) for this standard component. | $64.99 | |
| Online Room Data Sheet |
|---|
| Room Code | DISP-5-I |
| Net Room Area Briefed | 5 |
| Hours of Operation | 24 Hours |
| Occupancy | 1 - 2 intermittently |
| Description / Special Requirements | The Disposal Room provides for the temporary holding of clinical waste, general waste, sharps, soiled linen and recyclables prior to removal. The Disposal Room should include a handwashing basin within the room if waste will be handled in this area. The room should be lockable. |
| Amendment | 24.10.10, - First Draft |
| ID | Fabric | Material | Finish | Specification | Selection | Remarks |
| 1000 | Floor finish | Vinyl | Standard slip resistant | Seamless, coved | ||
| 2000 | Skirting | Vinyl | Prefinished | Floor vinyl coved, 150mmH | ||
| 3000 | Wall finish | Paint | Acrylic, washable | |||
| 3040 | Wall finish | Vinyl | Prefinished | Wall vinyl to 1200 AFFL | ||
| 8010 | Door protection | Composite | Prefinished PVC | Protection plate to 900 AFFL | ||
| 8040 | Door protection | Composite | Prefinished PVC | To door frame | ||
| 9001 | Doors | Solid Core | Paint | Single leaf | 920mm clear opening, lockable | |
| 6025 | Cornice | Aluminium | Powdercoat | shadow line | ||
| 5030 | Ceiling | Plasterboard | Prefinished | Drop-in tiles, 600x1200 mm |
| ID | Description | Category | Group | Qty | Selection / Remarks |
| 6154 | Dispenser: paper/ hand towel | Furniture/ Fitting | 2 | 1 | to hand basin, if provided |
| 6156 | Dispenser: soap | Furniture/ Fitting | 2 | 1 | to hand basin, if provided |
| 6157 | Dispenser: medicated hand gel | Furniture/ Fitting | 2 | 1 | |
| 24100 | Waste bin: paper, 20 Litre | Furniture/ Fitting | 3 | 1 | to hand basin, if provided |
| 24102 | Waste bin: general | Furniture/ Fitting | 3 | 1 | 240 Litre |
| 24125 | Waste bin: clinical | Furniture/ Fitting | 3 | 1 | 240 Litre |
| ID | Description | Grp | Qty | Ele | Data | CdW | HtW | WmW | Tap | Dns | Gas | Selection / Remarks |
| 2850 | Basin: handwash, Type C | 1 | 1 | ___ | ___ | yes | ___ | yes | yes | yes | ___ | optional, refer to BHWS-C (sim) |
| ID | Description | Service Category | Qty | Selection / Remarks |
| 5015 | Ventilation | HVAC | ||
| 5019 | Exhaust | HVAC | ||
| 2189 | General LED | Lighting |