Room Code | ENS-BR-B-6-I |
Net Room Area Briefed | 6 |
Hours of Operation | 24 Hours |
Occupancy | 1 patient; 1 staff assisting |
Description / Special Requirements | An Ensuite, Birthing Room is for the patient to wash, shower and use the toilet, either independently or with assistance. The area and layout must accommodate an assisting nurse, and wheelchair access. The Ensuite will have direct access from the Birthing Room. Acoustics: Sound attenuation level - High. Acoustic privacy required. Body Protected Electrical Area Additional Design Requirements: - The shower floor must not have a raised hob - The entrance is to be flush with the adjoining flooring - The door is to be fitted with escape hardware |
Amendment | 23.12.2024 First Draft |
ID | Fabric | Material | Finish | Specification | Selection | Remarks |
3795 | Ceiling | Plasterboard | Prefinished | Water resistant, drop-in tiles, 600x600mm | ||
8010 | Door protection | Composite | Prefinished PVC | Protection plate to 900mm AFFL | ||
9001 | Doors | Solid Core | Paint | Single leaf | 920 clear outward opening, privacy latch, emergency release | |
4159 | Cornice | Aluminium | Powdercoat | Angle flush against wall, in line with ceiling grid | ||
8040 | Door protection | Composite | Prefinished PVC | To door frame | ||
2000 | Skirting | Vinyl | Prefinished | Floor vinyl coved, 150mmH | or other coved skirting to match floor | |
3035 | Wall finish | Vinyl | Prefinished | Wall vinyl full height | other smooth impervious finish also acceptable | |
1020 | Floor finish | Vinyl, non-slip | Safety | Seamless, coved | other non-slip impervious floor finish suitable for barefeet also acceptable |
ID | Description | Category | Group | Qty | Selection / Remarks |
2300 | Chair: shower | Furniture/ Fitting | 3 | 1 | optional |
3400 | Coathook | Metalwork | 1 | 2 | 1 @ 1200 AFFL for wheelchair users |
4800 | Curtain track: shower | Metalwork | 1 | 1 | |
5300 | Curtain: shower | Furniture/ Fitting | 3 | 1 | |
6154 | Dispenser: paper/ hand towel | Furniture/ Fitting | 2 | 1 | |
6156 | Dispenser: soap | Furniture/ Fitting | 2 | 2 | 1 - to basin; 1 - to shower (optional) |
6160 | Dispenser: toilet paper | Furniture/ Fitting | 2 | 1 | |
8400 | Grab rail: WC | Metalwork | 1 | 2 | 1 behind toilet, 1 to side |
8450 | Grab rail: Shower | Metalwork | 1 | 1 | |
8500 | Grab rail: WC, hinged | Metalwork | 1 | 1 | |
10800 | Hook: for IV flasks | Metalwork | 1 | 2 | |
13700 | Mirror | Metalwork | 1 | 1 | over basin |
19100 | Waste bin: sanitary | Furniture/ Fitting | 3 | 1 | |
20603 | Soap/ shampoo holder: recessed | Furniture/ Fitting | 1 | 1 | |
23700 | Towel rail | Metalwork | 1 | 1 | with grab rail strength and fixings |
10061 | Waste bin: General, 20 Litres | Furniture/ Fitting | 3 | 1 | |
9200 | Hook: for catheter bag | Metalwork | 1 | 2 |
ID | Description | Grp | Qty | Ele | Data | CdW | HtW | WmW | Tap | Dns | Gas | Selection / Remarks |
3003 | Bidet handset | 1 | 1 | ___ | ___ | ___ | ___ | yes | yes | ___ | ___ | near toilet; optional |
5603 | Basin: ensuite | 1 | 1 | ___ | ___ | yes | ___ | yes | yes | yes | ___ | may include a vanity |
40402 | Tapware: basin mixer | 1 | 1 | ___ | ___ | yes | yes | yes | ___ | ___ | ___ | basin mounted |
40406 | Tapware: shower mixer | 1 | 1 | ___ | ___ | yes | yes | yes | ___ | ___ | ___ | |
47400 | Shower: hand-held | 1 | 1 | ___ | ___ | yes | ___ | yes | yes | yes | ___ | |
55605 | Toilet suite: patient | 1 | 1 | ___ | ___ | yes | ___ | ___ | yes | yes | ___ |
ID | Description | Service Category | Qty | Selection / Remarks |
8000 | Patient to Staff call | Nurse Call | 2 | + indicator button & light; 1 - shower & 1 - toilet (may be located on drop down rail beside toilet) |
8010 | Staff/ Nurse assist call | Nurse Call | 1 | + indicator button & light |
8080 | Emergency call | Nurse Call | 1 | + indicator button & light |
2577 | PO: Double | Power | 1 | locate near door outside room |
9040 | Body protected | Power | ||
2587 | PO: Special: for equipment | Power | 1 | for hair dryer & shaver use only; to comply with relevant electric safety guidelines |
2189 | General LED | Lighting | ||
5019 | Exhaust | HVAC | for steam/ heat | |
4033 | Floor waste | Hydraulics | 1 | |
5015 | Ventilation | HVAC |