Online Room Data Sheet |
---|
Room Code | ENS-ST-6-I |
Net Room Area Briefed | 6 |
Hours of Operation | 24 Hours |
Occupancy | 1 patient; 1 staff assisting |
Description / Special Requirements | An Ensuite is for a patient to wash, shave, groom themselves, shower and use the toilet, either independently or with assistance. The area and layout must accommodate an assisting nurse, patient lifter and wheelchair access. The Ensuite may vary in configuration to suit different room types including: - Inboard Ensuite, refer to ens-st-a-n - Outboard Ensuite, refer to ens-st-b-n Acoustics: Sound attenuation level - High. Acoustic privacy required. Body Protected Electrical Area Additional Design Requirements: - The shower floor must not have a raised hob - The entrance is to be flush with the adjoining flooring - The door is to be fitted with escape hardware; a sliding door is acceptable |
Amendment | 23.12.2024 First Draft |
ID | Fabric | Material | Finish | Specification | Selection | Remarks |
3795 | Ceiling | Plasterboard | Prefinished | Water resistant, drop-in tiles, 600x600mm | water resistant flush set plasterboard ceiling also acceptable | |
8040 | Door protection | Composite | Prefinished PVC | To door frame | ||
3080 | Wall finish | Tiles | Glazed | Full height | to wet areas; vinyl also acceptable; optional | |
2145 | Skirting | Tiles | To match floor | Coved | or floor vinyl coved skirting if vinyl is used | |
8010 | Door protection | Composite | Prefinished PVC | Protection plate to 900mm AFFL | ||
9001 | Doors | Solid Core | Paint | Single leaf | 920 clear outward opening, privacy latch, emergency release, a sliding door is acceptable | |
1175 | Floor finish | Tiles | Non-slip | Ceramic | non-slip vinyl also acceptable; optional | |
6025 | Cornice | Aluminium | Powdercoat | shadow line |
ID | Description | Category | Group | Qty | Selection / Remarks |
2300 | Chair: shower | Furniture/ Fitting | 3 | 1 | |
3400 | Coathook | Metalwork | 1 | 2 | 1 @ 1200 AFFL for wheelchair users |
4800 | Curtain track: shower | Metalwork | 1 | 1 | |
5300 | Curtain: shower | Furniture/ Fitting | 3 | 1 | |
6152 | Dispenser: disposable glove | Furniture/ Fitting | 2 | 1 | |
6154 | Dispenser: paper/ hand towel | Furniture/ Fitting | 2 | 1 | |
6156 | Dispenser: soap | Furniture/ Fitting | 1 | 1 | |
6160 | Dispenser: toilet paper | Furniture/ Fitting | 2 | 1 | |
8400 | Grab rail: WC | Metalwork | 1 | 1 | may wrap around behind toilet |
8450 | Grab rail: Shower | Metalwork | 1 | 1 | |
8500 | Grab rail: WC, hinged | Metalwork | 1 | 1 | |
10800 | Hook: for IV flasks | Metalwork | 1 | 2 | |
13700 | Mirror | Metalwork | 1 | 1 | over basin |
20603 | Soap/ shampoo holder: recessed | Furniture/ Fitting | 1 | 1 | |
23700 | Towel rail | Metalwork | 1 | 1 | with grab rail strength and fixings |
19100 | Waste bin: sanitary | Furniture/ Fitting | 3 | 1 | |
10061 | Waste bin: General, 20 Litres | Furniture/ Fitting | 3 | 1 | |
9200 | Hook: for catheter bag | Metalwork | 1 | 2 |
ID | Description | Grp | Qty | Ele | Data | CdW | HtW | WmW | Tap | Dns | Gas | Selection / Remarks |
3003 | Bidet handset | 1 | 1 | ___ | ___ | ___ | ___ | yes | yes | ___ | ___ | |
40402 | Tapware: basin mixer | 1 | 1 | ___ | ___ | yes | yes | yes | ___ | ___ | ___ | basin mounted |
40406 | Tapware: shower mixer | 1 | 1 | ___ | ___ | yes | yes | yes | ___ | ___ | ___ | |
47400 | Shower: hand-held | 1 | 1 | ___ | ___ | yes | ___ | yes | yes | yes | ___ | |
55605 | Toilet suite: patient | 1 | 1 | ___ | ___ | yes | ___ | ___ | yes | yes | ___ | |
5603 | Basin: ensuite | 1 | 1 | ___ | ___ | yes | ___ | yes | yes | yes | ___ | may include a vanity |
ID | Description | Service Category | Qty | Selection / Remarks |
4033 | Floor waste | Hydraulics | 1 | |
5000 | Airconditioning | HVAC | ||
5019 | Exhaust | HVAC | for steam/ heat | |
8010 | Staff/ Nurse assist call | Nurse Call | 1 | + indicator button & light |
8080 | Emergency call | Nurse Call | 1 | + indicator button & light |
9040 | Body protected | Power | ||
8000 | Patient to Staff call | Nurse Call | 2 | + indicator button & light; 1 - shower & 1 - toilet (may be located on drop down rail beside toilet) |
2467 | Downlights: LED | Lighting | ||
2587 | PO: Special: for equipment | Power | 1 | for hair dryer & shaver use only; to comply with relevant electric safety guidelines |