Room Code | ECL-14-I |
Net Room Area Briefed | 14 |
Hours of Operation | 24 Hours |
Occupancy | 1 - 2 |
Description / Special Requirements | The Equipment Clean-Up Room is used for cleaning and maintaining of equipment used in the Unit. Storage may be required for holding cleaned equipment and spares. Equipment may also be recharged in this room. Natural light is desirable. |
Amendment | 24.10.10, - First Draft 06.05.11, - FE and Services updated |
ID | Fabric | Material | Finish | Specification | Selection | Remarks |
9004 | Doors | Solid Core/ Glass | Paint | Single leaf, observation panel | 1100mm clear opening, lockable | |
1020 | Floor finish | Vinyl, non-slip | Safety | Seamless, coved | ||
2000 | Skirting | Vinyl | Prefinished | Floor vinyl coved, 150mmH | ||
3000 | Wall finish | Paint | Acrylic, washable | |||
8010 | Door protection | Composite | Prefinished PVC | Protection plate to 900 AFFL | ||
8040 | Door protection | Composite | Prefinished PVC | To door frame | ||
6025 | Cornice | Aluminium | Powdercoat | shadow line | ||
3052 | Wall finish | Vinyl | Prefinished | Wall vinyl to 1500mm AFFL | ||
5021 | Ceiling | Plasterboard | Paint, washable | Water resistant, flush set, suspended |
ID | Description | Category | Group | Qty | Selection / Remarks |
1010 | Bench: stainless steel | Metalwork | 1 | 1 | with wet edge, inset sinks |
4360 | Cupboard: door ht adj. shelves | Furniture/ Fitting | 3 | 2 | optional |
6152 | Dispenser: disposable glove | Furniture/ Fitting | 2 | 1 | |
6154 | Dispenser: paper/ hand towel | Furniture/ Fitting | 2 | 1 | to basin |
6156 | Dispenser: soap | Furniture/ Fitting | 2 | 1 | to basin |
6158 | Dispenser: soap antiseptic | Furniture/ Fitting | 2 | 1 | to basin |
19820 | Shelf: SS, under | Metalwork | 1 | 1 | under bench |
20000 | Shelving unit: adjustable | Furniture/ Fitting | 1 | 1 | over bench |
23950 | Trolley | Furniture/ Fitting | 3 | 3 | optional |
24100 | Waste bin: paper, 20 Litre | Furniture/ Fitting | 3 | 1 | to basin |
24105 | Waste bin: fliptop, 20 Litre | Furniture/ Fitting | 3 | 1 | under bench |
ID | Description | Grp | Qty | Ele | Data | CdW | HtW | WmW | Tap | Dns | Gas | Selection / Remarks |
2800 | Basin: handwash, Type B | 1 | 1 | ___ | ___ | yes | ___ | yes | yes | yes | ___ | Refer to BHWS-B (sim) |
45601 | Hose: spray | 1 | 1 | ___ | ___ | yes | yes | ___ | ___ | ___ | optional | |
49005 | Sink: 500x450x300D | 1 | 2 | ___ | ___ | yes | opt | opt | yes | yes | ___ | hot water |
58200 | Washer sanitiser: utensil | 1 | 1 | yes | ___ | yes | yes | ___ | yes | yes | ___ | optional |
ID | Description | Service Category | Qty | Selection / Remarks |
4000 | Hot water: outlet | Hydraulics | 1 | if utensil washer provided |
4010 | Cold water: outlet | Hydraulics | 1 | if utensil washer provided |
4033 | Floor waste | Hydraulics | 1 | |
5015 | Ventilation | HVAC | ||
5019 | Exhaust | HVAC | ||
2189 | General LED | Lighting | ||
2577 | PO: Double | Power | 2 | |
2587 | PO: Special: for equipment | Power | 1 | if utensil washer provided |