Room Code | GENXR-36-I |
Net Room Area Briefed | 36 |
Hours of Operation | Available 24 Hours |
Occupancy | 1 patient; 1 - 2 staff |
Description / Special Requirements | General X-ray is a room for undertaking general radiographic procedures, which may be located within the Imaging Unit or within an emergency care area. Additional Design Requirements: - Radiation sheilding to walls and glazing as advised by Radiation Consultant - Metal channel struts may be required to the ceiling, depending on equipment to be installed - Cable ducting between the X-ray table, vertical bucky and control area may be required, depending on equipment type and layout - 'X-ray in Use' warning lights will be required outside each entry door - Equipment and services required are to be installed to manufacturer's specifications Body Protected electrical area |
Amendment | 23.12.2024 First Draft |
ID | Fabric | Material | Finish | Specification | Selection | Remarks |
1000 | Floor finish | Vinyl | Standard slip resistant | Seamless, coved | ||
3000 | Wall finish | Paint | Acrylic, washable | |||
9230 | Doors | Solid Core | Paint | Double leaf, with lead shielding | patient entry/ exit; 1400mm (min) clear opening | |
4031 | Wall protection | Composite | Prefinished PVC | Corner guards to 1500mm AFFL | as required; other heights also acceptable as per project standardisation | |
3022 | Wall finish | Resinate, 6mm | Prefinished | Splashback | to basin, other smooth impervious finish also acceptable | |
8040 | Door protection | Composite | Prefinished PVC | To door frame | ||
2000 | Skirting | Vinyl | Prefinished | Floor vinyl coved, 150mmH | ||
9228 | Doors | Solid Core | Paint | Single leaf, with lead sheilding | staff entry to control area; 920mm clear opening; optional | |
8010 | Door protection | Composite | Prefinished PVC | Protection plate to 900mm AFFL | ||
7025 | Observation | Lead glass | Clear | Internal window | to control area | |
6025 | Cornice | Aluminium | Powdercoat | shadow line | ||
5032 | Ceiling | Plasterboard | Prefinished | Drop-in tiles, 600x 600 mm |
ID | Description | Category | Group | Qty | Selection / Remarks |
8291 | Air flowmeter | MEQ - General | 3 | 1 | to services panel |
1090 | Bench: laminate, free standing | Furniture/ Fitting | 3 | 1 | cupboards under; optional |
2150 | Chair: patient | Furniture/ Fitting | 3 | 1 | |
6152 | Dispenser: disposable glove | Furniture/ Fitting | 2 | 1 | |
6154 | Dispenser: paper/ hand towel | Furniture/ Fitting | 2 | 1 | to basin |
6158 | Dispenser: soap antiseptic | Furniture/ Fitting | 2 | 1 | to basin |
8309 | Oxygen flowmeter | MEQ - General | 3 | 1 | to services panel |
8321 | Suction bottle | MEQ - General | 3 | 1 | |
8313 | Rack: lead apron | MEQ - Imaging | 1 | 1 | |
8318 | Suction adapter | MEQ - General | 3 | 1 | |
8297 | Bracket: suction bottle | MEQ - General | 2 | 1 | |
8402 | Footstool: 2-step | MEQ - Furniture | 3 | 1 | |
2926 | Dispenser: hand sanitiser | Furniture/ Fitting | 2 | 1 | |
10061 | Waste bin: General, 20 Litres | Furniture/ Fitting | 3 | 1 |
ID | Description | Grp | Qty | Ele | Data | CdW | HtW | WmW | Tap | Dns | Gas | Selection / Remarks |
54520 | Telephone: handset, handsfree | 3 | 1 | ___ | yes | ___ | ___ | ___ | ___ | ___ | ___ | wall telephone |
2800 | Basin: handwash, Type B | 1 | 1 | ___ | ___ | yes | ___ | yes | yes | yes | ___ | refer to BHWS-B (sim) |
9095 | X-ray unit: chest | 1 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | |
9099 | X-ray table | 1 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | |
9093 | X-ray unit: general purpose, ceiling mounted | 1 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | |
9092 | Control console | 1 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | |
9710 | Clock: digital, electric | 1 | 1 | yes | ___ | ___ | ___ | ___ | ___ | ___ | ___ | |
40404 | Tapware: sensor | 1 | 1 | yes | ___ | yes | yes | yes | ___ | ___ | ___ | |
62400 | IMG: control booth | 1 | 1 | yes | yes | ___ | ___ | ___ | ___ | ___ | ___ | optional, if control area walls are not created |
ID | Description | Service Category | Qty | Selection / Remarks |
2242 | General LED: colour corrected | Lighting | ||
6110 | Downlights: dimmable | Lighting | ||
7000 | Oxygen (O2) | Medical Gases | 1 | patient services panel |
7020 | Medical Air (MA) | Medical Gases | 1 | patient services panel |
7040 | Suction | Medical Gases | 1 | patient services panel |
8010 | Staff/ Nurse assist call | Nurse Call | 1 | patient services panel |
8080 | Emergency call | Nurse Call | 1 | patient services panel |
2582 | PO: Single | Power | 2 | patient services panel |
2577 | PO: Double | Power | 3 | 2- walls; 1- bench |
2579 | PO: Emergency power, single | Power | 2 | patient services panel |
9040 | Body protected | Power | ||
12030 | Lead lining | Shielding | to walls and doors as specified | |
5000 | Airconditioning | HVAC | ||
1040 | Intercom | Communications | 1 | |
1006 | Voice / Data outlet: double | Communications | 3 | 1- patient services panel; 1- bench; 1- control console |
6826 | Trunking: 150mm x 70mm | Electrical Installations | 1 | between x-ray equipment, patient table, chest bucky and control console |
6076 | Special: 'X-ray In Use' lights | Lighting | 1 | |
9029 | Electrical Isolator: 3PH+N | Power | 1 | to x-ray generator cabinet |
11000 | Wall panel | Services Panels | 1 | |
11505 | Floor duct for power & data | Services Ducts | 1 | between x-ray equipment, patient table, chest bucky and control console |
1005 | Voice / Data outlet: single | Communications | 1 | to telephone |
6827 | Cabinet: generator | Power | 1 | |
2682 | PO: Double, UPS (uninterruptible power) | Power | 2 | to control console |
2233 | Direct connection: Emergency power | Power | 1 | sensor tap |
2473 | Power over Ethernet (PoE) | Power | 1 | clock |