Gymnasium, 45m2

Print
Edit it in Health Facility Briefing System (HFBS)
Edit this room data or print a PDF using the HFBS - Health Facility Briefing System. Customise this room data for your project, or add it to an existing health facility brief in HFBS Briefing Module. Edit Briefing
Room Layout Sheet
Download a PDF Room Layout Sheet (RLS) for this standard component. Free View
Other Files
Buy an edible Revit Room Layout Sheet (RLS) for this standard component. $64.99
Online Room Data Sheet
Room Code GYAH-45-I
Net Room Area Briefed 45
Hours of Operation 8am to 6pm daily
Occupancy Up to 4 patients/ hour; up to 3 staff
Description / Special Requirements The Gymnasium provides for patient evaluation, rehabilitation exercise activities, therapy and ambulation training. An external outlook is desirable. The Gym area will require access for wheelchairs and staff handwashing facilties. The equipment to be used in this area will be dependent on the funtion of the gym and the Operational Policy. Acoustics: Acoustic privacy required. Body protected electrical area Special Design Requirements - Floors, walls and ceilings must be structurally able to support exercise and weight training equipment that may be required in the gym
Amendment 24.10.2010 First Draft 02.05.2011 Fabric, FF & Services updated 02.03.2017 Description, Fabric updated 03.09.2023 RDS reviewed
ID Fabric Material Finish Specification Selection Remarks
3000 Wall finish Paint Acrylic, washable
7001 Windows desirable
8010 Door protection Composite Prefinished PVC Protection plate to 900mm AFFL
3022 Wall finish Resinate, 6mm Prefinished Splashback to basin & sink, other smooth impervious finish also acceptable
2000 Skirting Vinyl Prefinished Floor vinyl coved, 150mmH
4159 Cornice Aluminium Powdercoat Angle flush against wall, in line with ceiling grid
5062 Ceiling Acoustic Prefinished Drop-in tiles, 600x600 mm flush set plasterboard acoustic ceiling also acceptable
9127 Doors Solid Core/ Safety glass Paint 1 1/2 leaf, observation panel 1400 mm clear opening, lockable
1000 Floor finish Vinyl Standard slip resistant Seamless, coved
8040 Door protection Composite Prefinished PVC To door frame
ID Description Category Group Qty Selection / Remarks
1050 Bench: laminate Furniture/ Fitting 1 1 optional
2150 Chair: patient Furniture/ Fitting 3 1
2899 Blind: roller Furniture/ Fittings 1 1 to external window if provided; vertical blinds also acceptable
4410 Cupboard: under bench Furniture/ Fitting 1 1 optional
4430 Cupboard: drawer unit Furniture/ Fitting 1 1 under bench, optional
4460 Cupboard: wall mounted Furniture/ Fitting 1 1 over bench, optional
4600 Curtain track: bed screen Metalwork 1 2 to plinth spaces
5000 Curtain: bed screen Furniture/ Fitting 3 2 to plinth spaces
6154 Dispenser: paper/ hand towel Furniture/ Fitting 2 2 to basin & sink (if sink bench provided)
6156 Dispenser: soap Furniture/ Fitting 2 2 to basin & sink (if sink bench provided)
8303 Exercise stairs: static MEQ - Rehabilitation 3 1 optional
13800 Mirror: full length Metalwork 1 2 to one wall
8632 Parallel bars: floor mounted MEQ - Rehabilitation 3 1 removable
8633 Pulley weights: wall mounted MEQ - Rehabilitation 3 1 optional
8398 Trolley: resuscitation MEQ - Furniture 3 1 optional, can be deleted if resuscitation bay is provided nearby
8705 Exercise mat MEQ - Rehabilitation 3 6
8877 Table: mat, 1200mm MEQ - Rehabilitation 3 1
10061 Waste bin: General, 20 Litres Furniture/ Fitting 3 1
ID Description Grp Qty Ele Data CdW HtW WmW Tap Dns Gas Selection / Remarks
2800 Basin: handwash, Type B 1 1 ___ ___ yes ___ yes yes yes ___
10132 Clock: master clock 3 1 yes opt ___ ___ ___ ___ ___ ___
40404 Tapware: sensor 1 1 yes ___ yes yes yes ___ ___ ___ straight spout
40405 Tapware: sink mixer 1 1 ___ ___ yes yes yes ___ ___ ___ to sink if provided; provide hot water
47890 Sink & drainer: single, 930mmL 1 1 ___ ___ yes opt opt yes yes ___ optional
54510 Telephone: handset, standard 3 1 ___ yes ___ ___ ___ ___ ___ ___ wall phone
8767 Defibrillator: with monitor 3 1 yes ___ ___ ___ ___ ___ ___ ___ optional, can be deleted if resuscitation bay is provided nearby
8748 Exercise bicycle 3 1 yes opt ___ ___ ___ ___ ___ ___ optional
9064 Treadmill: exercise, automatic 3 1 yes opt ___ ___ ___ ___ ___ ___ optional
9184 Table: examination/ treatment, rehabilitation, electric 3 1 yes ___ ___ ___ ___ ___ ___ ___
ID Description Service Category Qty Selection / Remarks
1005 Voice / Data outlet: single Communications 1 to wall phone
1006 Voice / Data outlet: double Communications 8 1 to each plinth, optional; 1 - to bench if provided; 5- walls (optional); quantity will be determined by equipment to be used and operational Policy
5000 Airconditioning HVAC
2189 General LED Lighting
8000 Patient to Staff call Nurse Call 2 1 to each plinth space; + indicator button & light
8005 Patient call handset Nurse Call 2 1 to each plinth space; call button on the handset
8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light
8080 Emergency call Nurse Call 1 + indicator button & light
2577 PO: Double Power 9 1 - bench if provided; 1 per plinth space; 6- walls; quantity will be determined by equipment to be used and operational Policy
2576 PO: Cleaner Power 1
9040 Body protected Power
2724 Direct connection: Emergency power Power 1 sensor operated tapware
1080 Clock: master clock Communications 1 battery/ POE/ electrical connection TBC
0 0